Page 67

Issue 10/06

3 Functions

3-12). Drive data sets can only be changed-over in the "Ready" state and this takes approx. 50 ms.

Drive running Drive ready t Selection of DDS BI: DDS bit 1 P0821

CO/BO: Act CtrlWd2

3 r0055 .05 r0055 .05

(0:0)

2 BI: DDS bit 0

CO/BO: Act CtrlWd2

1

P0820 r0055 .04 r0055 .04

(0:0)

0 DDS active r0051[1] t Switch-over time aprox. 50 ms

Switch-over time aprox. 50 ms

3 2 1 0

Fig. 3-12 t

Changing-over DDS

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

67

Page 68

3 Functions

3.1.4

Issue 10/06

Reference quantities Parameter range:

P2000 – r2004

Physical quantities are normalized or de-normalized by the frequency inverter when data is output or is being entered. This conversion is undertaken by the particular interface using the reference quantities. The normalization / denormalization is carried-out for the following interfaces: Table 3-5

Normalized interfaces

Interafce

100 %

Analog input Current input Voltage input

20 mA 10 V

Analog output Current output Voltage output

20 mA 10 V

USS

4000 h

CB

4000 h

Further, for a BICO connection, a normalization is carried-out if the connector output (CO) represents a physical quantity and the connector input (CI) a normalized (percentage) quantity (e.g. PID controller). De-normalization is carriedout if the inverse situation exists. This normalization / de-normalization should be carefully taken into consideration, especially for the free function blocks (FFBs). Reference quantities (normalization quantities) are intended to allow setpoint and actual value signals to be represented in a standard fashion (normalization / denormalization of physical quantities such as setpoint and actual frequency). This also applies for permanently set parameters that are entered as a "percentage". A value of 100 % corresponds to a process data value PZD of 4000 h (USS or CB) – or a current / voltage value of 20 mA / 10 V (analog input / output). The following reference parameters and permanently saved reference values are available: Table 3-6

Normalization functions

Parameter

Designation

Value (100 % / 4000 h)

Units

P2000 P2001

Reference frequency

P2000

Hz

Reference voltage

P2001

V

P2002

Reference current

P2002

A

P2003

Reference torque

P2003

Nm r2004

Reference power

π * P2000 * P2003 kW

-

Reference speed

P2000 * 60 / r0313

RPM

-

Reference temperature

100 °C

°C

-

Reference energy

100 kWh kWh

MICROMASTER 440

68

Operating Instructions 6SE6400-5AW00-0BP0

Page 69

Issue 10/06

3 Functions

Example Using the reference frequency P2000 as example, normalization / de-normalization is demonstrated via the serial interface "USS at BOP link". If the connection between two BICO parameters is closed (directly using the BICO parameters or indirectly using P0719 or P1000), that have different representation types (normalized representation (hex) or physical representation (Hz)), then in the frequency inverter, the following normalization is made to the target value: P2016 [0] [1] [2] [3] r0021 x[Hz]

USS-PZD BOP link r0021[Hz] ⋅ 4000[Hex ] P2000[Hz] y[Hex] r2015 [0] [1] [2] [3]

USS-PZD BOP link

P1070 x[Hex]

Fig. 3-13 y[Hex] = y[Hz] = r2015[1] ⋅ P2000 4000[Hex] y[Hz]

Normalization / de-normalization

Note ¾ Analog values are limited to 10 V or 20 mA. A maximum of 100 % referred to the corresponding reference values can be output / entered as long as no DAC/ADC scaling is made (factory setting). ¾ Setpoints and actual value signals via serial interface: ♦ When transferring using the PZD part, they are limited to the value 7FFF h. This is the reason that the maximum value is 200 % referred to the reference value. ♦ When transferring data using the PKW part, they are transferred dependant on the data type and the units. ¾ Parameter P1082 (max. frequency) limits the frequency in the frequency inverter independent of the reference frequency. When changing P1082 (factory setting: 50 Hz), this is the reason that P2000 should always be adapted (factory setting: 50 Hz). If, e.g. for a NEMA motor, the parameter is set to 60 Hz, and no changes are made regarding P2000, then the analog setpoint / actual value is limited to 100 % or a setpoint / actual value signal at 4000 h is limited to 50 Hz!

