Page 97
Issue 10/06
3.5.7
3 Functions
Commissioning the application After the motor – drive inverter combination was commissioned using the quick or series commissioning, in the following step parameters should be adapted and set according to the technological requirements. As an example, the following points should be considered: ¾ Functional requirements of the drive inverter (e.g. closed-loop process control with PID controller) ¾ Limit values ¾ Dynamic requirements ¾ Starting torques ¾ Load surge requirement ¾ Overload ¾ Diagnostics If the application includes a function, which is not covered by the quick or series commissioning, then the following sections of the function description or the parameter list should be considered.
Adapting the drive inverter to the application The parameters designated with * offer more setting possibilities than are listed here. Refer to the parameter list for additional setting possibilities. START
Factory setting
P0003 = 3
User access level * 1 Standard: Allows access into most frequently used parameters 2 Extended: Allows extended access e.g. to inverter I/O functions 3 Expert (For expert use only)
3.5.7.1
Serial Interface (USS)
P2010 =...
USS baud rate Sets baud rate for USS communication.
6
P2011 =...
USS address Sets unique address for inverter.
0
P2012 =...
2 USS PZD length Defines the number of 16-bit words in PZD part of USS telegram.
P2013 =...
127 USS PKW length Defines the number of 16-bit words in PKW part of USS telegram.
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
1
Possible Settings: 4 5 6 7 8 9 10 11 12
2400 Baud 4800 Baud 9600 Baud 19200 Baud 38400 Baud 57600 Baud 76800 Baud 93750 Baud 115200 Baud
97
Page 98
3 Functions
Issue 10/06
3.5.7.2
Selection of command source
P0700 =...
2 Selection of command source Selects digital command source. 0 Factory fault setting 1 BOP (keypad) 2 Terminal 4 USS on BOP link 5 USS on COM link 6 CB on COM link
BOP Terminals P0700 = 2
USS BOP link USS COM link
Setpoint channel
CB COM link
3.5.7.3
Digital input (DIN)
P0701 = ...
Function digital input 1 Terminal 5 1 ON / OFF1
1
Function digital input 7 Via analog input, Terminal 3 0 Digital input disabled
0
P0708 = 0
Function digital input 8 Via analog input, Terminal 10 0 Digital input disabled
0
P0724 = ...
Debounce time for digital inputs Defines debounce time (filtering time) used for digital inputs. 0 No debounce time 1 2.5 ms debounce time 2 8.2 ms debounce time 3 12.3 ms debounce time
P0702 = ...
P0703 = ...
P0704 = ...
P0705 = ...
P0706 = ...
P0707 = 0
P0725 = ...
Sequence control
Possible Settings: 0 Digital input disabled 1 ON / OFF1 2 ON + Reverse / OFF1 12 Function digital input 2 3 OFF2 – coast to standstill Terminal 6 4 OFF3 – quick ramp-down 9 Fault acknowledge 12 Reverse 10 JOG right 9 Function digital input 3 11 JOG left Terminal 7 12 Reverse 9 Fault acknowledge 13 MOP up (increase frequency) 14 MOP down (decrease frequency) 15 Function digital input 4 15 Fixed setpoint (Direct selection) Terminal 8 16 Fixed setpoint (Direct selection + ON) 15 Fixed setpoint (Direct selection) 17 Fixed setpoint (Binary coded selection + ON) 15 21 Local/remote Function digital input 5 25 DC brake enable Terminal 16 29 External trip 15 Fixed setpoint (Direct selection) 33 Disable additional freq setpoint 15 99 Enable BICO parameterization Function digital input 6 Terminal 17 15 Fixed setpoint (Direct selection) ON > 3,9 V, OFF < 1,7 V DIN7 1 2 3 4
DIN8 1 2 10 11 3
1 PNP / NPN digital inputs Change-over (toggles) between high active (PNP) and low active (NPN). This applies to all digital inputs simultaneously. 0 NPN mode ==> low active 1 PNP mode ==> high active
MICROMASTER 440
98
Motor control
Operating Instructions 6SE6400-5AW00-0BP0
Page 99
Issue 10/06
3 Functions
DIN channel (e.g. DIN1 - PNP (P0725 = 1)) Kl.9 P24 (PNP) Kl.28 0 V (NPN)
PNP/NPN DIN 0 ... 1 P0725 (1)
P0701 Debounce time: DIN 0 ... 3 P0724 (3)
24 V
Function 0
0
1
1
24 V
T
0
&
Pxxxx BI: ...
