Page 107
Issue 10/06
3.5.7.12 p1080 = ...
p1082 = ...
p2000 = ...
P2001 = ...
P2002 = ...
P2003 = ...
3 Functions
Reference/limit frequencies 0.00 Hz Min. frequency (entered in Hz) Sets minimum motor frequency [Hz] at which motor will run irrespective of frequency setpoint. If the setpoint falls below the value of p1080, then the output frequency is set to p1080 taking into account the sign. 50.00 Hz Max. frequency (entered in Hz) Sets maximum motor frequency [Hz] at which motor will run irrespective of the frequency setpoint. If the setpoint exceeds the value p1082, then the output frequency is limited. The value set here is valid for both clockwise and anticlockwise rotation. 50.00 Hz Reference frequency (entered in Hz) The reference frequency in Hertz corresponds to a value of 100 %. This setting should be changed if a maximum frequency of higher than 50 Hz is required. It is automatically changed to 60 Hz if the standard 60 Hz frequency was selected using p0100. NOTE This reference frequency effects the setpoint frequency as both the frequency setpoints via USS as well as via PROFIBUS (FB100) (4000H hex 100 % p2000) refer to this value. 1000 V Reference voltage (entered in V) The reference voltage in Volt (output voltage) corresponds to a value of 100 %. NOTE This setting should only be changed if it is necessary to output the voltage with a different scaling. 0.10 A Reference current (entered in A) The reference current in Amps (output current) corresponds to a value of 100 %. Factory setting = 200 % of the rated motor current (P0305). NOTE This setting should only be changed if it is necessary to output the current with a different scaling. 0.12 Mn Reference torque (entered in Nm) The reference torque in Nm corresponds to a value of 100 %. Factory setting = 200 % of the rated motor torque at a constant motor torque determined from the appropriate motor data. NOTE This setting should only be changed if it is necessary to output the torque with a different scaling.
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
107
Page 108
3 Functions
Issue 10/06
3.5.7.13
Inverter protection p0290 = ...
Inverter overload reaction Selects reaction of inverter to an internal over-temperature. 0 Reduce output frequency 1 Trip (F0004 / F0005) 2 Reduce pulse frequency and output frequency 3 Reduce pulse frequency then trip (F0004) Inverter monitoring r0036 i2t P0294 r0037
Heat sink temperature P0292
Inverter overload reaction P0290 A0504 i_max control (U/f) Current control (SLVC, VC)
A0505 A0506 F0004 f_pulse control
IGBT temperature P0292
P0292 =...
0
F0005
15 °C Inverter temperature warning Defines the temperature difference (in ºC) between the Overtemperature trip threshold and the warning threshold of the inverter. The trip threshold is stored internally by the inverter and cannot be changed by the user.
Temperature warning threshold of inverter T_warn Twarn = Ttrip - P0292 Temperature shutdown threshold of inverter T_trip Temperature
P0295 = ...
3.5.7.14
MM440, Frame Size FX GX 95 kW 110 kW 132 kW 160 kW 200 kW CT CT CT CT CT 80 °C 88 °C 91 °C 80 °C 82 °C 88 °C
A-C
D-F
F 600 V
Heat sink
110 °C
95 °C
IGBT
140 °C 145 °C 145 °C 150 °C 150 °C 145 °C 147 °C 150 °C
Input rectifier
-
-
-
75 °C
75 °C
75 °C
75 °C
75 °C
Cooling air
-
-
-
55 °C
55 °C
55 °C
55 °C
50 °C
Control board
-
-
-
65 °C
65 °C
65 °C
65 °C
65 °C
0s Delay, fan shutdown This defines the delay time in seconds between powering down the frequency inverter and then powering-down the fan. A setting of 0 means that the fan is immediately shut down (powered-down).
Motor protection In addition to the thermal motor protection, the motor temperature is also included in the adaptation of the motor equivalent circuit diagram data. Especially for a high thermal motor load, this adaptation has a significant influence on the degree of stability of the closed-loop vector control. For MM440 the motor temperature can only be measured using a KTY84 sensor. For the parameter setting P0601 = 0,1, the motor temperature is calculated / estimated using the thermal motor model. If the frequency inverter is permanently supplied with an external 24V voltage, then the motor temperature is also tracked/corrected using the motor temperature time constant – even when the line supply voltage is switched-out.
MICROMASTER 440
108
Operating Instructions 6SE6400-5AW00-0BP0
Page 109
Issue 10/06
3 Functions
A high thermal motor load and when the line supply is frequently switchedout/switched-in requires, for closed-loop vector control − that a KTY84 sensor is used, or − an external 24V power supply voltage is connected P0335 = ...
Motor cooling (Selects motor cooling system used) 0 Self-cooled: Using shaft mounted fan attached to motor 1 Force-cooled: Using separately powered cooling fan 2 Self-cooled and internal fan 3 Force-cooled and internal fan
0
P0601 = ...
