Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 16 of 35

MICROMASTER 440 0.12 kW - 250 kW Operating Instructions: 3 Functions, pages 127 to 136

Pages 127 to 136 of 312, from MICROMASTER 440 0.12 kW - 250 kW Operating Instructions

The original document is the PDF (8.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Siemens 6SE6440-2UD13-7AA1

Page 127

Issue 10/06

3 Functions

3.5.7.19

Command and drive data set

P0810 =...

Command data set CDS bit 0 (local / remote) Selects the command source in which bit 0 should be read-out to select a command data set (CDS).

0

Selecting CDS BI: CDS bit 1

CO/BO: Act CtrlWd2 r0055 .15 r0055 .15

3

P0811 (0:0)

2 BI: CDS b0 loc/rem

CO/BO: Act CtrlWd1

1

P0810 r0054 .15 r0054 .15

(0:0)

0 t Changeover time approx. 4 ms

Active CDS r0050

Changeover time approx. 4 ms

3 2

CO: Active CDS r0050

1 0 t

The currently active command data set (CDS) is displayed using parameter r0050: Select CDS

Active CDS r0055 bit15 r0054 bit15 r0050

1. CDS

0

0

0

2. CDS

0

1

1

3. CDS

1

0

2

3. CDS

1

1

2

Most frequent settings: 722.0 = Digital input 1 (P0701 must be set to 99, BICO) 722.1 = Digital input 2 (P0702 must be set to 99, BICO) 722.2 = Digital input 3 (P0703 must be set to 99, BICO) 722.3 = Digital input 4 (P0704 must be set to 99, BICO) 722.4 = Digital input 5 (P0705 must be set to 99, BICO) 722.5 = Digital input 6 (P0706 must be set to 99, BICO) 722.6 = Digital input 7 (via analog input 1, P0707 must be set to 99) 722.7 = Digital input 8 (via analog input 2, P0708 must be set to 99) Example for CDS changeover: CDS1: Command source via terminals and setpoint source via analog input (ADC) CDS2: Command source via BOP and setpoint source via MOP CDS changeover is realized using digital input 4 (DIN 4) Steps: 1. Carry-out commissioning for CDS1 (P0700[0] = 2 and P1000[0] = 2) 2. Connect P0810 (P0811 if required) to the CDS changeover source (P0704[0] = 99, P0810 = 722.3) 3. Copy from CDS1 to CDS2 (P0809[0] = 0, P0809[1] = 1, P0809[2] = 2) 4. Adapt CDS2 parameters (P0700[1] = 1 and P1000[1] = 1)

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

127

Page 128

3 Functions

Issue 10/06

P0810 = 722.3 DIN4 Terminals

0

P0700[1] = 1

1

P1000[0] = 2

0

P1000[1] = 1

1

Sequence control

BOP ADC MOP

P0820 = ...

P0700[0] = 2

Setpoint channel

Motor control

0 Drive data set (DDS) bit 0 Selects the command source from which bit 0 should be read-out to select a drive data set. Operation Ready t Select DDS BI: DDS bit 1 P0821 (0:0)

CO/BO: Act CtrlWd2

3 r0055 .05 r0055 .05

2

BI: DDS bit 0

CO/BO: Act CtrlWd2

1

P0820 r0055 .04 r0055 .04

(0:0)

0 t Changeover time approx. 50 ms

Active DDS r0051[1]

Changeover time approx. 50 ms

3 2

CO: Active DDS r0051 .01 [2]

1 0 t

The currently active drive data set (DDS) is displayed using parameter r0051[1]: Select DDS r0055 r0054 bit05 bit04 r0051 [0]

Active DDS r0051 [1]

1. DDS

0

0

0

0

2. DDS

0

1

1

1

3. DDS

1

0

2

2

3. DDS

1

1

2

2

Most frequent settings: 722.0 = Digital input 1 (P0701 must be set to 99, BICO) 722.1 = Digital input 2 (P0702 must be set to 99, BICO) 722.2 = Digital input 3 (P0703 must be set to 99, BICO) 722.3 = Digital input 4 (P0704 must be set to 99, BICO) 722.4 = Digital input 5 (P0705 must be set to 99, BICO) 722.5 = Digital input 6 (P0706 must be set to 99, BICO) 722.6 = Digital input 7 (via analog input 1, P0707 must be set to 99) 722.7 = Digital input 8 (via analog input 2, P0708 must be set to 99)

