3 Functions
5.00 s OFF3 ramp-down time (enters the fast stop ramp-down time in s) Enters the time, for example, with which the motor should be braked from the maximum frequency P1082 down to standstill for an OFF3 command (fast stop). If the ramp-down time is parameterized too low, then this can result in alarms A0501 (current limit value), A0502 (overvoltage limit value) or the drive inverter being shutdown with fault F0001 (overcurrent) or F0002 (overvoltage).
P1300 =...
Control mode (enters the required control mode) 0 V/f with linear characteristic 1 V/f with FCC 2 V/f with parabolic characteristic 3 V/f with programmable characteristic 5 V/f for textile applications 6 V/f with FCC for textile applications 19 V/f control with independent voltage setpoint 20 Sensorless Vector control 21 Vector control with sensor 22 Sensorless Vector torque-control 23 Vector torque-control with sensor
0
P1500 =...
Selection of torque setpoint * (enters the source for the torque setpoint) 0 No main setpoint 2 Analog setpoint 4 USS on BOP link 5 USS on COM link (control terminals 29 and 30) 6 CB on COM link (CB = communications module) 7 Analog setpoint 2
0
P1910 = ...
Select motor data identification * (refer to Section 0) 0 Disabled
0
P1960 = ...
0 Speed controller optimization * 0 Inhibited In order to optimize the speed controller, the closed-loop vector control (P1300 = 20 or 21) must be activated. After the optimization has been selected (P1960 = 1), Alarm A0542 is displayed.
P3900 = 1
END
0 End of quick commissioning (start of the motor calculation) 0 No quick commissioning (no motor calculations) 1 Motor calculation and reset of all of the other parameters, which are not included in the quick commissioning (attribute "QC" = no), to the factory setting 2 Motor calculation and reset of the I/O settings to the factory setting 3 Only motor calculation. The other parameters are not reset. NOTE For P3900 = 1,2,3 → P0340 is internally set to 1 and the appropriate data calculated (refer to Section 3.5.4).
End of the quick commissioning/drive setting If additional functions must be implemented at the drive inverter, please use the Section "Commissioning the application" (refer to Section 3.5.7). We recommend this procedure for drives with a high dynamic response.
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
87
Page 88
3 Functions
Issue 10/06
WARNING The motor data identification routine (refer to Section 0) may not be used for loads which are potentially hazardous (e.g. suspended loads for crane applications). Before the motor data identification run is started, the potentially hazardous load must be carefully secured (e.g. by lowering the load to the floor or by clamping the load using the motor holding brake).
3.5.4
Calculating the motor / control data The calculation of the internal motor / control data is initiated using parameter P0340 or indirectly using parameter P3900 (refer to Section 3.5.3) or P1910 (refer to Section 0). The functionality of parameter P0340 can, for example, be used if the equivalent circuit diagram data (refer to Fig. 3-26) or the moment of inertia is known. Possible settings for parameter P0340 are described in Table 3-9. Table 3-10 lists which parameters are calculated for the different settings. Table 3-9
Possible settings for parameter P0340
Parameter
Description
P0340 = 0
No calculation is made
P0340 = 1
Starting from the rating plate parameters (P0300 - P0335) the motor equivalent circuit diagram parameters (P0350 - P0369) and the motor weight / moment of inertia (P0344, P0341) are determined. The V/f- / vector control parameters and reference quantities are then pre-assigned (this includes all calculations from P0340 = 2,3,4).
P0340 = 2
Starting from the rating plate parameters, the motor equivalent circuit diagram parameters (P0350 - P0369) are calculated (without any additional pre-assignments being made).
P0340 = 3
Starting from the motor equivalent circuit diagram parameters (P0350 - P0369) and motor weight / moment of inertia, moment of inertia ratio (P0344, P0341, P0342), the V/f- / vector control parameters are determined (contains all of the calculations from P0340 = 4).
P0340 = 4
Starting from the motor equivalent circuit diagram parameters (P0350 - P0369) and motor weight / moment of inertia, moment of inertia ratio (P0344, P0341, P0342), the vector control parameters are pre-assigned.