r0722 r0722 .0
CO/BO: Bin.inp.val 0V
3.5.7.4
Digital output (DOUT)
P0731 = ...
BI: Function of digital output 1 * Defines source of digital output 1.
52.3
P0732 = ...
BI: Function of digital output 2 * Defines source of digital output 2.
52.7
P0733 = ...
BI: Function of digital output 3 * Defines source of digital output 3.
0.0
P0748 = ...
0 Invert digital output Defines high and low states of relay for a given function.
Common Settings: 52.0 Drive ready 52.1 Drive ready to run 52.2 Drive running 52.3 Drive fault active 52.4 OFF2 active 52.5 OFF3 active 52.6 Switch on inhibit active 52.7 Drive warning active 52.8 Deviation, setpoint / actual value 52.9 Control from PLC (PZD control) 52.A Maximum frequency reached 52.B Alarm: Motor current limiting 52.C Motor holding brake (MHB) active 52.D Motor overload 52.E Motor direction of rotation, clockwise 52.F Frequency inverter overload 53.0 DC brake active .
Invert DOUTs 0 ... 7 P0748 (0)
DOUT channel
CO/BO: State DOUTs r0747 r0747.0
BI: Fct. of DOUT 1
Function xxxx.y rxxxx.y
P0731.C (52:3)
0 0 0 0 1 1 0 0 1 0 0 1 0 1 0 1 0 int. 24 V max. 100 mA Kl.9
0
1
COM Kl.20
-1
P0731 = xxxx.y
NO NC
Kl.19 or Kl.18
Relay : Text DC 30 V / 5 A AC 250 V / 2 A max. opening / closing time 5 / 10 ms
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
Kl.28
99
Page 100
3 Functions
Issue 10/06
Selection of frequency setpoint
P1000 =...
Selection of frequency setpoint 0 No main setpoint 1 MOP setpoint 2 Analog setpoint 3 Fixed frequency 4 USS on BOP link 5 USS on COM link 6 CB on COM link 7 Analog setpoint 2 10 No main setpoint + MOP setpoint 11 MOP setpoint + MOP setpoint 12 Analog setpoint + MOP setpoint
2
...
3.5.7.5
76 77
CB on COM link Analog setpoint 2
+ Analog setpoint 2 + Analog setpoint 2
NOTE In addition to the main setpoint, a supplementary setpoint can be entered using P1000 Example P1000 = 12 : P1000 = 12 ? P1070 = 755
P1000 = 12 ? P1075 = 1050
P1070
CI: Main setpoint r0755
CO: Act. ADC after scal. [4000h]
P1075
CI: Additional setpoint r1050
CO: Act. Output freq. of the MOP
MOP Sequence control ADC FF
P1000 = 12
Additonal setpoint
USS BOP link USS COM link
Setpoint channel P1000 = 12
Motor control
Main setpoint
CB COM link ADC2
P1074 = ...
BI: Disable additional setpoint Deaktiviert den Zusatzsollwert (ZUSW).
0:0
P1075 = ...
CI: Additional setpoint Defines the source of the additional setpoint which is added to the main setpoint. Common settings: 755 Analog input setpoint 1024 Fixed frequency setpoint 1050 MOP setpoint
0:0
P1076 = ...
