3 Functions
BICO parameterization If the setting 99 (BICO) is entered into parameters P0701 – P0708, then the BICO wiring is enabled for the appropriate digital input. The output parameter number of the function (parameter, included in the parameter text BO) should be entered into the command source (parameter which contains the code BI in the parameter text).
Example: An ON/OFF1 command should be realized using digital input DIN1. P0700 = 2 Control enabled via digital inputs P0701 = 99 BICO enabled for DIN1 P0840 = 722.0 ON/OFF1 via DIN1 NOTE Only experienced users should use the BICO parameterization and for applications where the possibilities provided by P0701 – P0708 are no longer adequate.
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
137
Page 138
3 Functions
3.6.2
Issue 10/06
Digital outputs (DOUT) Number: Parameter range: Function chart number: Features: - cycle time:
3 r0730 – P0748 FP2100 1 ms
Binary states in the drive can be output via the digital outputs. As result of the fast cycle time, it is possible to control external devices and to display the state in real time. In order that higher powers can also be output, the internal signal (TTL level) is amplified using a relay (refer to Fig. 3-30). Relay: - max. opening / closing time: - voltage / current
Invert DOUTs 0 ... 7 P0748 (0)
5 / 10 ms 30 V DC / 5 A 250 V AC / 2 A
CO/BO: State DOUTs r0747 r0747.0
BI: Fct. of DOUT 1 0
P0731.C (52:3)
-1
1
COM NO
Invert DOUTs 0 ... 7 P0748 (0)
NC
CO/BO: State DOUTs
Kl.19 Kl.18 r0747 r0747.1
BI: Fct. of DOUT 2 0
P0732.C (52:7)
2
-1
COM NO
Invert DOUTs 0 ... 7 P0748 (0)
Kl.22 Kl.21
CO/BO: State DOUTs r0747 r0747.2
BI: Fct. of DOUT 3 0
P0733.C (0:0)
4
-1
COM NO NC
Fig. 3-30
Kl.20
Kl.25 Kl.24 Kl.23
Digital outputs
The states, which are to be output, are defined using the "BI" parameters P0731 (digital output 1), P0732 (digital output 2) and P0733 (digital output 3). For the definition, the "BO" parameter number or "CO/BO" parameter number and the bit number of the particular state should be entered into P0731 – P0733. Frequently used states including the parameter number and bit are shown in the following Table (refer to Table 3-12).
Table 3-12
Parameters P0731 – P0733 (frequently used functions / states)
Parameter value
Significance
52.0
Drive ready
MICROMASTER 440
138
Operating Instructions 6SE6400-5AW00-0BP0
Page 139
Issue 10/06
3 Functions
52.1
Drive ready to run
52.2
Drive running
52.3
Drive fault active
52.4
OFF2 active
52.5
OFF3 active
52.6
Switch-on inhibit active
52.7
Drive warning active
52.8
Deviation, setpoint / actual value
52.9
PZD control (Process Data Control)
52.A
Maximum frequency reached
52.B
Warning: Motor current limit
52.C
Motor holding brake (MHB) active
52.D
Motor overload
52.E
Motor running direction right
52.F
Inverter overload
53.0
DC brake active
53.1
Act. frequency f_act >= P2167 (f_off)
53.2
Act. frequency f_act > P1080 (f_min)
53.3
Act. current
53.6
Act. frequency f_act >= setpoint r0027 >= P2170
NOTE A complete list of all of the binary status parameters (refer to "CO/BO" parameters) can be taken from the parameter list.
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
139
Page 140
3 Functions
3.6.3
Issue 10/06
Analog inputs (ADC) Number: Parameter range: Function chart number: Features: - cycle time: - resolution: - accuracy: - electrical features:
2 P0750 – P0762 FP2200 4 ms 10 bits 1 % referred to 10 V / 20 mA incorrect polarity protection, short-circuit proof
Analog setpoints, actual values and control signals are read-into the drive inverter using the appropriate analog inputs and are converted into digital signals / values using the ADC converter. The setting as to whether the analog input is a voltage input (10 V) or a current input (20 mA) must be selected using the 2 switches DIP1(1,2) on the I/O board as well as also using parameter P0756 (refer to Fig. 3-31).