NOTE ¾ When exiting the quick commissioning with P3900 > 0 (refer to Section 3.5.3), internally P0340 is set to 1 (complete parameterization). ¾ For the motor data identification (refer to Section 0), after the measurement has been completed, internally P0340 is set to 3. ¾ Equivalent circuit diagram data always refer to the star circuit configuration equivalent circuit diagram. If data for the delta equivalent circuit diagram are available, then this should first be converted into the star equivalent circuit diagram data before being entered. ¾ If equivalent circuit diagram data (P0350, . . ., P0360) is available, then this must be entered according to the motor circuit configuration being used (a star circuit configuration requires star-type equivalent circuit diagram data). If there is no consistency between the motor circuit configuration and the equivalent circuit diagram data, then the equivalent circuit diagram data should be converted according to the motor circuit configuration actually being used (P0350∆ = P0350Y, etc.).
MICROMASTER 440
88
Operating Instructions 6SE6400-5AW00-0BP0
Page 89
Issue 10/06
3 Functions
Table 3-10
Calculated parameters P0340 = 1 P0340 = 2 P0340 = 3 P0340 = 4
P0341[3] Motor inertia [kg*m^2] x
P0342[3] Total/motor inertia ratio P0344[3] Motor weight x
P0346[3] Magnetization time P0347[3] Demagnetization time x
P0350[3] Stator resistance (line-to-line)
x x
P0352[3] Cable resistance P0354[3] Rotor resistance x x x x
P0356[3] Stator leakage inductance x x
P0358[3] Rotor leakage inductance x x
P0360[3] Main inductance x x
P0362[3] Magnetizing curve flux 1 x x
P0363[3] Magnetizing curve flux 2 x x
P0364[3] Magnetizing curve flux 3 x x
P0365[3] Magnetizing curve flux 4 x x
P0366[3] Magnetizing curve imag 1 x x
P0367[3] Magnetizing curve imag 2 P0368[3] Magnetizing curve imag 3 x x x x
P0369[3] Magnetizing curve imag 4 P0625[3] Ambient motor temperature x x x x
P1253[3] Vdc-controller output limitation x x
P1316[3] Boost end frequency P1460[3] Gain speed controller x x x x x
P1462[3] Integral time speed controller P1470[3] Gain speed controller (SLVC)
x x x x x x
P1472[3] Integral time n-ctrl. (SLVC)
x x x
P1520[3] CO: Upper torque limit x
P1521[3] CO: Lower torque limit x
P1530[3] Motoring power limitation x
P1531[3] Regenerative power limitation x
P1715[3] Gain current controller x x x
P1717[3] Integral time current controller x x x
P1764[3] Kp of n-adaption (SLVC)
x x x
P1767[3] Tn of n-adaption (SLVC)
x x x
P2000[3] Reference frequency P2002[3] Reference current x
P2003[3] Reference torque x
P2174[3] Torque threshold M_thresh x
P2185[3] Upper torque threshold 1 x
P2186[3] Lower torque threshold 1 P2187[3] Upper torque threshold 2 x
P2188[3] Lower torque threshold 2 x
P2189[3] Upper torque threshold 3 x
P2190[3] Lower torque threshold 3 x x x x x x x
When calculating the motor / control data using P0340, there are different scenarios (refer to the following flowchart), which can be called-up as a function of the known data.
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
89
Page 90
3 Functions
Issue 10/06
START Factory setting 0 Calculation of motor parameters This parameter is required during commissioning in order to optimize the operating behavior of the drive inverter. For the complete parameterization (P0340 = 1), in addition to the motor / control parameters, parameters are preassigned which refer to the rated motor data (e.g. torque limits and reference quantities for interface signals). A list of the parameters, which are calculated, depending on the setting of P0340, are included in the parameter list. 0 No calculation 1 Complete parameterization 2 Calculation of equivalent circuit data 3 Calculation of V/f and Vector control data 4 Calculation of controller settings only
P0340 = 1
Additional Catalog and/or ECD data known ? no yes P0341 = ...
Motor inertia [kgm2]
FU-spez.
P0342 = ...
Total/motor inertia ratio
FU-spez.
P0344 = ...