MICROMASTER 440

128

Operating Instructions 6SE6400-5AW00-0BP0

Page 129

Issue 10/06

3 Functions

Example: 1. Commissioning steps with a motor: − Carry-out commissioning at DDS1. − Connect P0820 (P0821 if required) to the DDS changeover source (e.g. using DIN 4: P0704[0] = 99, P0820 = 722.3). − Copy DDS1 to DDS2 (P0819[0] = 0, P0819[1] = 1, P0819[2] = 2). − Adapt DDS2 parameters (e.g. ramp-up / ramp-down times P1120[1] and P1121[1]). Sequence control

SUM setpoint

ADC

AFM

Motor control

RFG

Gating unit

DIN

M

P0820 = 722.3 DIN4 0

1

P1120 P1121 [1] [2] [0] DDS1 DDS2 DDS3 2. Commissioning steps with 2 motors (motor 1, motor 2):

− −

Commission motor 1; adapt the remaining DDS1 parameters. Connect P0820 (P0821 if required) to the DDS changeover source (e.g. via DIN 4: P0704[0] = 99, P0820 = 722.3). Changeover to DDS2 (check using r0051). Commission motor 2; adapt the remaining DDS2 parameters. Motor 1

M2

Motor 2

K2

MM4

M1 K1

− −

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

129

Page 130

3 Functions

3.5.7.20

Issue 10/06

Diagnostic parameters r0035

CO: Motor temperature Displays the measured motor temperature in °C.

r0036

CO: Frequency inverter utilization Displays the frequency inverter utilization as a % referred to the overload. In so doing, the value is calculated using the I2t model. The I2t actual value relative to the maximum possible I2t value provides the level of utilization.

r0052

CO/BO: Act. status word 1 Displays the first active status word (ZSW) of the frequency inverter (bit format) and can be used to diagnose the inverter status.

r0054

CO/BO: Control word 1 Displays the first control word (STW) of the frequency inverter and can be used to display the active commands.

r0063

CO: Actual frequency Displays the actual frequency in Hz. 60 r0313

Frequency actual values:

Smoothed speed act. value 160 ms

V/f

SLVC (observer model) r0313 60 ⋅ P0408 0 Encoder

P0400 r0022

P1300

Smoothed freq. actual value r0021

<20

Frequency actual value

20,22 r0063

21,23

Freq.act.value fr. the encoder

0 r0061 1,2

P1300 = 21,23 and P0400 = 0 --> F0090 r1079

CO: Selected frequency setpoint Displays the selected frequency setpoint. The following frequency setpoints are displayed: r1078 total setpoint (HSW + ZUSW) P1058 JOG frequency, clockwise P1059 JOG frequency, counter-clockwise.

r1114

CO: Freq. setpoint after dir. ctrl. Displays the setpoint (reference) frequency in Hz after the function block to reverse the direction of rotation.

r1170

CO: : Frequency setpoint after RFG Displays the total frequency setpoint (reference value) in Hz after the ramp-function generator.

MICROMASTER 440

130

Operating Instructions 6SE6400-5AW00-0BP0

Page 131

Issue 10/06

3 Functions

3.5.7.21

End of commissioning

P0971 = 1

0 Transfer data from RAM to EEPROM 0 Inhibited 1 Start RAM->EEPROM All parameter changes are transferred from the RAM memory into the EEPROM memory and therefore saved in the MICROMASTER in a non-volatile fashion.

NOTE When using a BOP or AOP, MICROMASTER automatically carries-out the RAM→EEPROM data save operation. If the parameterization is carried-out using the commissioning tools - STARTER or DriveMonitor – then data is not automatically saved in the EEPROM. Automatic RAM→EEPROM data save can be selected by pressing the appropriate selection button. STARTER

RAM → EEPROM

DriveMonitor

Online-EEPROM

END

NOTE If P0971 is used to start data save from the RAM to EEPROM, then after the data has been transferred, the communications memory is re-initialized. This means that communications via USS as well as also via the CB board are interrupted for the time it takes to reset: ¾ The connected PLC (e.g. SIMATIC S7) goes into stop ¾ The STARTER start-up program buffers the communications failure ¾ For the DriveMonitor start-up program, "NC" (not connected) or "drive busy" is displayed. ¾ The "busy" text is displayed at the BOP operator panel After reset has been completed, for the start-up programs STARTER and DriveMonitor and the BOP operator panel, communications are automatically reestablished.