Motor temperature sensor Selects the motor temperature sensor. 0 No sensor 1 PTC thermistor (PTC) 2 KTY84 When "no sensor" or "PTC thermistor (PTC)“ is selected, the motor temperature is determined on the basis of the value estimated by the thermal motor model.
0
Fault F0015
P0601 = 2
5V T1 = 4 s Signal loss detection
ADC
0 1 2
PTC KTY
&
No sensor PTC KTY r0052 Bit13
1 0
≥1
Motor temp. reaction r0035
ϑ
P0601 V
1
P0610
0
Equivalent circuit data Power dissipation PV,mot
Thermal motor model r0631
P0604 r0632 r0633
P0604 = ...
130.0 °C Alarm threshold, motor overtemperature Defines the alarm threshold for the motor overtemperature protection. This threshold, where either a shutdown (trip) or Imax reduction is initiated (P0610) always lies 10 % above the alarm threshold.
ϑtrip = 1.1⋅ ϑwarn = 1.1 ⋅ P0604
ϑwarn : Warning threshold (P0604) ϑtrip : Trip threshold (max. permissible temperature)
The alarm threshold should be at least 40 °C greater than the ambient temperature P0625. P0604 ≥ P0625 + 40 °C
P0610 = ...
p0640 = ...
Inverter temperature reaction Defines reaction when motor temperature reaches warning threshold. 0 No reaction, warning only 1 Warning and Imax reduction (results in a lower output frequency) 2 Warning and trip (F0011)
2
150.0 % Motor overload factor [%] Defines motor overload current limit in [%] relative to p0305 (rated motor current). Limited to maximum inverter current or to 400 % of rated motor current (p0305), whichever is the lower.
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
109
Page 110
3 Functions
3.5.7.15 P0400 =...
Issue 10/06
Encoder 0 Select encoder type Selects the encoder type. 0 Inhibited 1 Single-track pulse encoder 2 Two-track pulse encoder
The table shows the values of P0400 as a function of the number of tracks:
Parameter
Terminal
P0400 = 1
A single ended
A differential
Track
Encoder output
AN P0400 = 2
A single ended
B differential
A AN B BN
In order to guarantee reliable operation, the DIP switches on the encoder module must be set as follows depending on the encoder type (TTL, HTL) and encoder output: Output
Type single ended differential
TTL (e.g. 1XP8001-2)
111111
010101
HTL (e.g. 1XP8001-1)
101010
000000 1024
P0408 =...
Encoder pulses per revolution Specifies the number of encoder pulses per revolution.
P0491 =...
Reaction on speed signal loss Defines the calculation method. 0 No transition 1 Transition into SLVC
P0492 =...
10.00 Hz Allowed speed difference Parameter P0492 defines the frequency threshold for the loss of the encoder signal (fault F0090). CAUTION p0492 = 0 (no monitoring function): With p0492 = 0, the loss of the encoder signal at high frequency as well as at a low frequency is de-activated. As a result, the system does not monitor for the loss of the encoder signal.
P0494 =...
0
10 ms Delay speed loss reaction P0492 is used to detect the loss of the encoder signal at low frequencies. If the motor speed is less than the value of P0492, the loss of the encoder signal is determined using an appropriate algorithm. P0494 defines the delay time between detecting the loss of the speed signal and initiating the appropriate response. CAUTION p0494 = 0 (no monitoring function): With p0494 = 0, the loss of the encoder signal at low frequencies is de-activated. As a result, at these frequencies, a loss of the encoder signal is not detected (loss of the encoder signal at high frequency remains active as long as parameter p0492 > 0).
MICROMASTER 440
110
Operating Instructions 6SE6400-5AW00-0BP0
Page 111
Issue 10/06
3 Functions
3.5.7.16
V/f control
P1300 =...
0 Control mode The control type is selected using this parameter. For the "V/f characteristic" control type, the ratio between the frequency inverter output voltage and the frequency inverter output frequency is defined. 0 V/f with linear 1 V/f with FCC 2 V/f with parabolic characteristic 3 V/f with programmable characteristic (→ P1320 – P1325)
P1310 =...
50.00 % Continuous boost (entered in %) Voltage boost as a % relative to P0305 (rated motor current) and P0350 (stator resistance). P1310 is valid for all V/f versions (refer to P1300). At low output frequencies, the effective resistance values of the winding can no longer be neglected in order to maintain the motor flux.
