Page 57

Issue 10/06

3.1.2

3 Functions

Interconnecting signals (BICO technology) A state-of-the-art drive unit must be able to interconnect internal and external signals (setpoint / actual values and control / status signal). This interconnection functionality must have a high degree of flexibility in order to be able to adapt the drive to new applications. Further, a high degree of usability is required, which also fulfills standard applications. This is the reason that within the MICROMASTER series of drive units, BICO technology (→ flexibility) and fast parameterization using parameters P0700 / P1000 (→ usability) or P0719 (→ combination P0700/P1000) have been introduced to be able to fulfill both of these requirements.

3.1.2.1

Selecting the command source P0700 / selecting the setpoint source P1000 The following parameters can be used to quickly interconnect setpoints and control signals: ¾ P0700 "Selection of command source" ¾ P1000 "Selection of setpoint source" These parameters are used to define via which interface the drive inverter receives the setpoint or the power-on/power-off command. The interfaces, listed in Table 3-2 can be selected for the command source P0700. Table 3-2

Parameter P0700

Parameter values

Significance / command source

0

Factory default

1

BOP (operator panel, refer to Section 3.2.1)

2

Terminal strip

4

USS on BOP link

5

USS on COM link

6

CB on COM link

The following internal or external sources / interfaces can be selected for the frequency setpoint source P1000. In addition to the main setpoint (1st position), a supplementary setpoint (2nd position) can be selected (refer to Table 3-3).

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

57

Page 58

3 Functions

Issue 10/06

Table 3-3

Parameter P1000 Significance

Parameter values

Main setpoint source

Supplementary setpoint source

0

No main setpoint

-

1

MOP setpoint (motorized potentiometer)

-

2

Analog setpoint

-

3

Fixed frequency

-

4

USS on BOP link

-

5

USS on COM link

-

6

CB on COM link

-

7

Analog setpoint 2

-

10

No main setpoint

MOP setpoint

11

MOP setpoint

MOP setpoint

12

Analog setpoint

MOP setpoint

..

..

..

..

..

..

..

..

..

77

Analog setpoint 2

Analog setpoint 2

NOTE ¾ Communications between the AOP and MICROMASTER are established using the USS protocol. The AOP can be connected to both the BOP link (RS 232) as well as at the COM link interface (RS 485) of the drive inverter. If the AOP is to be used as command source or setpoint source then for parameter P0700 or P1000, either "USS on BOP link" or "USS on COM link" should be selected. ¾ The complete list of all of the setting possibilities can be taken from the parameter list (refer to parameter list P1000). ¾ Parameters P0700 and P1000 have the following default settings: a) P0700 = 2 (terminal strip) b) P1000 = 2 (analog setpoint) In this case, the selection of the command source is made independently of the selection of the frequency setpoint source. This means that the source to enter the setpoint does not have to match the source to enter the power-on/power-off command (command source). This means, for example, that the setpoint (P1000 = 4) can be connected via an external device which is connected to the BOP link interface via USS and the control (ON/OFF command, etc.) is entered via digital inputs (terminals, P0700 = 2).

CAUTION ¾ When P0700 or P1000 are modified, then the frequency inverter also changes the subordinate BICO parameters (refer to the parameter list for P0700 or P1000 in the appropriate tables) ¾ There is no prioritization (priority assignment) between direct BICO parameterization and P0700/P1000. The last modification is valid.

MICROMASTER 440

58

Operating Instructions 6SE6400-5AW00-0BP0

Page 59

Issue 10/06

3.1.2.2

3 Functions

Selection of command/frequency setpoint P0719 Parameter P0719 represents a combination of the functionalities of the two parameters P0700 and P1000. Here, it is possible to changeover the command source as well as also the frequency setpoint source via a parameter change. Contrary to P0700 and P1000, for parameter P0719, the subordinate (lower-level) BICO parameters are not changed. This characteristic/feature is especially used by PC tools in order to briefly retrieve the control authority for the drive without having to change the existing BICO parameterization. Parameter P0719 "Selection of command/frequency setpoint" comprises the command source (Cmd) and the frequency setpoint (setpoint). Table 3-4

Parameter P0719 Significance

Parameter values

Command source

Setpoint source (frequency source)

0

Cmd=BICO parameter

Setpoint = BICO parameter

1

Cmd=BICO parameter

Setpoint = MOP setpoint

2

Cmd=BICO parameter

Setpoint = Analog

3

Cmd=BICO parameter

Setpoint = Fixed frequency

4

Cmd=BICO parameter

Setpoint = USS BOP link

5

Cmd=BICO parameter

Setpoint = USS COM link

6

Cmd=BICO parameter

Setpoint = CB COM link

10

Cmd=BOP

Setpoint = BICO Param

11

Cmd=BOP

Setpoint = MOP setpoint

12

Cmd=BOP

Setpoint = Analog

..

