Page 117
Issue 10/06
3 Functions
Supplementary torque setpoint ¾ In the vector mode – with / without encoder – the speed controller can be subordinate to a constant or variable supplementary torque. ¾ The supplementary setpoint can be used to advantage for hoisting gear with low intrinsic friction when starting in the vertical direction. The supplementary torque setpoint must always be impressed in the hoisting (raising) direction (please observe the sign!). As a result of the supplementary torque, also when lowering, a slip is immediately established that has a stabilizing effect on the closed-loop control (there is no significant load sag). ¾ The sign of the supplementary torque setpoint can be determined as follows in the commissioning phase with the appropriate care and taking into account all of the relevant safety regulations: Hoist (raise) a minimum load using the hoisting gear and read-out the sign from parameter r0079 (the sign of r0079 corresponds to the sign of the supplementary torque setpoint). ¾ An empirical value of approx. 40 % of the rated motor torque r0333 has lead to good results for existing hoisting gear (carefully observe the sign!). P1511=...
0:0 CI: Supplementary torque setpoint Selects the source of the supplementary torque setpoint.
Frequent settings: 2889 Fixed setpoint 1 as a % 2890 Fixed setpoint 2 as a % 755.0 Analog input 1 755.1 Analog input 2 2015. 2 USS (BOP link) 2018. 2 USS (COM link) 2050. 2 CB (e.g. PROFIBUS)
Droop Precontrol r1518
Kp r1170
–
*)
Freq. setpoint
–
Tn
PI Speed controller r1538 r1538 r1539 r1539
Ti r0063 r1508
Torque setpoint r0079
Act. frequency r1515
CI: Add. trq. setp P1511.C (0:0)
*) only active, if pre-control is enabled (P1496 > 0)
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
Ti
Kp
Tn
SLVC:
P1452
P1470
P1472
VC:
P1442
P1460
P1462
117
Page 118
3 Functions
3.5.7.18
Issue 10/06
Converter-specific Functions
Flying start p1200 = ...
Flying start Starts inverter onto a spinning motor by rapidly changing the output frequency of the inverter until the actual motor speed has been found. 0 Flying start disabled 1 Flying start is always active, start in direction of setpoint 2 Flying start is active if power on, fault, OFF2, start in direction of setpoint 3 Flying start is active if fault, OFF2, start in direction of setpoint 4 Flying start is always active, only in direction of setpoint 5 Flying start is active if power on, fault, OFF2, only in direction of setpoint 6 Flying start is active if fault, OFF2, only in direction of setpoint p1202 = ...
Motor-current: Flying start (entered in %) Defines search current used for flying start.
p1203 = ?
0
100 %
100 % Search rate: Flying start (entered in %) Sets factor by which the output frequency changes during flying start to synchronize with turning motor.
Automatic restart p1210 = ...
1
Automatic restart Configures automatic restart function. 0 Disabled 1 Trip reset after power on 2 Restart after mains blackout 3 Restart after mains brownout or fault 4 Restart after mains brownout 5 Restart after mains blackout and fault 6 Restart after mains brown/blackout or fault
MICROMASTER 440
118
Operating Instructions 6SE6400-5AW00-0BP0
Page 119
Issue 10/06
3 Functions
Holding brake ¾ Series / commissioning for hazardous loads − lower the load to the floor − when replacing the frequency inverter, prevent (inhibit) the frequency inverter from controlling the motor holding brake (MHB) − secure the load or inhibit the motor holding brake control (so that the brake cannot be controlled) and then – and only then – carry-out quick commissioning / parameter download using the PC-based tool (e.g. STARTER, AOP) ¾ Parameterize the weight equalization for hoisting gear applications − magnetizing time P0346 greater than zero − min. frequency P1080 should approximately correspond to the motor slip r0330 (P1080 ≈ r0330) − adapt the voltage boost to the load a) V/f (P1300 = 0 ...3): P1310, P1311 b) SLVC (P1300 =20): P1610, P1611 ¾ It is not sufficient to just select the status signal r0052 bit 12 "motor holding brake active" in P0731 – P0733. In order to activate the motor holding brake, in addition, parameter P1215 must be set to 1. ¾ It is not permissible to use the motor holding brake as operating brake. The reason for this is that the brake is generally only dimensioned/designed for a limited number of emergency braking operations. ¾ The brake closing / opening times can be taken from the appropriate manual. The following typical values have been taken from Motor Catalog M11 2003/2004, Page 2/51:
P1215 =...