Linear V/f
V
Boost voltage Vmax
Validity range
Vn (P0304) actual VBoost VConBoost,100
VConBoost,50
0
P1311 =...
tpu Ou olt tv e ag
ON OFF t
⏐f⏐ f V/ ) al = 0 m or 0 N 130 (P t P1310 active 1 0 fn f max (P0310) (P1082)
fBoost,end (P1316)
t f
0.0 % Acceleration boost (entered in %) Voltage boost for accelerating/braking as a % relative to P0305 and P0350. P1311 only results in a voltage boost when ramping-up/ramp-down and generates an additional torque for accelerating/braking. Contrary to parameter P1312, that is only active for the 1st acceleration operation after the ON command, P1311 is effective each time that the drive accelerates or brakes.
Boost-Spannung
V
Gültigkeitsbereich
Vmax Vn (P0304)
ON OFF ng nu n a sp gs n a al m ) sg or = 0 Au n f 0 U/ 30 1 P (
V istBoost
VAccBoost,100
VAccBoost,50
0 f Boost,end (P1316)
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0 t P1311 aktiv 1 0 fn (P0310)
t
⏐f⏐ fmax (P1082)
t f
111
Page 112
3 Functions
P1320 =...
0.0 % Starting boost (entered in %) Voltage boost when starting (after an ON command) when using the linear or square-law V/f characteristic as a % relative to P0305 (rated motor current) or P0350 (stator resistance). The voltage boost remains active until 1) the setpoint is reached for the first time and 2) the setpoint is reduced to a value that is less than the instantaneous ramp-function generator output.
Programmable V/f freq. 0.0 Hz coord. 1 Sets V/f coordinates (P1320/1321 to P1324/1325) to define V/f characteristic.
V
Vn P0304
P1321 =...
Programmable. V/f volt. 0.0 Hz coord. 1
P1322 =...
Programmable V/f freq. 0.0 Hz P1323 coord. 2
P1323 =...
Programmable V/f volt. coord. 2
P1324 =...
Programmable U/f Freq. 0.0 Hz coord. 3
P1325 =...
Programmable V/f volt. coord. 3
0.0 Hz
0.0 Hz
Vmax = f(Vdc, Mmax)
Vmax r0071
P1325
P1321 P1310 f0 0 Hz f1 f2 P1320 P1322
P1310[V] =
P1333 = ...
10.0 % Starting frequency for FCC (entered as a %) Defines the FCC starting frequency as a function of the rated motor frequency (P0310).
P0310 ⋅ P1333 100 P0310 ⋅ (P1333 + 6%) f FCC+Hys = 100 f FCC =
FCC
V/f fFCC
NOTE The constant voltage boost P1310 is continually decreased analog to switching-in FCC.
P1335 = ...
0.0 % Slip compensation (entered in %) Dynamically adjusts output frequency of inverter so that motor speed is kept constant independent of motor load.
f
% P1335
100 % f out fN
0.00
Resonance damping gain V/f Defines resonance damping gain for V/f.
MICROMASTER 440
112 fFCC+Hys
Range of slip compensation :
6 % 10 %
P1338 =...
fmax f P1082 f3 fn P1324 P0310
P1310[%] r0395[%] ⋅ ⋅ P0304[V ] 100[%] 100[%]
Switch-over
P1312 =...
Issue 10/06
Operating Instructions 6SE6400-5AW00-0BP0
Page 113
Issue 10/06
3.5.7.17
3 Functions
Field-orientated control
Limitations p0640 = ...
150.0 % Motor overload factor [%] Defines motor overload current limit in [%] relative to p0305 (rated motor current). Limited to maximum inverter current or to 400 % of rated motor current (p0305), whichever is the lower.
p0640max = p1520 = ...
min (r0209, 4 ⋅ p0305) ⋅ 100 p0305
CO: Upper torque limit FC-spec. Resultant Specifies fixed value for upper torque limit torque limitation. |M|
Power limitation
Stall limitation
P1520 def = 1.5 ⋅ r0333
Torque limitation
P1520 max = ± 4 ⋅ r0333 p1521 = ...
CO: Lower torque limit FC-spec. Enters fixed value of lower torque limitation.
~ r1526 r1527
1 f
~
1 f2 p1530 p1531
P1521 def = − 1.5 ⋅ r0333 |fact|
P1521 max = ± 4 ⋅ r0333 Constant torque p1530 = ...
FC-spec. Motoring power limitation Defines fixed value for the max. permissible motoring active power. P1530 def = 2.5 ⋅ P0307 P1530 max = 3 ⋅ P0307 p1531 = ...
Constant power fstall
Power limitation (motoring, regenerative) M=
P 2⋅π⋅f
M p1530 p1531
Regenerative power limitation FC-spec. Enters fixed value for the max. permissible regenerative active power P1531def = - 2.5 ⋅ P0307 P1531 max = - 3 ⋅ P0307
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
Stall power f p1530 p1531
113
Page 114
3 Functions
Issue 10/06
Sensorless vector control (SLVC) p1300=20 p1452 = ...