Motor weight (entered in kg)
FU-spez.
ECD data known ? no P0340 = 4 yes Calculation of motor parameters 4 Calculates the controller setting (refer to parameter P0340)
P0350 = ...
FU-spez. Stator resistance (line-to-line) (entered in Ω) Stator resistance in Ω of the motor which is connected (from line-to-line). This parameter value also includes the cable resistance.
P0354 = ...
FU-spez. Rotor resistance (entered in Ω) Defines the rotor resistance of the motor equivalent diagram (phase value).
P0356 = ...
FU-spez. Stator leakage inductance (entered in mH) Defines the stator leakage inductance of the motor equivalent diagram (phase value).
P0358 = ...
FU-spez. Rotor leakage inductance (entered in mH) Defines the rotor leakage inductance of the motor equivalent diagram (phase value).
P0360 = ...
FU-spez. Main inductance (entered in mH) Defines the main (magnetizing) inductance of the motor equivalent diagram (phase value).
P0340 = 3
0 Calculation of motor parameters 3 Calculation of V/f and Vector control All of the parameters, dependent on the ECD data are calculated and, in addition, the controller settings (P0340 = 4).
END
The motor parameters have been calculated and it is now possible to return to the additional parameterization in the Section 3.5.7 "Commissioning the application".
MICROMASTER 440
90
0
Operating Instructions 6SE6400-5AW00-0BP0
Page 91
Issue 10/06
3.5.5
3 Functions
Motor data identification MICROMASTER has a measuring technique which is used to determine the motor parameters: ¾ Equivalent circuit data (ECD, refer to Fig. 3-26) → P1910 = 1 → P1910 = 3
¾ Magnetizing characteristic (refer to Fig. 3-27)
For control-related reasons, we absolutely recommend that the motor data identification is carried-out as, starting from the rating plate data, it is only possible to estimate the equivalent circuit data, the motor cable resistance, the IGBT letthrough voltage and the compensation of IGBT interlocking times. For example, the stator resistance is extremely important for the stability of the closed-loop Vector control and for the voltage boost for the V/f characteristic. The motor data identification routine should be executed, especially if long feeder cables or if thirdparty motors are being used. If the motor data identification routine is being started for the first time, then the following data (refer to Fig. 3-26) is determined, starting from the rating plate data (rated [nominal] data) with P1910 = 1: ¾ Equivalent circuit data ¾ Motor cable resistance ¾ IGBT on-state voltage and compensation of IGBT gating dead times The rating plate data represent the initialization values for the identification. This is the reason that it is necessary to have correct and consistent input of the rating plate data when determining the data specified above (refer to Section 3.5.8).
Inverter
Cable
Stator res. (L2L) 0.00001 ... 2000.00000 [Ohm] P0350.D (4.00000)
On-state voltage Gating dead time 0.0 ... 20.0 [V] 0.00 ... 3.50 [us] P1825 (1.4) P1828 (0.50)
Cable resistance 0.0 ... 120.0 [Ohm] P0352.D (0.0)
R Cable
C Cable
Fig. 3-26
Motor
Rotor leak.induct. 0.0 ... 1000.0 P0358.D (10.0) Stator leak.induct Rotor resistance 0.00001 ... 1000.00000 0.0 ... 300.0 [Ohm] P0356.D (10.00000) P0354.D (10.0)
P0350 = 2(RCable + R S)
RS
L?R
L?S
Main inductance 0.0 ... 3000.0 P0360.D (10.0)
RR
LM
Equivalent circuit diagram (ECD)
In addition to the equivalent circuit data, the motor magnetizing characteristic (refer to Fig. 3-26) can be determined using the motor data identification (P1910 = 3). If the motor-drive inverter combination is operated in the field-weakening range, then this characteristic should be determined, especially when Vector control is being used. As a result of this magnetizing characteristic, MICROMASTER can, in the field-weakening range, more precisely calculate the current which is generating the field and in turn achieve a higher torque accuracy.