Possible settings of P0756: 0 Unipolar voltage input ( 0 to +10 V ) 1 Unipolar voltage input with monitoring (0 to 10 V ) 2 Unipolar current input (0 to 20 mA) 3 Unipolar current input with monitoring (0 to 20 mA) 4 Bipolar voltage input (-10 V to +10 V) only ADC1
Fig. 3-31
DIP switch and P0756 for ADC current / voltage input
NOTE ¾ The setting (analog input type) of P0756 must match that of switch DIP1(1,2) on the I/O board. ¾ The bipolar voltage input is only possible with analog input 1 (ADC1). Depending on the ADC type or source, the appropriate connection must be made. Using, as an example, the internal 10 V voltage source, a connection is shown as an example in the following diagram (refer to Fig. 3-32).
MICROMASTER 440
140
Operating Instructions 6SE6400-5AW00-0BP0
Page 141
Issue 10/06
3 Functions
Voltage input
Current input KL1
10 V
KL2
0V
KL3 ADC+
> 4.7 kΩ
0 ...20 mA
A
KL4 ADC−
KL1
10 V
KL2
0V
KL3 ADC+
A
KL4 ADC−
D KL10 ADC+
D KL10 ADC+
A
KL11 ADC−
D
Fig. 3-32
A
KL11 ADC−
D
Connection example for ADC voltage / current input
DIP switch KL
ADC+ ADC KL type ADC?
P0756
A D
ADC type
P0753
P0757 P0758 P0759 P0760
The ADC channel has several function units (filter, scaling, dead zone) (refer to Fig. 3-33).
ADC scaling r0754 P1000 P0761 ADC dead zone
Function r0755
Pxxxx r0752
1 0
Fig. 3-33 r0722 r0722.x
ADC channel
NOTE When the filter time constant P0753 (ADC-PT1) is increased, this smooths the ADC input signal therefore reducing the ripple. When this function is used within a control loop, this smoothing has a negative impact on the control behavior and immunity to noise (the dynamic performance deteriorates).
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
141
Page 142
3 Functions
3.6.4
Issue 10/06
Analog outputs (D/A converter) Number: Parameter range: Function chart number: Features: - cycle time: - resolution: - accuracy:
2 r0770 – P0785 FP2300 4 ms 10 bit 1 % referred to 20 mA
Setpoints, actual values and control signals inside the drive inverter are read-out via the D/A converter using these analog inputs. The digital signal is converted into an analog signal. All of the signals can be output via the D/A which contain the "CO" abbreviation in the parameter text (refer to list of all of the BICO parameters in the parameter list). Parameter P0771 defines, by assigning the parameter number, the quantity which is output as analog signal through the D/A converter channel (refer to Fig. 3-34). The smoothed output frequency is output, e.g. via the analog output, if P0771[0] = 21.
Function
Fig. 3-34 rxxxx r0755
CO: Freq. setpoint before RFG CO: Act. filtered frequency CO: Act. filtered output freq. CO: Act. filtered output voltage CO: Act. filtered DC-link volt. CO: Act. filtered output current CO/BO: Act. status word 1 CO/BO: Act. status word 2 CO/BO: Act. control word 1
Pxxxx P0771
D/A conv. channel
KL
D
D/A conv.+
A
KL
D/A conv.−
0 ... 20 mA r0020 r0021 r0024 r0025 r0026 r0027 ... r0052 r0053 r0054 ...
Signal output through the D/A converter channel
In order to adapt the signal, the D/A converter channel has several function units (filter, scaling, dead zone) which can be used to modify the digital signal before conversion (refer to Fig. 3-35).
Fig. 3-35
D/A converter channel
MICROMASTER 440
142
Operating Instructions 6SE6400-5AW00-0BP0
Page 143
Issue 10/06
3 Functions
With parameter P0775 = 1, negative values can be avoided on the input side of the DAC channel. If this parameter is activated, the absolute value is always entered in the input of the DAC scaling (the DAC characteristic is mirrored on the Y axis). If the value was originally a negative one, the corresponding bit in r0785 is set for detection.
NOTE The analog outputs only provide current outputs (0 ... 20 mA). A 0 ... 10 V voltage signal can be generated by connecting a 500 Ohm resistor across the outputs. The voltage drop across the resistor can be read using parameter r0774 if the parameter P0776 is changed-over from current output (P0776 = 0) to voltage output (P0776 = 1). The D/A scaling parameters P0778, P0780 and the D/A converter dead zone must still be entered in mA (0 ... 20).