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

131

Page 132

3 Functions

3.5.8

Issue 10/06

Series commissioning The parameter set can be read-out (upread) from the drive converter via the serial interface and saved on the hard disk / floppy disk or in a non-volatile memory (e.g. EEPROM) using the following ¾ PC Tools (e.g. STARTER, DriveMonitor) or the ¾ Operator panel AOP (please refer to Fig. 3-28). The interfaces of the drive inverter with USS protocol and the fieldbus interfaces (e.g. PROFIBUS) which can be used to transfer parameters, can be used as serial interface. AOP 3)* 1) DriveMonitor 2)*

USS on BOP link (RS232)

4)*

USS on COM link (RS485)

STARTER 2)*

CB on COM link (PROFIBUS)

CB MM4

4)* 5)* * Parameter transmission from different sources via download

Option is absolutely required for the connection

1) Option: Operator panel door mounting kit for single inverter control 2) Option: PC to inverter connection kit 3) Option: AOP door mounting kit for multiple inverter control (USS) 4) Option: RS232-RS485 Converter 5) With PROFIBUS: SIMATIC NET With CANopen or DeviceNet: see user organisation

Fig. 3-28

Upread / download using AOP and PC Tools

If there is already an appropriate parameter set for the drive, which, for example, was created by either upreading or by programming offline, then this can be downloaded into the drive inverter. This means that it is possible to transfer the parameter set from drive inverter A to drive inverter B which, for identical applications (e.g. series machines, group drives) allows data to be copied and therefore in turn fast commissioning.

MICROMASTER 440

132

Operating Instructions 6SE6400-5AW00-0BP0

Page 133

Issue 10/06

3 Functions

WARNING ¾ For series commissioning, all of the communication interfaces as well as also the digital and analog interfaces are re-initialized. This results in a brief communications failure or causes the digital outputs to switch. ¾ Potentially hazardous loads must be carefully secured before starting a series commissioning. ¾ Potentially hazardous loads can be secured as follows before starting series commissioning: ♦ Lower the load to the floor, or ♦ Clamp the load using the motor holding brake (Caution: During series commissioning, MICROMASTER must be prevented from controlling the motor holding brake). ¾ If the motor holding brake (refer to Section 3.14) is controlled by the MICROMASTER, then series commissioning may not be carried-out for potentially hazardous loads (e.g. suspended loads for crane applications).

3.5.9

Parameter reset to the factory setting The factory setting is a defined initial state of all of the drive inverter parameters. The drive inverters are shipped from the factory in this state. The drive inverters have the following default settings: ¾ Control via the digital inputs a) ON/OFF via DIN1 b) Direction of rotation reversal via DIN2 c) Fault acknowledgement via DIN3 ¾ Setpoint input via analog input 1 ¾ Signal output via the digital outputs a) Fault active via DOUT 1 b) Warning active via DOUT 2 ¾ Actual frequency via the analog output ¾ The basic V/f characteristic is the control mode (P1300 = 0) ¾ Induction motor (P0300 = 1) When appropriately connected-up and with the appropriate motor – drive inverter combination, MICROMASTER drive inverters are ready to run when shipped from the factory without requiring any additional parameterization. You can re-establish the initial state at any time by carrying-out a parameter reset to the factory setting. This undoes all of the parameter changes which were made since the drive inverter was supplied. This value is designated as "Def" in the parameter list.