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
91
Page 92
3 Functions
Issue 10/06
Φ [%] P0365 P0364 100 % P0363 P0362
0
P0366 P0367 100 % P0368
P0369 iµ [%] iµ [A] iµ [%] = r0331
Fig. 3-27
Magnetizing characteristic
After selecting the motor data identification using parameter P1910, alarm A0541 is immediately generated. The motor identification routine is started by the ON command and different excitation signals are impressed in the motor (DC and AC voltages). This measurement is carried-out with the motor at a standstill and it takes, including the data calculation per selection (P1910 = 1.3) between 20 s ... 4 min. The identification time depends on the motor and increases with its size (this takes approx. 4 min for a 200 kW motor). The motor data identification routine must be carried-out with the motor in the cold condition so that the motor resistance values saved can be assigned to the parameter of the ambient temperature P0625. Only then is correct temperature adaptation of the resistances possible during operation. The motor data identification routine operates with the results of the "Complete parameterization" P0340 = 1 or the motor equivalent diagram data which was last saved. The results become increasingly better the more times that the identification routine is executed (up to 3 times).
WARNING ¾ It is not permissible to carry-out the motor identification routine for loads which are potentially hazardous (e.g. suspended loads for crane applications). Before starting the motor data identification routine, the potentially hazardous load must be secured (e.g. by lowering the load to the floor or clamping the load using the motor holding brake). ¾ When starting the motor data identification routine, the rotor can move into a preferred position. This is more significant for larger motors.
MICROMASTER 440
92
Operating Instructions 6SE6400-5AW00-0BP0
Page 93
Issue 10/06
3 Functions
NOTE ¾ The equivalent circuit data (P0350, P0354, P0356, P0358, P0360), with the exception of parameter P0350, should be entered as phase values. In this case, parameter P0350 (line-to-line value) corresponds to twice the phase value. ¾ Equivalent circuit diagram data always refer to the star circuit configuration equivalent circuit diagram data. If data for the delta equivalent circuit diagram is available, then this data must be converted into the star equivalent circuit diagram data before being entered (refer to Section 0). ¾ The motor cable resistance P0352 is defined as phase value ¾ During the motor identification routine, the stator resistance and the motor cable resistance are determined and entered into parameter P0350. If a correction is made in parameter P0352, then MICROMASTER defines the motor cable resistance using the following relationship: P0352 = 0.2 * P0350. ¾ If the motor cable resistance is known, then the value can be entered into parameter P0352 after the motor data identification. The stator resistance is appropriately reduced as a result of this entry and is therefore more precisely adapted to the actual application. ¾ It is not necessary to lock the motor rotor for the motor data identification routine. However, if it is possible to lock the motor rotor during the identification routine (e.g. by closing the motor holding brake), then this should be used to determine the equivalent circuit diagram data. ¾ The following formula can be applied to check the correctness of the motor rating plate data: PN = √3 ∗ VN Υ∗ INΥ ∗ cosϕ ∗ η ≈ √3 ∗ VN ∆∗ IN∆ ∗ cosϕ ∗ η with PN rated motor power VN Υ, VN ∆ rated motor voltage (star / delta) IN Υ, IN ∆ rated motor current (star / delta) cosϕ power factor η efficiency
Motor data identification routine START Factory setting
P0625 = ?
| Motor temp. - P0625| ≤ 5 °C ? yes no
20 °C Ambient motor temperature (entered in °C) The motor ambient temperature is entered at the instant that motor data is being determined (factory setting: 20 °C). The difference between the motor temperature and the motor ambient temperature P0625 must lie in the tolerance range of approx. ± 5 °C. If this is not the case, then the motor data identification routine can only be carried-out after the motor has cooled down.
Allow the motor to cool down
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
93
Page 94
3 Functions
Issue 10/06
P1910 = 1 A0541
0 Select motor data identification with P1910 = 1 p1910 = 1: Identifies the motor parameter with parameter change. These are accepted and applied to the controller. When p1910 = 1 is selected, Alarm A0541 (motor data identification active) is output, and internally p0340 is set to 3.
ON
Starts the motor data identification run with p1910 = 1 The measuring operation is initiated with the continuous (steady-state) ON command. The motor aligns itself and current flows through it. Diagnostics is possible using r0069 (CO: Phase current). After the motor data identification routine has been completed, p1910 is reset (p1910 = 0, motor data identification routine inhibited) and Alarm A0541 is cleared (deleted).
