Page 51
2
3
4
EWA 4NEB 812 6120-02b 5
L+ 2
4
6
7
M 8
5
3
1
10
2 3
.2 .6 1
1
.1 .5
.3 .7
.0 .4
F
S5-100U Installation Guidelines
Connecting Four-Channel Output Modules
Example: Connecting a lamp to channel 3 (address Q 1.3) on the output module in slot 1 (see Figure 3-13)
L+ M
4
5
6
7
8
9
9
5
10
DIGITAL OUTPUT
4 x 24 V DC/2 A 6ES5 440-8MA22
6
Lamp
Figure 3-13. Two-Wire Connection of a Lamp to Channel 3
3-15
Page 52
Installation Guidelines
S5-100U
Connecting Eight-Channel Digital Modules These modules do not have a two-wire connection. You therefore need an external distribution block. The eight channels of a module are numbered from .0 through .7. One terminal on the terminal block is assigned to each channel. The terminal assignment and the connection diagram are printed on the front plate of the module. Connecting Eight-Channel Input Modules The sensors must be connected to terminal 1 via the L+ terminal block.
Example: Connecting a sensor to channel 4 (address I 3.4) on an input module in slot 3 (see Figure 3-14)
1
L+
F
.6
10
.7
9
1
DIGITAL INPUT 8 x 24 V DC 6ES5 421-8MA12 2
3
4
5
L+
4
7
6
9
8
10
Sensor
M
6
1
2
4
5
3
7
.5
8
.4
5
.3
6
.2
3
.1
4
2M
.0
L+Terminal
Figure 3-14. Connecting a Sensor to Channel 4
3-16
EWA 4NEB 812 6120-02b
Page 53
1 2
3
DIGITAL OUTPUT
8 x 24 V DC/0.5 A 6ES5 441-8MA11
4
EWA 4NEB 812 6120-02b 5
2
L+ 4
M
5
7
6
5
8
3
.7
1
10
.4
.3
.2
.1
.0
.6
.5
2
1
S5-100U Installation Guidelines
Connecting Eight-Channel Output Modules
The actuators must be connected to terminal 2 via the M (negative) terminal block. This does not apply to the digital output module 8× 5 to 24 V DC/0.1 A (see section 14.6.2).
Example: Connecting a lamp to channel 6 (address output Q 5.6) on an output module in slot 5 (see Figure 3-15)
L+
M
4
3
6
5
8
7
9
9
10
Lamp
6
M Terminal
Figure 3-15. Connecting a Lamp to Channel 6
3-17
Page 54
Installation Guidelines
3.2.4
S5-100U
Connecting the Digital Input/Output Module
Use only slots 0 through 7 when you plug the module into the bus unit. Use a 40-pin cable connector with a screw-type connection or crimp snap-in connection for wiring. The module does not have a two-wire connection. You must therefore use an external distribution block. Every channel is assigned a terminal on the 40-pin connector. The channel numbers are printed on the front plate. The 16 channels on the input side (IN) are numbered from n.0 through n.7 and from n+1.0 through n+1.7. The 16 channels on the output side (OUT) are numbered from n.0 through n.7 and from n+1.0 through n+1.7. “n” is the start address of the slot. Slot 0, for example, has the start address of n=64 (see chapter 6).
n+1 n
L+ .0 .1 .2 .3 .4 .5 .6 .7 M L+ .0 .1 .2 .3 .4 .5 .6 .7 M
IN 1
0.5 A
0.5 A
OUT b
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
11
11
12
12
13
13
14
14
15
15
16
16
17
17
18
18
19
19
20
20 n+1 n
L+ .0 .1 .2 .3 .4 .5 .6 .7 NC NC .0 .1 .2 .3 .4 .5 .6 .7 M
40-pin crimp snap-in connector
Figure 3-16. Front View of the Digital I/O Module with a Crimp Snap-In Connector (simplified view and not true to scale)
3-18
EWA 4NEB 812 6120-02b
Page 55
S5-100U
Installation Guidelines
Example:
The start address for the modules is 65.3. Inputs and outputs have the same address. A sensor is to be connected to input I 64.4 and a lamp to output Q 7.3. Figure 3-17 illustrates the wiring on the front connector.
OUT
IN L+
A 65.3
M
L+
L+ 1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
10
11
11
12
12
13
13
14
14
15
15
16
16
17
17
18
18
19
19
20
20
E 64.4
M
Lamp M L+
M
M Terminal
Sensor
L+Terminal
Figure 3-17. Connecting a Sensor and a Load to Digital Input/Output Module 482
Note Chapter 11 describes how to connect analog modules.
