Page 61
S5-100U
3.3.3
Installation Guidelines
Non-Floating and Floating Configurations
The S5-100U is powered by its own control circuit. The I/Os are powered by the load circuit. The circuits can either be connected to the same grounding point (non-floating) or galvanically isolated (floating).
Example of a Non-Floating Connection of Digital Modules A 24 V DC load circuit has the same chassis grounding as the control circuit of the CPU.
Central grounding point
PS
CPU L+ M
Common chassis ground M
L+
Load power supply Figure 3-21. Example: Non-Floating Connection of I/Os to the S5-100U
EWA 4NEB 812 6120-02b
3-25
Page 62
Installation Guidelines
S5-100U
The common chassis grounding connection makes it possible for you to use reasonably priced nonfloating I/Os. These modules function according to the following principles. •
Input modules - The ground line, line M (control circuit chassis) is the reference potential. A voltage drop V1 on line affects the input signal level VI.
•
Output modules - Terminal 2 (M) of the terminal block is the reference potential. A voltage drop V2 on the line raises the chassis potential of the output driver and thus reduces the resulting control voltage VCV.
Figure 3-22 shows a simplified connection of the S5-100U with a non-floating external I/O.
+9 V Data GND
VCV
CPU
L+
M
L+
M
24 V DC supply
2
V1
1
VI
V2
Figure 3-22. Simplified Representation of a Non-Floating I/O Connection
3-26
EWA 4NEB 812 6120-02b
Page 63
S5-100U
Installation Guidelines
When you have a non-floating configuration, you must make certain that the voltage drop on cables and does not exceed 1 V. If 1 V is exceeded, the reference potentials could change and the modules could malfunction.
Warning If you use non-floating I/O modules, you must provide an external connection between the chassis ground of the non-floating I/O module and the chassis ground of the CPU.
Example of a Floating Configuration with Digital Modules Floating configuration is required in the following situations. •
When you need to increase interference immunity in the load circuits
•
When load circuits cannot be interconnected
•
When you have AC load circuits
If you have a floating configuration, the PLC's control circuit and the load circuit must be galvanically isolated. Figure 3-23 shows a simplified connection of galvanically isolated I/Os. Central grounding point
PS
CPU
L+
L+ M
M
Load power supply Figure 3-23.
Simplified Representation of a Galvanically Isolated Connection of the I/Os to the S5-100U
EWA 4NEB 812 6120-02b
3-27
Page 64
Installation Guidelines
S5-100U
•
•
•
+9 V Data GND
•
Figure 3-24 shows a simplified schematic for the connection of floating I/O modules.
CPU
1L+ M
L1 N
2L+ •
•
2M
Figure 3-24. A Simplified Representation of a Floating I/O Connection
3-28
EWA 4NEB 812 6120-02b
Page 65
S5-100U
3.4
Installation Guidelines
Wiring Arrangement, Shielding and Measures against Electromagnetic Interference
This section describes the wiring arrangements for bus cables, signal cables, and power supply cables that guarantee the electromagnetic compatibility (EMC) of your installation.
3.4.1
Running Cables Inside and Outside a Cabinet
Dividing the lines into the following groups and running the groups separately will help you to achieve electromagnetic compatibility (EMC). Group A:
Shielded bus and data lines (for programmer, OP, printer, SINEC L1, Profibus, Industrial Ethernet, etc.) Shielded analog lines Unshielded lines for DC voltage 60 V Unshielded lines for AC voltage 25 V Coaxial lines for monitors
Group B:
Unshielded lines for DC voltage > 60 V and 400 V Unshielded lines for AC voltage > 25 V and 400 V
Group C:
Unshielded lines for AC voltage > 400 V
You can use the following table to see the conditions which apply to the running of the various combinations of line groups.
Table 3-3. Rules for Common Running of Lines Group A
Group B
Group C
Group A Group B Group C
Legend for table: Lines can be run in common bundles or cable ducts Lines must be run in separate bundles or cable ducts (without minimum distance) Inside cabinets, lines must be run in separate bundles or cable ducts and outside cabinets but inside buildings, lines must be run on separate cable trays with a gap of a least of 10 cm between lines.
EWA 4NEB 812 6120-02b
3-29
Page 66
Installation Guidelines
3.4.2
S5-100U
Running Cables Outside Buildings
Run lines outside buildings where possible in metal cable supports. Connect the abutting surfaces of the cable supports galvanically with each other and ground the cable supports. When you run cables outdoors, you must observe the regulations governing lightning protection and grounding. Note the general guidelines: Lightning Protection If cables and lines for SIMATIC S5 devices are to be run outside buildings, you must take measures to ensure internal and external lightning protection. Outside buildings run your cables either -
In metal conduits grounded at both ends or In steel-reinforced concrete cable channels
Protect signal lines from overvoltage by using: • •
Varistors or Lightning arresters filled with inert gas
Install these protective elements at the point where the cable enters the building.
