Page 77
Issue 10/06
3.5
3 Functions
Commissioning A differentiation is made between the following scenarios when commissioning MICROMASTER: ¾ 50/60 Hz changeover ¾ Quick commissioning ¾ Motor data identification ¾ Calculating the motor / control data ¾ Series commissioning ¾ Commissioning the application
Start commissioning
Carry-out checklist
NEMA motor 60 Hz / hp ? Section 3.5.2 yes 50/60 Hz setting Section 3.5.1 no
Complete parameter list of a commissioning available ?
no Quick commissioning Section 3.5.3 no
Is the moment of inertia of the motor and load known ?
yes yes P0341 = ? P0342 = ? P0344 = ? P0340 = 1 Series commissioning Section 3.5.7
Motor equivalent circuit diagram data known ? Motor data identification Section 3.5.5 no yes Enter motor equivalent circuit diagram data Section 3.5.4
Commissioning the application Section 3.5.6
End of commissioning
Fig. 3-20
Procedure when commissioning
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
77
Page 78
3 Functions
Issue 10/06
When commissioning, initially, a quick or series commissioning should be carriedout. The actual application should only be commissioned if the drive inverter – motor combination provides a satisfactory result. If the drive is to be commissioned from a defined state, then the drive inverter can be reset to the initial state when it left the plant. This is done as follows: ¾ Reset parameters to the factory setting
Check list The following check list should help you to commission MICROMASTER without any problems and to guarantee a high degree of availability: ¾ When handling the drive unit, carefully observe all of the ESD measures. ¾ All of the screws must have been tightened up to their specified torque. ¾ All connectors / option modules must have been correctly inserted and locked / screwed into place. ¾ The DC link pre-charging has been completed. ¾ All of the components are grounded/earthed at the points provided and all of the shields have been connected. ¾ MICROMASTER drive units have been designed for defined mechanical, climatic and electrical ambient conditions. It is not permissible that the specified limit values are exceeded in operation and when the drive units are being transported. The following must be especially carefully observed: ♦ Line supply conditions ♦ Pollutant stressing ♦ Gases which can have a negative impact on the function ♦ Ambient climatic conditions ♦ Storage / transport ♦ Shock stressing ♦ Vibration stressing ♦ Ambient temperature ♦ Installation altitude
In addition to carrying-out all of the installation work, an important prerequisite for successful commissioning is that the drive inverter is not disconnected from the line supply while being parameterized. If a line supply failure interrupts commissioning, then inconsistencies can occur regarding the parameterization. In this case, it is important that the commissioning is re-started (possibly reset and establish the original factory settings (refer to Section 3.5.9)).
NOTE When using output reactors, the pulse frequency may not be set higher than 4 kHz. The following parameter setting is mandatory when using an output reactor: P1800 = 4 kHz , P0290 = 0 or 1
MICROMASTER 440
78
Operating Instructions 6SE6400-5AW00-0BP0
Page 79
Issue 10/06
3.5.1
3 Functions
50/60 Hz setting
Remove I/O board
The frequency setting made in the factory can be adapted to the North American market, without requiring any parameterization using an operator panel or PC tool using the DIP50/60 switch (refer to Fig. 3-21) under the I/O board (refer to the Appendix C when removing the I/O board).
Fig. 3-21
DIP50/60
DIP switch to change-over between 50/60 Hz
The switch determines the value of parameter P0100 corresponding to the following diagram (refer to Fig. 3-22). Besides P0100 = 2, after the power supply voltage has been switched-in, the DIP50/60 switch determines the 50/60 Hz setting (value of parameter P0100). Quick commissioning P0010 = 1
Power cycle
P0100 = 2 ?
yes yes no no no
DIP2 = OFF ?
P0100 = 2 ?
P0100 = 1 ? yes no yes
Fig. 3-22
Power in kW Frequency 50 Hz
Power in kW Frequency 60 Hz
Power in hp Frequency 60 Hz
P0100 = 0
P0100 = 2
P0100 = 1
Mode of operation of the DIP50/60 switch in conjunction with P0100
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
79
Page 80
3 Functions
Issue 10/06
By changing the setting of DIP50/60 switch, after the drive inverter has been powered-down/powered-up, the parameters for the rated motor frequency P0310, max. frequency P1082 and reference frequency P2000 are automatically pre-set. In addition, the rated motor parameters as well as all of the other parameters which depend on the rated motor parameters, are reset. The units of the power parameters are, depending on P0100, are either interpreted as kW value or hp value.
NOTE Switch DIP2(1) (refer to Fig. 3-21) under the I/O board has no function.