EWA 4NEB 812 6120-02b
3-19
Page 56
Installation Guidelines
3.3
Electrical Configuration
3.3.1
Electrical Configuration for the S5-100U
S5-100U
Power Supply The entire control for the S5-100U consists of the following separate electrical circuits: •
Control circuit for the S5-100U (24 V DC)
•
Control circuit for the sensors (24 V DC)
•
Load circuit for the actuators (24 V DC or 115/230 V AC)
Control Circuit The power source for the control circuit supplies the CPU, the bus units, the programmer interface, and the internal control circuits for the I/O modules. When the incoming supply is 24 V DC/1 A, the PS 931 power supply module provides an internal supply of +9 V up to a total of 1 A current input to the I/O modules. The grounding spring on the CPU forces the control circuit to be connected to the standard mounting rail. The grounding spring must also be protected from interference. The grounding spring must be grounded. Load Circuit The power source for the load circuit supplies the actuators of the process peripherals. It is suggested that you use one of the following for a 24 V DC power supply: •
The PS 931 power supply module (see Chapter 14)
•
A Siemens load power supply from the 6EV1 series (see Appendix D)
If you use load power supplies other than the recommended ones, make certain that the load voltage is in the range of 20 to 30 V (including ripple).
Note If you use a switched-mode power supply unit to supply floating analog modules and BEROs, then this supply must be filtered through a network.
You can connect several mutually independent load circuits adjacent to each other on a single programmable controller. These connections can either be non-floating or floating (see section 3.3.3).
3-20
EWA 4NEB 812 6120-02b
Page 57
S5-100U
3.3.2
Installation Guidelines
Electrical Configuration with External I/Os
Figures 3-18, 3-19, and 3-20 display different configuration possibilities. Pay attention to the following points when you design your configuration. The numbers appearing in parentheses in the following points refer to the numbers in Figures 3-18 to 3-20. •
You must have a main switch (1) in accordance with VDE 0100 for your S5-100U, the sensors, and the actuators.
•
You do not need an additional fuse (2) to connect your S5-100U and the load circuit to power if your radial lines are a maximum of 3 meters (9.84 feet) long and are inherently earth-fault proof and short-circuit proof.
•
You need a load power supply (3) for 24 V DC load circuits. - You need a back-up capacitor (rating: 200 µF per 1 A of load current) if you have nonstabilized load power supplies.
•
If you have AC load circuits, galvanic isolation via a transformer (4) is recommended.
•
You should ground the load circuit at one end. Provide a removable connection (5) to the ground conductor on the load power supply (terminal M) or on the isolating transformer. - You must provide earth-fault monitoring for any non-grounded load circuits.
•
You must separately fuse (6 and 7) the load voltage for sensor circuits and for actuator circuits.
•
You must connect the standard mounting rail of the S5-100U to the ground conductor through a capacitor (8, to suppress high-frequency noise) for a non-grounded configuration.
•
You must have a low-resistance connection between the standard mounting rail and the cabinet’s chassis ground (10) for a grounded configuration.
•
You need a power fuse (9) to protect against a short-circuit occurring in the power supply.
EWA 4NEB 812 6120-02b
3-21
Page 58
3-22 (4)
PS
(10)
(6)
(7)
(2)
DI
DI
1 2 1 2
(5)
N
(1)
L1 L2
PE
Installation Guidelines S5-100U
L3
(9)
CPU
DO DO 1 2 1 2
230 V AC
Figure 3-18. Configuration Possibility: S5-100U with 115/230 V AC Power Supply for Programmable Controller, Sensors, and Actuators
EWA 4NEB 812 6120-02b
Page 59
S5-100U
Installation Guidelines
L2 L3
(1)
L1
PE
N (2)
CPU
L+ M
Figure 3.19
EWA 4NEB 812 6120-02b
1 2
1 2
DO DO 1 2
1 2
(7)
M
DI
(6)
(10)
DI
L+
M
(3)
(5)
L+ Configuration Possibility: S5-100U with 24 V DC Power Supply (with Safe Electrical Isolation According to DIN VDE 0160) for Programmable Controller, Sensors, and Actuators
3-23
Page 60
Installation Guidelines
(1)
L3 N
L2
PE (2)
L1
S5-100U
(8)
1 µF/ 500 V AC
Install the standard mounting rail electrically isolated
(3) L+
M
100 K
CPU
L+ M
DI
DI
1 2
1 2
DO DO 1 2
1 2
M
(7)
(6)
L+
Figure 3-20. Non-Grounded Operation; 24 V DC Power Supply (with Safe Electrical Isolation According to DIN VDE 0160) for Programmable Controller and I/Os
Interference voltages are discharged to the ground conductor (PE) via a capacitor. You can prevent static charges by connecting a high-ohmic resistor (approx. 100 k / W) parallel to the capacitor.
3-24
EWA 4NEB 812 6120-02b