CI: Additional setpoint scaling Defines the source to scale the additional setpoint. Common settings: 1 Scaling of 1.0 (100 %) 755 Analog input setpoint 1024 Fixed frequency setpoint 1050 MOP setpoint
1:0
MICROMASTER 440
100
Operating Instructions 6SE6400-5AW00-0BP0
Page 101
Issue 10/06
3 Functions
3.5.7.6
Analog input (ADC)
P0756 = ...
0 ADC type Defines the analog input type and activates the monitoring function of the analog input.
0 Unipolar voltage input (0 to +10 V) 1 Unipolar voltage input with monitoring (0 to 10 V) 2 Unipolar current input (0 to 20 mA) 3 Unipolar current input with monitoring (0 to 20 mA) 4 Bipolar voltage input (-10 to +10 V) NOTE For P0756 to P0760, the following applies: Index 0 : Analog input 1 (ADC1), terminals 3, 4 Index 1 : Analog input 2 (ADC2), terminals 10, 11 P0757 =...
Value x1 of ADC scaling
0V
P0761 > 0 0 < P0758 < P0760 || 0 > P0758 > P0760
P0758 =...
P0759 =... P0760 =...
P0761 =...
0.0 %
%
Value y1 of ADC scaling This parameter represents the value of x1 as a % of P2000 (reference frequency). Value x2 of ADC scaling
100 % 4000 h
ASPmax
10 V P0760
Value y2 of ADC scaling 100.0 % This parameter represents the value of x2 as a % of P2000 (reference frequency).
P0758 10 V x100% P0759 20 mA
P0757
Width of ADC deadband 0 V Defines width of deadband on analog input.
V mA
P0761 P0757 = P0761 ASPmin
10 ms Delay, ADC signal loss Defines the delay time between the loss of the analog setpoint and fault message F0080 being displayed. ADC channel DIP switch
P0756
P0753
P0757 P0758 P0759 P0760
P0762 = ...
r0754 P1000 P0761 Setpoint
KL3 ADC+ KL4 ADC−
ADC type
A D
ADC type
ADC dead zone
ADC scaling
P0756
P0761 r0755
Pxxxx r0752
P0762 T
0
F0080
Wire breakage sensing
0
3.9 V r0751 r0722 r0722.6
1.7 V 1
Pxxxx
P0707 Function
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
101
Page 102
3 Functions
Issue 10/06
3.5.7.7
Analog output (DAC)
P0771 = ...
CI: DAC Defines function of the 0 - 20 mA analog output. 21 CO: Output frequency (scaled according to P2000) 24 CO: Frequency inverter output frequency (scaled according to P2000) 25 CO: Output voltage (scaled according to P2001) 26 CO: DC link voltage (scaled according to P2001) 27 CO: Output current (scaled according to P2002) NOTE For P0771 to P0781, the following applies: Index 0 : Analog output 1 (DAC1), terminals 12, 13 Index 1 : Analog output 2 (DAC2), terminals 26, 27
P0773 =...
2 ms Smooth time DAC Defines smoothing time [ms] for analog output signal. This parameter enables smoothing for DAC using a PT1 filter.
P0775 = ...
Permit absolute value Decides if the absolute value of the analog output is used. If enabled, this parameter will take the absolute value of the value to be outputed. If the value was originally negative then the corresponding bit in r0785 is set, otherwise it is cleared. 0 OFF 1 ON
P0776 = ...
DAC type Defines the analog output type. 0 Current output 1 Voltage output
21
0
NOTE • P0776 changes the scaling of r0774 (0 – 20 mA ⇔ 0 – 10 V) • Scaling parameters P0778, P0780 and the dead zone are always entered in 0 – 20 mA For the DAC as voltage output, the DAC outputs must be terminated using a 500 Ω resistor P0777 = ...
P0778 = ...
P0779 = ...