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

69

Page 70

3 Functions

3.2

Issue 10/06

Operator panels for MICROMASTER MICROMASTER drive units can be optionally equipped with a BOP (Basic Operator Panel) or AOP (Advanced Operator Panel). The AOP distinguishes itself as a result of a plain text display which simplifies operator control, diagnostics as well as also commissioning (start-up).

BOP Fig. 3-14

3.2.1

AOP

Operator panels

Description of the BOP (Basic Operator Panel) The BOP, available as option, allows drive inverter parameters to be accessed. In this case, the Status Display Panel (SDP) must be removed and the BOP either inserted or connected in the door of a cabinet using a special mounting kit (Operator panel door mounting set) (refer to the Attachment A). Parameter values can be changed using the BOP. This allows the MICROMASTER drive unit to be set-up for a particular application. In addition to the keys (refer to Section 3.2.3), it includes a 5-digit LCD display on which the parameter numbers rxxxx and Pxxxx, parameter values, parameter units (e.g. [A], [V], [Hz], [s]), alarm Axxxx or fault messages Fxxxx as well as setpoints and actual values.

NOTE ¾ Contrary to the AOP, for the BOP, parameters do not have to be set or taken into consideration when establishing the communications between the BOP and drive inverter. ¾ A BOP does not have a local memory. This means that it is not possible to save a parameter set on the BOP.

MICROMASTER 440

70

Operating Instructions 6SE6400-5AW00-0BP0

Page 71

Issue 10/06

3.2.2

3 Functions

Description of the AOP (Advanced Operator Panel) An AOP (this is available as option) has the following additional functions with respect to a BOP: ¾ Multi-language and multi-line plain text display ¾ Units are additionally displayed, such as [Nm], [°C], etc. ¾ Active parameters, fault messages, etc. are explained ¾ Diagnostics menu to support troubleshooting ¾ The main menu is directly called by simultaneously pressing keys Fn and P ¾ Timer with 3 switching operations per entry ¾ Up to 10 parameter sets can be downloaded / saved ¾ Communications between an AOP and MICROMASTER are realized using the USS protocol. An AOP can be connected to the BOP link (RS 232) as well as to the COM link interface (RS 485) of the drive inverter. ¾ Multi-point capable coupling to control (open-loop) and visualize up to 31 MICROMASTER drive inverters. The USS bus must, in this case, be configured and parameterized via the drive inverter terminals of the COM link interface. Please refer to Sections 3.2.3, 3.2.4 and the AOP Manual for additional details.

NOTE ¾ Contrary to the BOP, for the AOP, the communications parameters of the particular interface must be taken into account. ¾ When inserting / connecting to the drive inverter, the AOP automatically changes the parameter P2012 (USS-PZD length) to 4 corresponding to the interface. COM link: P2012[0] BOP link: P2012[1] ¾ For DriveMonitor, the default value for the USS-PZD length is set to 2. This results in a conflict if the AOP and the DriveMonitor are operated, alternating, at the same interface. Remedy: Increase the USS-PZD length to 4.

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

71

Page 72

3 Functions

3.2.3

Issue 10/06

Keys and their functions on the operator panel (BOP / AOP)

Operator panel/key

Function Status display

Effects

The LCD indicates the settings which the drive inverter is presently using.

Start motor

The drive inverter is started by pressing the key. This key is de-activated in the default setting. Parameter P0700 or P0719 should be changed as follows to activate the key: BOP: P0700 = 1 or P0719 = 10 ... 16 AOP: P0700 = 4 or P0719 = 40 .... 46 on the BOP link P0700 = 5 or P0719 = 50 .... 56 on the COM link

Stop motor

OFF1 When this key is pressed, the motor comes to a standstill within the selected ramp-down time. It is de-activated in the default setting; to activate → refer to the "Start motor" key. OFF2 The motor coasts down to a standstill by pressing the key twice (or pressing once for a longer period of time). This function is always activated.