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

133

Page 134

3 Functions

Issue 10/06

Reset to the factory setting START

P0003 = 1

User access level 1 Access level, standard

1

P0004 = 0

Parameter filter 0 All parameters

0

P0010 = 30

Commissioning parameter 30 Factory setting

0

P0970 = 1

Factory reset 1 Parameter reset to the default values

0

END

The drive inverter carries-out a parameter reset (duration, approx. 10 s) and then automatically exits the reset menu and sets P0970 = 0 : Disabled P0010 = 0 : Ready

NOTE When resetting the parameters to the factory setting, the communications memory is re-initialized. This means that communications via USS as well as also via the CB board are interrupted for the time it takes to make the reset: ¾ The connected PLC (e.g. SIMATIC S7) goes into stop ¾ The STARTER start-up program buffers the communications failure ¾ For the DriveMonitor start-up program, "NC" (not connected) or "drive busy" is displayed. ¾ The "busy" text is displayed at the BOP operator panel After reset has been completed, for the start-up programs STARTER and DriveMonitor or the BOP operator panel, communications are automatically reestablished.

MICROMASTER 440

134

Operating Instructions 6SE6400-5AW00-0BP0

Page 135

Issue 10/06

3 Functions

3.6

Inputs / outputs

3.6.1

Digital inputs (DIN) Number: Parameter range: Function chart number: Features: - cycle time: - switch-on threshold: - switch-out threshold: - electrical features:

6+2 r0722 – P0725 FP2000, FP2200 2 ms 10.6 V 10.6 V electrically isolated, short-circuit proof

External control signals are required for a drive converter to be able to operate autonomously. These signals can be entered via a serial interface as well as also via digital inputs (refer to Fig. 3-29). MICROMASTER has 6 digital inputs which can be expanded to a total of 8 by using the 2 analog inputs. The digital inputs, as far as their assignment, can be freely programmed to create a function. Whereby, regarding the program, it is possible to directly assign the function via parameters P0701 - P0708 or to freely program the function using BICO technology. DIN channel (e.g. DIN1 - PNP (P0725 = 1)) Kl.9 P24 (PNP) Kl.28 0 V (NPN)

PNP/NPN DIN 0 ... 1 P0725 (1)

P0701 Debounce time: DIN 0 ... 3 P0724 (3)

24 V

Function 0

0

1

1

24 V

T

0

& r0722 r0722 .0

Pxxxx BI: ...

CO/BO: Bin.inp.val 0V

DIN channel (e.g. DIN1 - NPN (P0725 = 0)) Kl.9 P24 (PNP) Kl.28 0 V (NPN)

PNP/NPN DIN 0 ... 1 P0725 (1)

P0701 Debounce time: DIN 0 ... 3 P0724 (3)

24 V

Function 0

0

1

1

24 V

T

0

& r0722 r0722 .0

Pxxxx BI: ...

CO/BO: Bin.inp.val 0V

Fig. 3-29

Digital inputs

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

135

Page 136

3 Functions

Issue 10/06

Parameter P0725 is used to define as to whether digital inputs DIN1 - DIN6 are logical "1" when appropriately connected to 0 V or 24 V. The logical states of the digital inputs can be de-bounced using P0724 and read-out using parameter r0722 (BICO monitoring parameter). Further, this parameter is used to parameterize BICO for the digital inputs (refer to BICO parameterization in the following Section). P0701 – P0706 (digital inputs 1–6) or P0707 – P0708 (analog inputs 1-2) The possible settings of the individual inputs are listed in Table 3-11. Table 3-11

Parameters P0701 – P0706

Parameter value

Significance

0

Digital input disabled

1

ON / OFF1

2

ON+reverse / OFF1

3

OFF2 – coast to standstill

4

OFF3 – quick ramp-down

9

Fault acknowledge

10

JOG right

11

JOG left

12

Reverse

13

MOP up (increase frequency)

14

MOP down (decrease frequency)

15

Fixed setpoint (direct selection)

16

Fixed setpoint (direct selection + ON)

17

Fixed setpoint (binary-coded selection + ON)

25

Enable DC braking

29

External trip

33

Disable additional frequency setpoint

99

Enable BICO parameterization

Example: An ON/OFF1 command should be realized using digital input DIN1. P0700 = 2 Control enabled via terminal strip (digital inputs) P0701 = 1 ON/OFF1 via digital input 1 (DIN1) NOTE If an analog input (refer to Fig. 3-33) has been configured as digital input, then the following limit values apply: < 1.7 V DC → "0" > 3.9 V DC → "1"

MICROMASTER 440

136

Operating Instructions 6SE6400-5AW00-0BP0