3.5.2
Motor circuit In order to ensure a straightforward, successful commissioning, it is important that the circuit connection in the motor terminal box (refer to Fig. 3-23) matches the rated motor voltage entered in P0304 or the rated motor current P0305. IEC Motor
W2
U2
V2
U1
V1
W1
W2
U2
V2
U1
V1
W1
U1 U1
V1 W1
V1 W1
Delta connection
Star connection e.g.: Volts 230 V (Delta connection) / 400 V (Star connection) T1
NEMA Motor
Volts low high
U
V
Connected together
Connection
T4-T5-T6
YY
T1-T7 T2-T8 T3-T9
Y
W
T1-T7 T2-T8 T3-T9 T1
T2
T3
T4 T7 T8 T5
T6T9 e.g.: Volts 230 V YY (low) / 460 V Y (high)
T3
T2
T1
Volts low high Fig. 3-23
U
V
W
Connected together
T1-T6-T7 T2-T4-T8 T3-T5-T9
-
T2
T4-T7 T5-T8 T6-T9
T1
T3
Connection
∆∆ ∆
T3
T4 T7
T8 T5
T2
Motor terminal box
MICROMASTER 440
80
T9 T6
Operating Instructions 6SE6400-5AW00-0BP0
Page 81
Issue 10/06
3 Functions
The following must be noted when entering the rating plate data or the ESB data: ¾ The outer conductor voltage/phase-to-phase voltage (voltage U12 between outer conductors L1, L2) and the outer conductor current (phase current) I1 are always specified on the rating plate. ¾ The rated motor voltage P0304 and the rated motor current P0305 must always be entered according to the motor circuit configuration (either delta/star circuit configuration). ¾ If rated motor data that are available (P0304, P0305) are not consistent with the motor circuit configuration, then an appropriate conversion should be made which is then entered. ¾ If equivalent circuit diagram data (P0350, P0354, P0356, P0358, P0360) is available, then these should be entered according to the motor circuit configuration. If there is no consistency between the motor circuit configuration and equivalent circuit diagram data, then the equivalent circuit diagram data should be converted and entered corresponding to the data on the rating plate (P0304, P0305). I1
1 U12
U12
Z
U1N
N 2
Z
2
Z
3
Z
I1,∆ =
1 3
I1,Y
U12 = U23 = U31 = 3 ⋅ U1Ν
U12, ∆ =
1
U12 = 2⋅ Z I1
Z12, ∆ =
Z12,Y 3
3
U12, Y
Z
I12 Z
3
I1 = I2 = I3
Fig. 3-24
I1
1
I1N
I12 = I23 = I31 =
1 3
⋅ I1
U12 = U23 = U31 U12 2 = ⋅Z 3 I1
Star / delta circuit configurations
NOTE The precise equivalent circuit diagram data are of extreme important regarding the stability of the closed-loop vector control and for the voltage boost applied to the V/f characteristic. Equivalent circuit diagram data can only be estimated from the rating plate data; this is the reason that equivalent circuit diagram data is either determined - using the motor data identification (refer to Chapter 0), or - is entered from a motor data sheet that may be available (refer to Chapter 0).
NOTE The MICROMASTER series of drive units is not available for 3-ph. 690 V AC.
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
81
Page 82
3 Functions
Issue 10/06
87 Hz characteristic When a motor with a delta circuit configuration (e. g. VN∆, motor = 230 V) is fed from a frequency inverter, where the rated voltage corresponds to the star circuit configuration (e.g. 400 V frequency inverter), then it is important to proceed as follows and observe the following: ¾ The motor must have the appropriate voltage strength. ¾ Above the rated motor frequency, the iron losses in the motor increase overproportionally. This is the reason that above this frequency, the thermal motor torque should be reduced. ¾ For the quick commissioning, the rating plate data for the delta circuit configuration should be entered or the rating plate must be appropriately converted. ¾ The drive inverter must be designed for the higher current (delta circuit configuration). ¾ The 87 Hz characteristic is independent of the control type and can therefore be used both for V/f control as well as for closed-loop vector control. ¾ When using the 87 Hz characteristic, the mechanical motor limits must be taken into account (refer to Catalog M11). For the 87 Hz characteristic, the ratio between the voltage and frequency (V/f characteristic) remain constant. This is the reason that the following relationships apply: U UN1 (400 V) UN∆ (230 V)
V/f characteristic
Table 3-8
Example 1LA7060-4AB10
UN1 ⋅ PN∆ UN∆ f N1 =
UN1 ⋅ f N∆ UN∆
P = power f = frequency n = speed p = pole pair No.