0.0 % Value x1 of DAC scaling Defines the output characteristic value x1 as a %. This parameter represents the lowest analog value as a % of P200x (depending on the setting of P0771).
mA
20 P0780 y2
0 P0781 Value y1 of DAC scaling This parameter represents the value for P0778 y1 x1 in mA. 100.0 % Value x2 of DAC scaling Defines the output characteristic value x2 as a %. This parameter represents the lowest analog value as a % of P200x (depending on the setting of P0771).
P0777 x1
P0779 x2
100 % %
P0780 = ...
Value y2 of DAC scaling This parameter represents the value for x2 in mA.
20
P0781 = ...
Width of DAC deadband Sets width of deadband in [mA] for analog output.
0
MICROMASTER 440
102
Operating Instructions 6SE6400-5AW00-0BP0
Page 103
Issue 10/06
3.5.7.8 P1031 =...
3 Functions
Motor potentiometer (MOP) 0 Setpoint memory of the MOP Saves last motor potentiometer setpoint (MOP) that was active before OFF command or power down. 0 MOP setpoint will not be stored 1 MOP setpoint will be stored (P1040 is updated) 1
P1032 =...
Inhibit negative MOP setpoints 0 Neg. MOP setpoint is allowed 1 Neg. MOP setpoint inhibited
P1040 =...
Setpoint of the MOP Determines setpoint for motor potentiometer control.
5.00 Hz
MOP ramp-up and ramp-down times are defined by the parameters P1120 and P1121. Possible parameter settings for the selection of MOP: Selection
MOP up
MOP down
DIN
P0719 = 0, P0700 = 2, P1000 = 1 or P0719 = 1, P0700 = 2
P0702 = 13 (DIN2)
P0703 = 14 (DIN3)
BOP
P0719 = 0, P0700 = 1, P1000 = 1 or P0719 = 11
UP button
DOWN button
USS on BOP link
P0719 = 0, P0700 = 4, P1000 = 1 or P0719 = 41
USS control word r2032 Bit13
USS control word r2032 Bit14
USS on COM link
P0719 = 0, P0700 = 5, P1000 = 1 or P0719 = 51
USS control word r2036 Bit13
USS control word r2036 Bit14
CB
P0719 = 0, P0700 = 6, P1000 = 1 or P0719 = 61
CB control word r2090 Bit13
CB control word r2090 Bit14
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
103
Page 104
3 Functions
3.5.7.9 P1001 = ...
P1002 = ...
P1003 = ...
Issue 10/06
Fixed frequency (FF) 0.00 Hz Fixed frequency 1 Can be directly selected via DIN1 (P0701 = 15, 16) 5.00 Hz Fixed frequency 2 Can be directly selected via DIN2 (P0702 = 15, 16) 10.00 Hz Fixed frequency 3 Can be directly selected via DIN3 (P0703 = 15, 16)
P1010 = ...
When defining the function of the digital inputs 15.00 Hz Fixed frequency 4 (P0701 to P0703), three different types can be Can be directly selected via DIN4 selected for fixed frequencies: (P0704 = 15, 16) 15 = Direct selection (binary-coded) In this particular mode, the appropriate 20.00 Hz Fixed frequency 5 digital input always selects the associated Can be directly selected via DIN5 fixed frequency, e.g.: (P0705 = 15, 16) Digital input 3 = selects fixed frequency 3. If several inputs are simultaneously active, 25.00 Hz Fixed frequency 6 then these are summed. An ON command is Can be directly selected via DIN6 additionally required. (P0706 = 15, 16) 16 = Direct selection + ON command (binary-coded + On / Off1) 30.00 Hz Fixed frequency 7 In this mode, the fixed frequencies are selected as for 15, however these are 35.00 Hz Fixed frequency 8 combined with an ON command. 17 = Binary coded selection + ON command 40.00 Hz Fixed frequency 9 (BCD-coded + On/ Off1) The BCD-coded operating mode is effective for 45.00 Hz digital inputs 1 to 3. Fixed frequency 10
P1011 = ...