OFF1
In order to set the frequency converter into a defined state, an OFF1 command must be issued before the next step.
P1910 = 3 A0541
0 Select motor data identification with P1910 = 3 p1910 = 3: Identifies the saturation characteristic with parameter change. When p1910 = 3 is selected, Alarm A0541 (motor data identification active) is output and internally, p0340 is set to 2.
ON
Starts the motor data identification run with P1910 = 3 The measuring operation must be started with a continuous ON command. After the motor identification routine has been completed, p1910 is reset (p1910 = 0, motor data identification routine inhibited) and Alarm A0541 is cleared (deleted).
OFF1
In order to set the frequency converter into a defined state, an OFF1 command must be issued before the next step.
END
If problems occur during the identification run, e.g. the current controller oscillates, then the rating plate data should be re-checked and an approximately correct magnetizing current P0320 entered. The motor data identification routine should then be re-started by calling P0340 = 1 (refer to Section 3.5.4).
MICROMASTER 440
94
Operating Instructions 6SE6400-5AW00-0BP0
Page 95
Issue 10/06
3.5.6
3 Functions
Magnetizing current ¾ The value of the magnetizing current r0331/P0320 has a significant influence on the closed-loop control. This cannot be measured at standstill. This means that the value is estimated for standard 4-pole 1LA7 SIEMENS standard using the automatic parameterization P0340=1 (P0320=0; result in r0331). ¾ If the deviation of the magnetizing current is too high, then the values for the magnetizing reactance and those of the rotor resistance will not be able to be accurately determined. ¾ Especially for third-party motors it is important that the magnetizing current that is determined, is carefully checked and if required, appropriately corrected. The procedure to manually determine the magnetizing current and to re-calculate the equivalent circuit diagram data when the drive is operated with closed-loop vector control (P1300 = 20/21) is shown in the following.
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
95
Page 96
3 Functions
Issue 10/06
START
Quick commissioning
Quick commissioning routine Using the quick commissioning routine the frequency inverter is adapted to the motor and important technology parameters are set.
Motor data identificationdentif
Motor data identification routine Using the motor data identification routine motor equivalent circuit diagram data is determined using a measuring technique.
Operation under no-load conditions
Determing the magnetizing current In order to determine the magnetizing current (P0320/r0331), the motor should be accelerated up to approximately 80% of its rated speed under no-load operating conditions. In so doing, the following conditions must be carefully maintained: − the vector control must be activated, P1300 = 20.21 − no field weakening (r0056.8 = 0) − flux setpoint, r1598 = 100 % − no efficiency optimization, P1580 = 0 % No-load operation means that the motor is operated without a load (i.e. no coupled driven machine). Under steady-state conditions, a current r0027 is obtained that approximately corresponds to the rated magnetizing current r0331. (the current is always less than the no-load current for a pure V/f control).
Criterium fulfilled ?
Measuring and entering the magnetizing current and therefore the associated new calculation of the equivalent circuit diagram data of the motor is an iterative procedure. It must be repeated at least 2-3 times until the following criteria are fulfilled: − The more accurate the value of the magnetizing current that was entered, the better the flux setpoint (r1598=100%) matches the flux actual value (r0084=96..104%) of the observer model. − The output Xm adaptation (r1787) of the observer model should be as low as possible. Good values lie between 1-5%. The less that the Xh adaptation of the observer must operate, the sensitivity of the motor parameters after power failures are that much less sensitive. NOTE In order to display r0084 at the BOP/AOP, the LEVEL 4 parameters must be enabled using service parameter P3950=46.
no yes
0
P0320 = ...
Calculating P0320 Now, the new value can be entered in P0320 from the determined fluxgenerating current component r0029 by applying the following equation. P0320 = r0029 * 100 / P0305
P0340 = 1
0 Calculating the motor parameters The values of the motor equivalent circuit diagram data are calculated from the entered rating plate data. In addition, the parameters of the controls are pre-set (subsequently optimized) (P0340 = 3).
END