⎡ s ⎤ 60 ⎢ ⎥ ⎣ min ⎦ ( − nN1 = f N1 f N∆ ) + n ∆ p f fN∆(50 Hz) fN1(87 Hz)
Fig. 3-25
PN1 =
Delta circuit configuration
87 Hz characteristic
Star circuit configuration
P0304
Rated motor voltage
230 V
400 V
400 V
P0305
Rated motor current
0.73 A
0.73 A
0.42 A
P0307
Rated motor power
120 W
207 W
120 W
P0308
Cos ϕ
0.75
0.75
0.75
P0310
Rated motor frequency
50 Hz
87 Hz
50 Hz
P0311
Rated motor speed
1350 RPM
2460 RPM
1350 RPM
P0314
Motor pole pairs
2
2
2
Contrary to the BOP, AOP operator panels or the commissioning program DriveMonitor, the STARTER commissioning (start-up) program offers a mask-orientated quick commissioning, which is especially advantageous for users who are using MICROMASTER for the first time. On the other hand, BOP, AOP and DriveMonitor offer, in conjunction with the drive inverter, parameter-orientated quick commissioning where the user is navigated through the menu tree mentioned.
MICROMASTER 440
82
Operating Instructions 6SE6400-5AW00-0BP0
Page 83
Issue 10/06
3.5.3
3 Functions
Quick commissioning If there is still no appropriate parameter set for the drive, then a quick commissioning must be carried-out for the closed-loop Vector control and for the V/f control including a motor data identification routine. The following operator units can be used to carry-out quick commissioning: ¾ BOP (option) ¾ AOP (option) ¾ PC Tools (with commissioning program STARTER, DriveMonitor) When the quick commissioning is carried-out, the motor – drive inverter is basically commissioned; the following data must be obtained before quick commissioning is started: ¾ Line supply frequency ¾ Motor rating plate data ¾ Command / setpoint sources ¾ Min. / max. frequency or ramp-up / ramp-down time ¾ Closed-loop control mode ¾ Motor data identification
Parameterizing the drive with BOP or AOP The frequency inverter is adapted to the motor using the quick commissioning function and important technological parameters are set. The quick commissioning shouldn't be carried-out if the rated motor data saved in the frequency inverter (4-pole 1LA Siemens motor, star circuit configuration frequency inverter (FU)specific) match the rating plate data. Parameters, designated with a * offer more setting possibilities than are actually listed here. Refer to the parameter list for additional setting possibilities.
NOTE ¾ Parameter P0308 or P0309 can only be viewed on the BOP or AOP if P0003 ≥ 2. Depending on the setting of parameter P0100, either P0308 or P0309 is displayed. ¾ The value entered into P0307 and all of the other power data – depending on P0100 – are either interpreted as kW or hp value.
START
Factory setting
P0003 = 3
User access level * 1 Standard: Allows access into most frequently used parameters 2 Extended: Allows extended access e.g. to inverter I/O functions 3 Expert (For expert use only)
1
P0004 = 0
Parameter filter * 0 All parameters 2 Inverter 3 Motor 4 Speed sensor
0
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
83
Page 84
3 Functions
P0010 = 1
Issue 10/06
0
Commissioning parameter * 0 Ready 1 Quick commissioning 30 Factory setting (refer to Section 3.5.9)
NOTE P0010 should be set to 1 in order to parameterize the data of the motor rating plate.
P0100 =... P0100 = 1, 2 P0100 = 0
0 Europe/ North America (enters the line supply frequency) 0 Europe [kW], frequency default 50 Hz 1 North America [hp], frequency default 60 Hz 2 North America [kW], frequency default 60 Hz NOTE For P0100 = 0 or 1, the setting of switch DIP50/60 determines the value of P0100 (refer to Section 3.5.1).
OFF = kW, 50 Hz ON = hp, 60 Hz P0205 =... P0205 =... Inverter application (enters the required torque) 0 Constant torque (e.g. compressors, processing machines) 1 Variable torque (e.g. pumps, fans) NOTE This parameter is only effective for drive inverters ≥ 5.5 kW / 400 V
0
1 P0300 =... P0300 =... Select motor type 1 Asynchronous motor (induction motor) 2 Synchronous motor NOTE For P0300 = 2 (synchronous motor), only the V/f control types (P1300 < 20) are permitted. FU-spec. P0304 =... P0304 =... Rated motor voltage (Nominal motor voltage [V] from rating plate) The rated motor voltage on the rating plate must be checked, regarding the star/delta circuit configuration to ensure that it matches with the circuit connection configured at the motor terminal board
P0305 =... P0305 =... Rated motor current (Nominal motor current [A] from rating plate)
P0310 P0304
FU-spec.