Note Lightning protection measures always require an individual assessment of the entire system. If you have any questions, please consult your local Siemens office or any company specializing in lightning protection.
Grounding Make certain that you have sufficient equipotential bonding between the devices.
3-30
EWA 4NEB 812 6120-02b
Page 67
S5-100U
3.4.3
Installation Guidelines
Equipotential Bonding
Potential differences may occur between separate sections of the system if • Programmable controllers and I/Os are connected via non-floating interface modules or • Cables are shielded at both ends but grounded via different sections of the system. Potential differences may be caused, for instance, by differences in the system input voltage. These differences must be reduced by means of equipotential bonding conductors to ensure proper functioning of the electronic components installed. Note the following for equipotential bonding: A low impedance of the equipotential bonding conductor makes equipotential bonding more efficient.
•
If any shielded signal cables connected to earth/protective earth at both ends are laid between the system sections concerned, the impedance of the additional equipotential bonding conductor must not exceed 10 % of the shield impedance.
•
The cross-section of the equipotential bonding conductor must be matched to the maximum compensating currents. The following cross-sections are recommendable: - 16 mm2 copper wire for equipotential bonding line up to 200 m (656.2 ft). - 25 mm2 copper wire for equipotential bonding line over 200 m (656.2 ft).
•
Use equipotential bonding conductors made of copper or zinc-plated steel. Equipotential bonding conductors are to be connected to earth/protective earth via a large contact area and to be protected against corrosion.
•
The equipotential bonding conductor should be laid in such a way as to achieve a relatively small contact area between equipotential bonding conductor and signal cables (see Figure 3-25).
•
Signal line
Equipotential bonding conductor
Figure 3-25. Laying Equipotential Bonding Conductor and Signal Cable
EWA 4NEB 812 6120-02b
3-31
Page 68
Installation Guidelines
S5-100U
3.4.4 Shielding Cables Shielding is a measure to weaken (attenuate) magnetic, electric or electromagnetic interference fields. Interference currents on cable shields are discharged to ground over the shield bar which has a conductive connection to the housing. So that these interference currents do not become a source of noise in themselves, a low-resistance connection to the protective conductor is of special importance. Use only cables with shield braiding if possible. The effectiveness of the shield should be more than 80%. Avoid cables with foil shielding since the foil can easily be damaged by tension and pressure; this leads to a reduction in the shielding effect. As a rule, you should always shield cables at both ends. Only shielding at both ends provides good suppression in the high frequency range. As an exception only, you can connect the shielding at one end. However, this attenuates only the lower frequencies. Shielding at one end can be of advantage in the following cases: • • •
If you cannot run an equipotential bonding conductor If you are transmitting analog signals (e.g. a few microvolts or microamps) If you are using foil shields (static shields).
Always use metallic or metalized connectors for data lines for serial connections. Secure the shield of the data line at the connector housing. Do not connect the shield to the PIN1 of the connector strip! In the case of stationary operation, you are recommended to insulate the shielded cable without interrupt and to connect it to the shield/protective ground bar.
Note If there are potential differences between the earthing points, a compensating current can flow over the shielding that is connected at both ends. For this reason, connect an additional equipotential bonding conductor.
3-32
EWA 4NEB 812 6120-02b
Page 69
S5-100U
Installation Guidelines
Note the following when connecting the cable shield: •
Use metal cable clamps for fixing the braided shield. The clamps have to enclose the shield over a large area and make good contact (see Figure 3-26). Connect the shield to a shield bar immediately at the point where the cable enters the cabinet. Route the shield to the module; do not connect it to the module.
•
Figure 3-26. Fixing Shielded Cables with Various Types of Cable Clamps
3.4.5
Special Measures for Interference-Free Operation
Arc Suppression Elements For Inductive Circuits Normally, inductive circuits (e.g. contactor or relay coils) energized by SIMATIC S5 do not require to be provided with external arc suppressing elements since the necessary suppressing elements are already integrated on the modules. It only becomes necessary to provide arc supressing elements for inductive circuits in the following cases: • If SIMATIC S5 output circuits can be switched off by additionaly inserted contactors (e.g. relay contactors for EMERGENCY OFF). In such a case, the integral suppressing elements on the modules become ineffective. • If the inductive circuits are not energized by SIMATIC S5.
You can use free-wheeling diodes, varistors or RC elements for wiring inductive circuits.
- with Zener diode with varistor
+ with diode
Wiring coils activated by alternating current
Wiring coils activated by direct current with RC element
+
-
Figure 3-27. Wiring Coils
EWA 4NEB 812 6120-02b