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
143
Page 144
3 Functions
3.7
Issue 10/06
Communications Parameter range: Function chart number: CB at COM link USS at COM link USS at BOP link
P2009 – r2091 FP2700, FP2710 FP2600, FP2610 FP2500, FP2510
MICROMASTER 440 has 2 serial communication interfaces which can be simultaneously used. These interfaces are designated as follows in the following text: ¾ BOP link ¾ COM link Different units, such as the BOP and AOP operator panels, PCs with the start-up software DriveMonitor and STARTER, interface modules for PROFIBUS DP, DeviceNet and CAN as well as programmable controls with communication processors can be connected at this interface (refer to Fig. 3-28). DriveMonitor/ STARTER
BOP
BOP
1)
USS RS232 2)*
PROFIBUS board
AOP
DeviceNet board
CAN board
AOP
USS RS232
DriveMonitor/ STARTER
USS RS485 3)*
1) CB
4)*
CB
29 30
CB
USS RS485
BOP link
COM link
*
Option is absolutely required for the connection 1) Option: Operator panel door mounting kit for single inverter control 2) Option: PC to inverter connection kit 3) Option: AOP door mounting kit for multiple inverter control (USS) 4) Option: RS232-RS485 Converter
Fig. 3-36
Serial communication interfaces - BOP link and COM link
MICROMASTER 440
144
Operating Instructions 6SE6400-5AW00-0BP0
Page 145
Issue 10/06
3 Functions
The BOP, a programming / operator unit (e.g. AOP, PC with DriveMonitor / STARTER) or a programmable control with communications processor can be connected via this BOP link. Data transfer between MICROMASTER and the programming / operator units is realized using the USS protocol via the RS232 interface (point-to-point data coupling). Communications between the BOP and MICROMASTER uses a optimized interface which takes into consideration the somewhat limited resources of the BOP. If the BOP is replaced by an USS unit (PC, AOP), then MICROMASTER automatically identifies the interface of the new unit. This is also true for the inverse replacement sequence. The BOP link interface can be adapted to the particular unit using the following parameters (refer to Table 3-13). Table 3-13
BOP link BOP link – interface BOP on BOP link
USS on BOP link
No parameter
P2009[1] P2010[1] P2011[1] P2012[1] P2013[1] P2014[1] r2015 P2016 r2024[1] r2025[1] r2026[1] r2027[1] r2028[1] r2029[1] r2030[1] r2031[1] r2032 r2033
Communication modules (CB) such as PROFIBUS, DeviceNet, CANopen and also programming / operator units (e.g. PCs with the DriveMonitor / STARTER start-up software and AOP) as well as programmable controls with communication processor can be connected to the COM link. The plug connector allows the communication modules to be connected to MICROMASTER. On the other hand, the programming / operator units must be connected to the MICROMASTER through terminals 29/30. As for the BOP link, data is transferred between MICROMASTER and the programming / operator unit using the USS protocol. In so doing, for the COM link, the USS protocol is transferred via the bus-capable RS485 interface. Essentially the same as the BOP link, the COM link also automatically defines if a communications module is replaced with a USS unit (PC, AOP). The COM link can be adapted to the particular unit using the following parameters (refer to Table 3-14). Table 3-14
COM link COM link – interface CB on COM link
P2040 P2041 r2050 P2051
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
USS on COM link r2053 r2054 r2090 r2091
P2009[0] P2010[0] P2011[0] P2012[0] P2013[0] P2014[0] r2018 P2019 r2024[0] r2025[0] r2026[0] r2027[0] r2028[0] r2029[0] r2030[0] r2031[0] r2036 r2037
145
Page 146
3 Functions
Issue 10/06
NOTE ¾ A communications (CB) module as well as a programming / operator unit can be simultaneously connected to the COM link interface via terminals 29/30 (USS). This is the reason that the communications module has priority over USS. In this case, the USS node (USS station) via the COM link is de-activated. ¾ Contrary to PROFIBUS, the RS485 port (terminals 29/30) is not optically isolated (not floating). When installing the system, it must be ensured that EMC faults do not result in communication failures or damage to the RS485 drivers.
3.7.1
Universal serial interface (USS) Parameter range:
Alarms: Faults: Function chart number: Features: − electrical features:
P2009 – r2037 Significance
COM link
BOP link
USS basic setting USS baud rate USS address USS-PZD length USS-PKW length
P2010[0] P2011[0] P2012[0] P2013[0]
P2010[1] P2011[1] P2012[1] P2013[1]
PZD data Received data Received control word 1 Received control word 2 Sent data Sent status word 1 Sent status word 2 r2018[8] r2036 r2037 P2019[8] r0052 r0053 r2015[8] r2032 r2033 P2016[8] r0052 r0053
--F0071, F0072 FP2500, FP2510, FP2600, FP2610 Not electrically isolated Not electrically isolated
− cycle time (MM440): 8 ms Background
USS at the BOP link with PCconverter connecting set USS at COM link (terminals 29 /30)