Motor size
Brake type
Opening time [ms]
Closing time [ms]
63
2LM8 005-1NAxx
25
56
71
2LM8 005-2NAxx
25
56
80
2LM8 010-3NAxx
26
70
90
2LM8 020-4NAxx
37
90
100
2LM8 040-5NAxx
43
140
112
2LM8 060-6NAxx
60
210
132
2LM8 100-7NAxx
50
270
160
2LM8 260-8NAxx
165
340
180
2LM8 315-0NAxx
152
410
200 225
2LM8 400-0NAxx
230
390
Holding brake enable Enables/disables holding brake function (MHB). 0 Motor holding brake disabled 1 Motor holding brake enabled NOTE
0
The following must apply when controlling the brake relay via a digital output: P0731 = 52.C (= 52.12) (refer to Section 3.5.7.4 "Digital output (DOUT)").
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
119
Page 120
3 Functions
Issue 10/06
52.3 Frequent settings: P0731=52.C BI: Fct digital output 1 Defines the source for digital output 1. 52.0 Ready to power-up 0 52.1 Ready 0 NOTE 52.2 Drive operational 0 The brake relay can also be controlled 52.3 Fault present 0 from another digital output (if this is 52.4 OFF2 active (present) 1 available) or using a distributed I/O 1 module. Analog to DOUT 1, it should 52.5 OFF3 active (present) 52.6 Power-on inhibit active (present) 0 be guaranteed that the I/Os are 52.7 Alarm active (present) 0 controlled by the status bit “MHB 52.8 Deviation, setpoint/actual value 1 active”.
P0748 = 0
52.9 PZD / PLC control 0 52.A Maximum frequency reached 0 52.B Alarm: Motor current limit 1 52.C Motor holding brake active 0 52.D Motor overload 1 52.E Motor dir. of rotation, clockwise 0 52.F Frequency inverter overload 1 53.0 DC brake active 0 53.1 Actual freq. f_act > P2167 (f_off) 0
0 Inverting digital outputs This parameter allows the signals to be output to be inverted.
Closed Closed Closed Closed Closed Closed Closed Closed Closed Closed Closed Closed Closed Closed Closed Closed Closed Closed
: : Invert DOUTs 0 ... 7 P0748 (0)
DOUT channel
CO/BO: State DOUTs r0747 r0747.0
BI: Fct. of DOUT 1
Function xxxx.y rxxxx.y
P0731.C (52:3)
0
1
COM Kl.20
-1
P0731 = xxxx.y
NO Relay : Text
NC
DC 30 V / 5 A AC 250 V / 2 A - max. opening / closing time 5 / 10 ms p1216 = ...
p1217 = ...
Kl.19 or Kl.18 Kl.28
1.0 s Holding brake release delay (entered in s) Defines the time interval during which the frequency inverter runs with the min. frequency p1080 after magnetizing, before the ramp-up starts. P1216 ≥ brake opening time + relay opening time 1.0 s Holding time after ramp-down (entered in s) Defines time for which inverter runs at minimum frequency (p1080) after ramping down. P1217 ≥ brake closing time + relay closing time
MICROMASTER 440
120 int. 24 V max. 100 mA Kl.9
Operating Instructions 6SE6400-5AW00-0BP0
Page 121
Issue 10/06
3 Functions
Braking functions Priorities are assigned to the various braking functions. For instance, if a DC brake or a compound brake is activated, then this has a higher priority than the dynamic brake (resistance-type braking).
DC braking P1233 > 0 ?
Compound braking P1236 > 0 ?
no yes yes DC braking enabled
Dynamic braking P1237 > 0 ?
no
Compound braking enabled no yes Dynamic braking enabled disabled
DC-Bremse P1230 = ...