Direction reversal

To reverse the direction of rotation of the motor, press this key. The opposing direction is displayed using the minus character (-) or by the flashing decimal point. In the default setting this function is de-activated; to activate it → refer to the "Start motor" key.

Jog motor

In the "Ready to power-on" state, when this key is pressed, the motor starts and rotates with the pre-set jog frequency. The motor stops when the key is released. When the motor is rotating, this key has no effect.

Functions

This key can be used to display additional information. If you press the key during operation, independent of the particular parameter, for two seconds, then the following data is displayed: 1. Voltage of the DC current link (designated by d – units V). 2. Output current (A) 3. Output frequency (Hz) 4. Output voltage (designated by o – units V). 5. The value, selected in P0005 (if P0005 is configured so that one of the above pieces of data is displayed (1 to 4), then the associated value is not re-displayed). The displays mentioned above are run-through one after the other by pressing again. Step function Starting from any parameter (rXXXX or PXXXX), if the key Fn is briefly pressed, then a jump is immediately made to r0000. You can then, when required, change an additional parameter. After returning to r0000, when key Fn is pressed, then the system returns to the starting point. Acknowledgement If alarm and fault messages are present, then these can be acknowledged by pressing key Fn.

+ Fig. 3-15

Parameter access

Parameters can be accessed by pressing this key.

Increase value

When this key is pressed, the displayed value is increased.

Reduce value

When this key is pressed, the displayed value is decreased.

AOP menu

Calls the AOP menu prompting (this is only available for AOP).

Operator panel keys

MICROMASTER 440

72

Operating Instructions 6SE6400-5AW00-0BP0

Page 73

Issue 10/06

3.2.4

3 Functions

Changing parameters using the operator panel The way that parameter P0719 can be changed will now be described; please use this description as a basis when setting all of the other parameters using the BOP.

Changing P0004 – parameter filter function Step 1

Press in order to access the parameter

2

Press until P0004 is displayed

3

Press level in order to reach the parameter value

4

Press or required value

5

Press the value

6

The user can only see the command parameters.

Result on the display in order to obtain the to acknowledge the value and to save

Changing an indexed parameter P0719 – selecting the command/frequency setpoint Step 1

Press in order to access the parameter

2

Press until P0719 is displayed

3

Press in order to reach the parameter value

4

Press value in order to display the currently set

5

Press value or

6

Press the value to acknowledge the value and to save

7

Press until r0000 is displayed

8

Press in order to return to the operating display (the display which the customer has defined)

Fig. 3-16

Result on the display in order to obtain the required

Changing parameters using the BOP

NOTE The BOP sometimes display when changing parameter values. This means that the drive inverter is presently handling another higher-priority task.

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

73

Page 74

3 Functions

3.3

Issue 10/06

Block diagram PE 1/3 AC 200 - 240 V 3 AC 380 - 480 V 3 AC 500 - 600 V

L/L1, N/L2 or L/L1, N/L2,L3 or L1, L2, L3

PE

+10 V

1

0V

2

ADC1+

≥ 4.7 kΩ

3

ADC1-

BOP link

A/D

4

RS232

ADC2+ 10

ADC2-

A/D

150.00 Hz

I

11

External 24 V

0

Fn Jog

P

BOP/AOP

DIN1

DIN1 5

6

6

7

7

8

8

~

DIN3

Opto Isolation

DIN2 DIN3

DIN4

DIN4

DIN5

DIN5 16

= Frame sizes A to F

B+/DC+

R

16

DIN6

B-

DIN6 17

17 9 or NPN 28

DC-

Output +24 V max. 100 mA (isolated) Output 0 V max. 100 mA (isolated)