0
Control mode 20 Closed-loop Vector control – speed without encoder SLVC can provide excellent performance for the following types of application: • Applications which require high torque performance • Applications which require fast respond to shock loading • Applications which require torque holding while passing through 0 Hz • Applications which require very accurate speed holding • Applications which require motor pull out protection
4 ms Filter time for act. freq (SLVC) Sets time constant of PT1 filter to filter the frequency deviation of speed controller in operation mode SLVC (sensorless vector control). Decreasing the value leads to a higher dynamic of the speed regulation. Instability is seen if the value is to low (or to high). p1452 = 2 can be set for most applications. 3.0 p1470 = ...
Gain speed controller (SLVC) Enters gain of speed controller for sensorless vector control (SLVC).
p1472 = ...
Integral time n-ctrl. (SLVC) Enters integral time of speed controller for sensorless vector control (SLVC). p1488 r1490
400 ms p1489
150 ms Droop
0 p1496 p0341 p0342 1
0 r1518 p1492 Precontrol p1470 p1472 r1084 r1170
– r1438
Kp
Tn
*)
Freq. setpoint
– p1452 r0064 r1508 r0063
Act. frequency from observer model p1610 = ...
p1611 = ...
r0079
*) only active, if pre-control is enabled (p1496 > 0)
50.0 % Continuous torque boost (SLVC) Sets continuous torque boost in lower frequency range of SLVC (sensorless vector control). Value is entered in [%] relative to rated motor torque r0333. p1610 is only effective in the open-loop mode between 0 Hz and approx. ±p1755. 0.0 % Acc. torque boost (SLVC) Sets acceleration torque boost in lower frequency range of SLVC (sensorless vector control). Value is entered in [%] relative to rated motor torque r0333. p1611 is only effective in the open-loop mode between 0 Hz and approx. ±p1755. In opposite to p1610 the acceleration torque boost p1611 is only in operation during acceleration/deceleration.
MICROMASTER 440
114
Torque setpoint
Operating Instructions 6SE6400-5AW00-0BP0
Page 115
Issue 10/06 p1750 = ...
3 Functions
1 Control word of motor model This parameter controls the operation of the sensorless vector control (SLVC) at very low frequencies. This therefore includes the following conditions: Bit00 Start SLVC open loop 0 NO 1 YES (Operation directly after an ON command) Bit01 Zero crossing SLVC open loop 0 NO 1 YES (zero crossing) Start f
Zero crossing f
Closed loop
Closed loop p1755 p1755 Open loop
Open loop t t p1755
For most applications the setting of parameter p1750 = 0 gives the best result at low frequency. p1755 = ...
5.0 Hz Start-freq. motor model (SLVC) Enter the start frequency of sensorless vector control (SLVC), thereby SLVC switches over from open-loop to closed-loop at that frequency. Precontrol
Torque limitation r0062 Frequency setpoint
Speed controller
− p1470 p1452
. .
isq p1750/p1755 open/closed loop p1472 Flux setpoint closed loop
Current controller
Act. output voltage isd p1610 p1611
Flux setpoint open loop
Current measurement iu iv iw Act. angle
+
Act. output frequency
Act. frequency
−
+ Slip
Observer model closed loop
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
0
115
Page 116
3 Functions
Issue 10/06
Vector control with encoder (VC) • First step: Parameterizing the speed encoder (refer to Section 3.5.7.15) • When commissioning Vector Control with encoder-feedback (VC), the drive should be configured for V/f mode (see p1300) first. Run the drive and compare r0061 with r0021 that should agree in: - sign - magnitude (with a deviation of only a few percent)
Only if both criteria are fulfilled, change p1300 and select VC (p1300 = 21/23). • Encoder loss detection must be disabled (p0492 = 0) if torque is limited externally., e.g.: - closed-loop winder control - traversing / moving to a fixed endstop - when using a mechanical brake p1300=21 p1442 = ...
0
Control mode 21 Vector control with sensor
4 ms Filter time for act. speed Sets time constant of PT1 filter to smooth actual speed of speed controller. Decreasing the value leads to a higher dynamic of the speed regulation. Instability is seen if the value is to low. p1442 = 2 can be set for most applications. 3.0 p1460 = ...
Gain speed controller Enters gain of speed controller.
p1462 = ...
Integral time speed controller Enters integral time of speed controller.
400 ms p1488 r1490 p1489
150 ms Droop
0 p1496 p0341 p0342 1
0 r1518 p1492 Precontrol p1460 p1462 r1084 r1170
– r1438
Freq. setpoint
Tn
– p1442 r0063
Act. frequency from encoder
Kp
*) Torque setpoint r0064 r1508
*) only active, if pre-control is enabled (p1496 > 0)
MICROMASTER 440
116 r0079
Operating Instructions 6SE6400-5AW00-0BP0