Fixed frequency 11
50.00 Hz
P1012 = ...
Fixed frequency 12
55.00 Hz
P1013 = ...
Fixed frequency 13
60.00 Hz
P1014 = ...
Fixed frequency 14
65.00 Hz
P1015 = ...
Fixed frequency 15
65.00 Hz
P1004 = ...
P1005 = ...
P1006 = ...
P1007 = ... P1008 = ... P1009 = ...
P1016 = ...
1 Fixed frequency code - Bit 0 Defines the selection method for fixed frequencies.
P1017 = ...
Fixed frequency code - Bit 1
1
P1018 = ...
Fixed frequency code - Bit 2
1
P1019 = ...
Fixed frequency code - Bit 3
1
P1025 = ...
Fixed frequency code - Bit 4
1
P1027 = ...
Fixed frequency code - Bit 5
1
1 Direct selection 2 Direct selection + ON command 3 Binary coded selection + ON command NOTE For settings 2 and 3, all parameters P1016 to P1019 must be set to the selected value so that the drive inverter accepts the ON command.
1 2
Direct selection Direct selection + ON command
MICROMASTER 440
104
Operating Instructions 6SE6400-5AW00-0BP0
Page 105
Issue 10/06
3.5.7.10 p1058 = ...
p1059 = ...
3 Functions
JOG 5.00 Hz JOG frequency right Frequency in Hz when the motor is rotating clockwise in the jog mode.
JOG
5.00 Hz JOG frequency left Frequency in Hz when the motor is rotating counter-clockwise in the jog mode.
p1060 = ...
10.00 s JOG ramp-up time Ramp-up time in s from 0 to the maximum frequency (p1082). JOG rampup is limited by p1058 or p1059.
p1061 = ...
10.00 s JOG ramp-down time Ramp-down time in s from the maximum frequency (p1082) to 0.
f p1082 (fmax) p1058 t p1060 p1061
A0923
A0923
"1" DIN
Tippen rechts P1055
BOP USS BOP link USS COM link CB COM link t "0"
(0)
"1" Tippen links P1056 t
"0" (0)
f P1082 P1058
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
P1061
P1060
P1061
P1059 -P1082
P1060 t
105
Page 106
3 Functions
Issue 10/06
3.5.7.11
Ramp function generator (RFG)
p1091 = ...
Skip frequency 1 (entered in Hz) 0.00 Hz Defines skip frequency 1, which avoids effects of mechanical resonance and suppresses frequencies within +/- p1101 (skip frequency bandwidth).
p1092 = ...
Skip frequency 2
0.00 Hz p1093 = ...
Skip frequency 3
0.00 Hz p1094 = ...
Skip frequency 4
0.00 Hz p1101 = ...
Skip frequency bandwidth (entered in Hz)
2.00 Hz p1120 = ...
Ramp-up time (enters the accelerating time in s)
10.00 s
Ramp-down time (enters the deceleration time in s)
10.00 s fout p1101 Skip frequency bandwidth fin p1091 Skip frequency f p1082 (fmax) f1 p1121 = ...
t p1120
Rump-up initial rounding time (entered in s)
0.00 s p1133 = ...
Ramp-down final rounding time (entered in s)
0.00 s p1134 = ...
Rounding type 0 Continuous smoothing 1 Discontinuous smoothing p1130 = ... p1131 = ... p1132 = ...
p1135 = ...
The rounding times are recommended as abrupt responses can be avoided therefore reducing stress and damage to the mechanical 0.00 s Ramp-up final rounding time system. (entered in s) The ramp-up and ramp-down times are Rump-down initial rounding time 0.00 s extended by the component of the rounding ramps. (entered in s)
0
5.00 s OFF3 ramp-down time Defines ramp-down time from maximum frequency to standstill for OFF3 command.
MICROMASTER 440
106 p1121
Operating Instructions 6SE6400-5AW00-0BP0