BI: Enabling the DC brake This enables DC braking using a signal that was used from an external source. The function remains active as long as the external input signal is active. DC braking causes the motor to quickly stop by injecting a DC current BI: Enable DC brk. 1 P1230.C (0:0)
0 t
⏐f⏐ f* f_set DC braking f_act t i
P0347 t DC braking active r0053 1 Bit00 0 t Note: DC brake can be applied in drive states r0002 = 1, 4, 5
P1232 =...
DC braking current (entered in %) Defines level of DC current in [%] relative to rated motor current (P0305).
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
100 %
121
Page 122
3 Functions
P1233 =...
Issue 10/06
0s Duration of DC braking (entered in s) Defines duration for which DC injection braking is to be active following an OFF1 or OFF3 command.
1
ON OFF1/OFF3 t P0347
OFF2 t ⏐f⏐
OFF2 DC braking
P1234 t DC braking active r0053 1 Bit00 0 t P1233
2 ON OFF1/OFF3 t P0347
OFF2 t ⏐f⏐ OFF ramp P1234
OFF2 DC braking
OFF2 t DC braking active r0053 1 Bit00 0 t P1233
P1234 =...
650 Hz
DC braking start frequency (entered in Hz) Sets the start frequency for the DC brake.
MICROMASTER 440
122
Operating Instructions 6SE6400-5AW00-0BP0
Page 123
Issue 10/06
3 Functions
Compound braking P1236 =...
0% Compound braking current (entered in %) Defines DC level superimposed on AC waveform after exceeding DC-link voltage threshold of compound braking. The value is entered in [%] relative to rated motor current (P0305). (see also Vdc controller ").
If P1254 = 0 : Compound braking switch-on level otherwise : Compound braking switch-on level
= 1.13 ⋅ 2 ⋅ Vmains = 1.13 ⋅ 2 ⋅ P0210
U
= 0.98 ⋅ r1242
DC_Comp
DC_Comp
P1236 = 0 Without Compound braking ⏐f⏐
U
P1236 > 0 With Compound braking ⏐f⏐ f_set f_set f_act f_act t i t i t uDC-link t uDC-link UDC_Comp t t
Dynamic braking P1237 = ...
0 Dynamic braking Dynamic braking is activated using parameter P1237 – the nominal (rated) duty cycle as well as the switch-in duration of the braking resistor are also defined. 0 Inhibited 1 Load duty cycle 5 % 2 Load duty cycle 10 % 3 Load duty cycle 20 % 4 Load duty cycle 50 % 5 Load duty cycle 100 % Using the dynamic brake, the regenerative feedback energy is transferred to the external braking resistor using the chopper control (braking chopper); it is converted into thermal energy (heat) in this resistor. This dynamic braking allows the drive to be braked in a controlled fashion. This function is not available for sizes FX and GX.
Chopper resistor MM4
~
B+
= ~
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
Chopper control
B-
= ~
123
Page 124
3 Functions
Issue 10/06
Vdc controller P1240 =...
P1254 =...
Configuration of Vdc controller Enables / disables Vdc controller. 0 Vdc controller disabled 1 Vdc-max controller enabled
1
1 Auto detect Vdc switch-on levels Enables/disables auto-detection of switch-on levels for Vdc control functionalities. 0 Disabled 1 Enabled
VDC r1242 t VDC_max -controller active r0056 Bit14
A0911
1 0 t
⏐f⏐ fact fset t
PID controller P2200 =...
P2253 =...
P2254 =...
0.0 BI: Enable PID controller PID mode Allows user to enable/disable the PID controller. Setting to 1 enables the PID controller. Setting 1 automatically disables normal ramp times set in P1120 and P1121 and the normal frequency setpoints. 0.0
CI: PID setpoint Defines setpoint source for PID setpoint input.
0.0 CI: PID trim source Selects trim source for PID setpoint. This signal is multiplied by the trim gain and added to the PID setpoint.
P2257 =...
Ramp-up time for PID setpoint Sets the ramp-up time for the PID setpoint.
1.00 s
P2258 =...
Ramp-down time for PID setpoint Sets ramp-down time for PID setpoint.
1.00 s
P2264 =...