PNP

28 14

A/D

PTCB

DCNA

Frame sizes FX and GX

PTCA

Motor PTC KTY84

DCPA

CPU

External braking module connection

5

DIN2

15

DCNS DAC1+ 12

0 - 20 mA max. 500 Ω

DAC1-

DCPS

D/A

13

= DAC2+

0 - 20 mA max. 500 Ω

26

Connection for dv/dt filter

+ _ 24 V

SI

3~

D/A DAC2-

27

COM 20

Relay1

19

Not used

NO

50 Hz 1 2 DIP switch (on Control Board)

NC

18

30 V DC / 5 A (resistive) 250 V AC / 2 A (inductive)

COM Relay2

22

ADC ADC 1 2

NO

0 - 20 mA current 0 - 10 V voltage

21

COM 25

Relay3

24

60 Hz

DIP switch (on I/O Board) 1

2

NO NC

23

P+ 29

RS485

COM link

CB Option automatic

N30

PE

U,V,W

M

Fig. 3-17

MICROMASTER 440 – block diagram

MICROMASTER 440

74

Operating Instructions 6SE6400-5AW00-0BP0

Page 75

Issue 10/06

3.4

3 Functions

Factory setting The MICROMASTER drive unit is shipped from the plant with a Status Display Panel (SDP, refer to Fig. 3-18). The SDP has two LEDs on the front panel which display the operating state of the drive inverter (refer to Section 4.1). When MICROMASTER is shipped from the plant with the SDP functioning, it can be operated without any additional parameterization. In this case, the drive inverter default settings (which depend on the drive inverter type / size) match the following data of a 4pole motor: ¾ Rated motor power P0307 ¾ Rated motor voltage P0304 ¾ Rated motor current P0305 ¾ Rated motor frequency P0310

Fig. 3-18

Status Display Panel (SDP)

(We recommend a Siemens standard motor.) Further, the following conditions must be fulfilled: ¾ Control (ON/OFF command) via digital inputs ¾ Setpoint input via analog input 1 ¾ Induction motor ¾ Self-cooled motor ¾ Motor overload factor ¾ Min. frequency ¾ Max. frequency ¾ Ramp-up time ¾ Ramp-down time ¾ Linear V/f characteristic Table 3-7

(refer to Table 3-7) P1000 = 2 P0300 = 1 P0335 = 0 P0640 = 150 % P1080 = 0 Hz P1082 = 50 Hz P1120 = 10 s P1121 = 10 s P1300 = 0

Pre-assignment of the digital inputs

Digital inputs

Terminals

Parameter

Function

Active

Command source

-

P0700 = 2

Terminal strip

Yes

Digital input 1

5

P0701 = 1

ON / OFF1

Yes

Digital input 2

6

P0702 = 12

Reversing

Yes

Digital input 3

7

P0703 = 9

Fault acknowledge

Yes

Digital input 4

8

P0704 = 15

Fixed setpoint (direct)

No

Digital input 5

16

P0705 = 15

Fixed setpoint (direct)

No

Digital input 6

17

P0706 = 15

Fixed setpoint (direct)

No

Digital input 7

Via ADC1

P0707 = 0

Digital input disabled

No

Digital input 8

Via ADC2

P0708 = 0

Digital input disabled

No

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

75

Page 76

3 Functions

Issue 10/06

If the various prerequisites are fulfilled and the appropriate conditions present, then after the motor has been connected and the power connected, then the following is possible with the factory setting: ¾ The motor can be started and stopped (via DIN1 with external switch) ¾ The direction of rotation can be reversed (via DIN2 with external switch) ¾ Faults reset (via DIN3 with external switch) ¾ A frequency setpoint can be entered (via ADC1 with external potentiometer default setting of the ADC: Voltage input) ¾ The frequency actual value can be output (via D/A converter, D/A converter output: current output) The potentiometer and the external switches can be connected through the drive inverter internal power supply, as shown in Fig. 3-19.

Analog output

Pre-assignment of the digital inputs DIN1 to DIN3, refer to Table 3-7.

Fig. 3-19

Recommended wiring for the factory setting

If settings have to be made which go beyond the factory setting, then depending on the complexity of the application, when commissioning the drive system, the particular function description as well as the parameter list including function charts must be carefully taken into consideration.

MICROMASTER 440

76

Operating Instructions 6SE6400-5AW00-0BP0