FU-spec. P0307 P0305 P0307 =... P0307 =... Rated motor power P0308 P0311 (Nominal motor power [kW/hp] Example of a typical motor rating plate (data for from rating plate) If P0100 = 0 or 2, value will be in kW. a delta circuit configuration). The precise definition and explanation of this If P0100 = 1, value will be in in hp. data is specified in DIN EN 60 034-1.
P0308 =...
P0308 =... Rated motor cosPhi (Nominal motor power factor (cos ϕ) from rating plate) If the setting is 0, the value is automatically calculated P0100 = 1,2: P0308 no significance, no entry required.
P0309 =... P0309 =... Rated motor efficiency (Nominal motor efficiency in [%] from rating plate) Setting 0 causes internal calculation of value. P0100 = 0: P0309 no significance, no entry required.
MICROMASTER 440
84
FU-spec.
FU-spec.
Operating Instructions 6SE6400-5AW00-0BP0
Page 85
Issue 10/06
3 Functions
50.00 Hz
P0310 =...
Rated motor frequency (Nominal motor frequency in [Hz] from rating plate) Pole pair number recalculated automatically if parameter is changed.
P0311 =...
FU-spec. Rated motor speed (Nominal motor speed in [rpm] from rating plate) Setting 0 causes internal calculation of value. NOTE An entry must be made for closed-loop Vector control, V/f control with FCC and for slip compensation.
P0320 = ...
0.0 Motor magnetizing current (this is entered as a % referred to P0305) Motor magnetizing current as a % relative to P0305 (rated motor current). With P0320 = 0, the motor magnetizing current is calculated using P0340 = 1 or using P3900 = 1 - 3 (end of the quick commissioning) – and is displayed in parameter r0331. 0
P0335 =...
Motor cooling (Selects motor cooling system used) 0 Self-cooled: Using shaft mounted fan attached to motor 1 Force-cooled: Using separately powered cooling fan 2 Self-cooled and internal fan 3 Force-cooled and internal fan
P0640 =...
150 % Motor overload factor (Motor overload factor in [%] relative to P0305) This defines the limit of the maximum output current as a % of the rated motor current (P0305). This parameter is set, using P0205 for constant torque, to 150 %, and for variable torque, to 110 %.
P0700 =...
Selection of command source (enters the command source) 0 Factory default setting 1 BOP (keypad) 2 Terminal 4 USS on BOP link 5 USS on COM link (control terminals 29 and 30) 6 CB on COM link (CB = communications module)
2
BOP Terminals USS BOP link
P0700 = 2
Sequence control
USS COM link CB COM link
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
Setpoint channel
Motor control
85
Page 86
3 Functions
2
Selection of frequency setpoint * (enters the frequency setpoint source) 1 MOP setpoint 2 Analog setpoint 3 Fixed frequency 4 USS on BOP link 5 USS on COM link (control terminals 29 and 30) 6 CB on COM link (CB = communications module) 10 No main setpoint + MOP setpoint 11 MOP setpoint + MOP setpoint 12 Analog setpoint + MOP setpoint
...
P1000 =...
Issue 10/06
76 77
CB on COM link + Analog setpoint 2 Analog setpoint 2 + Analog setpoint 2 MOP Sequence control ADC FF
P1000 = 12
Additonal setpoint
USS BOP link USS COM link
Setpoint channel P1000 = 12
Motor control
Main setpoint
CB COM link ADC2
P1080 =...
P1082 =...
P1120 =...
P1121 =...
0.00 Hz Min. frequency (enters the minimum motor frequency in Hz) Sets minimum motor frequency at which motor will run irrespective of frequency setpoint. The value set here is valid for both clockwise and anticlockwise rotation. 50.00 Hz Max. frequency (enters the maximum motor frequency in Hz) Sets maximum motor frequency at which motor will run irrespective of the frequency setpoint. The value set here is valid for both clockwise and anticlockwise rotation. 10.00 s Ramp-up time (enters the ramp-up time in s) Time taken for motor to accelerate from standstill up to maximum motor frequency (P1082) when no rounding is used. If a ramp-up time is parameterized which is too low, then this can result in alarm A0501 (current limit value) or the drive inverter being shutdown with fault F0001 (overcurrent). 10.00 s Ramp-down time (enters the deceleration time in s) Time taken for motor to decelerate from maximum motor frequency (P1082) down to standstill when no rounding is used. If the ramp-down time is parameterized too low, then this can result in alarms A0501 (current limit value), A0502 (overvoltage limit value) or the drive inverter being powered-down with fault F0001 (overcurrent) or F0002 (overvoltage).
MICROMASTER 440
86
Operating Instructions 6SE6400-5AW00-0BP0