CI: PID feedback Selects the source of the PID feedback signal.
755.0
P2267 =...
Max. value for PID feedback Sets the upper limit for the value of the feedback signal in [%]..
100.00 %
P2268 =...
Min. value for PID feedback Sets lower limit for value of feedback signal in [%]..
0.00 %
P2280 =...
PID proportional gain Allows user to set proportional gain for PID controller.
3.000
P2285 =...
PID integral time Sets integral time constant for PID controller.
0.000 s
P2291 =...
PID output upper limit Sets upper limit for PID controller output in [%].
100.00 %
MICROMASTER 440
124
Operating Instructions 6SE6400-5AW00-0BP0
Page 125
Issue 10/06
0.00 %
P2253
USS BOP link USS COM link
P2264
CB COM link
P2200
P2285
PID PT1
P2280
PID RFG
0 PID SUM
P2270
PID FF
P2254
P2269
ADC
P2257
PID MOP
P2261
PID output lower limit Sets lower limit for the PID controller output in [%]. P2258
P2292 =...
3 Functions
PID PT1
PID SCL
P2265
P2271
PID
− ∆PID
0
Motor control
1
PIDOutput
& P2251
ADC2
Example: Parameter
Parameter text
Example
P2200 P2253 P2264 P2267 P2268 P2280 P2285 P2291 P2292
BI: Enable PID controller CI: PID setpoint CI: PID feedback Max. PID feedback Min. PID feedback PID proportional gain PID integral time PID output upper limit PID output lower limit
P2200 = 1.0 P2253 = 2224 P2264 = 755 P2267 P2268 P2280 P2285 P2291 P2292
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
PID controller active PID-FF1 ADC Adapt to the application Adapt to the application Determined by optimizing Determined by optimizing Adapt to the application Adapt to the application
125
Page 126
3 Functions
Issue 10/06
Free function blocks (FFB)
P2801 =...
P2802 =...
0 Enable FFBs Parameter P2800 is used to activate all free function blocks (generally, P2800 is set to 1). Possible settings: 0 Inhibited 1 Enabled 0.0 Activate FFBs Parameter P2801 is used to individually enable (activate) the free function blocks P2801[0] to P2801[16] (P2801[x] > 0). Further, parameters P2801 and P2802 are used to define the chronological sequence of all of the function blocks. The table below indicates that the priority increases from left to right and from bottom to top. Possible settings: 0 Inactive 1 Level 1 2 Level 2 0 Level 3 Example: P2801[3] = 2, P2801[4] = 2, P2802[3] = 3, P2802[4] = 2 FFBs are calculated in the following sequence: P2802[3], P2801[3] , P2801[4], P2802[4] The active function blocks are calculated every 132 ms.
Activate FFBs Parameter P2802 is used to individually enable (activate) the free function blocks P2802[0] to P2802[13] (P2802[x] > 0). Possible settings: 0 Inactive 1 Level 1 2 Level 2 1 Level 3 low
Priority 2
3 2 1 Inactive 0 P2802 [13] CMP 2 P2802 [12] CMP 1 P2802 [11] DIV 2 P2802 [10] DIV 1 P2802 [9] MUL 2 P2802 [8] MUL 1 P2802 [7] SUB 2 P2802 [6] SUB 1 P2802 [5] ADD 2 P2802 [4] ADD 1 P2802 [3] Timer 4 P2802 [2] Timer 3 P2802 [1] Timer 2 P2802 [0] Timer 1 P2801 [16] RS-FF 3 P2801 [15] RS-FF 2 P2801 [14] RS-FF 1 P2801 [13] D-FF 2 P2801 [12] D-FF 1 P2801 [11] NOT 3 P2801 [10] NOT 2 P2801 [9] NOT 1 P2801 [8] XOR 3 P2801 [7] XOR 2 P2801 [6] XOR 1 P2801 [5] OR 3 P2801 [4] OR 2 P2801 [3] OR 1 P2801 [2] AND 3 P2801 [1] AND 2 P2801 [0] AND 1
MICROMASTER 440
126 high Priority 1
Level Level Level low
P2800 =...
Operating Instructions 6SE6400-5AW00-0BP0