..

..

..

..

..

64

Cmd=CB COM link

Setpoint = USS BOP link

66

Cmd=CB COM link

Setpoint = USS COM link

NOTE ¾ The complete list of all of the possible settings can be taken from the parameter list (refer to the parameter list, P0719). ¾ Contrary to parameter P0700 and P1000, subordinate BICO parameters are not changed for parameter P0719. This characteristic/feature can be used during service if the control authority must be briefly and quickly re-assigned (e.g. selecting and executing the motor data identification routine using a PC-based tool).

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

59

Page 60

3 Functions

3.1.2.3

Issue 10/06

BICO technology Using BICO technology (English: Binector Connector Technology), process data can be freely interconnected using the "standard" drive parameterization. In this case, all values which can be freely interconnected (e.g. frequency setpoint, frequency actual value, current actual value, etc.) can be defined as "Connectors" and all digital signals which can be freely interconnected (e.g. status of a digital input, ON/OFF, message function when a limit is violated etc.) can be defined as "Binectors". There are many input and output quantities as well as quantities within the closedloop control which can be interconnected in a drive unit. It is possible to adapt the drive to the various requirements using BICO technology. A binector is a digital (binary) signal without any units and which can either have the value 0 or 1. Binectors always refer to functions whereby they are sub-divided into binector inputs and binector outputs (refer to Fig. 3-4). In this case, the binector input is always designated using a "P" parameter with attribute "BI" (e.g.: P0731 BI: Function, digital output 1), while the binector output is always represented using an "r" parameter with attribute "BO" (e.g.: r0751 BO: ADC status word). As can be seen from the examples above, the binector parameters have the following abbreviations in front of the parameter names: ¾ BI Binector Input, signal receiver ("P" parameters) → The BI parameter can be interconnected with a binector output as source, by entering the parameter number of the binector output (BO parameter) as value in the BI parameter (e.g.: Interconnecting the "BO" parameter r0751 with "BI" parameter P0731 → P0731 = 751). ¾ BO Binector Output, signal source ("r" parameters) → The BO parameter can be used as source for BI parameters. For the particular interconnection the BO parameter number must be entered into the BI parameter (e.g.: Interconnecting the "BO" parameter r0751 with "BI" parameter P0731 → P0731 = 751). Abbreviation and symbol

Name

BI

Binector input (signal receiver)

Function Data flow Pxxxx Function BI: ...

Binector output (signal source)

BO

Data flow rxxxx Function BO: ...

Fig. 3-4

Binectors

A connector is a value (16 or 32 bit), which can include a normalized quantity (without dimension) as well as also a quantity with associated units. Connectors always refer to functions whereby they are sub-divided into connector inputs and connector outputs (refer to Fig. 3-5). Essentially the same as the binectors, the connector inputs are characterized by a "P" parameter with attribute "CI" (e.g.: P0771 CI: D/A converter); while the connector outputs are always represented using an "r" parameter with attribute "CO" (e.g.: r0021 CO: Smoothed output frequency).

MICROMASTER 440

60

Operating Instructions 6SE6400-5AW00-0BP0

Page 61

Issue 10/06

3 Functions

As can be seen from the examples above, connector parameters have the following abbreviations in front of the parameter names: ¾ CI Connector Input, signal sink ("P" parameters) → The CI parameter can be interconnected with a connector output as source, by entering the parameter number of the connector output (CO parameter) as value in the CI parameter (e.g.: P0771 = 21). ¾ CO Connector Output, signal source ("r" parameters) → The CO parameter can be used as source for CI parameters. For the particular interconnection, the CO parameter number must be entered in the CI parameter (e.g.: P0771 = 21). Further, MICROMASTER has "r" parameters where several binector outputs are combined in a word (e.g.: r0052 CO/BO: Status word 1). This feature reduces, on one hand, the number of parameters and simplifies parameterization via the serial interface (data transfer). This parameter is further characterized by the fact that it does not have any units and each bit represents a digital (binary) signal. As can be seen from the examples of parameters, these combined parameters have the following abbreviation in front of the parameter names: ¾ CO/BO Connector Output / Binector Output, signal source ("r" parameters) → CO/BO parameters can be used as source for CI parameters and BI parameters: a) In order to interconnect all of the CO/BO parameters, the parameter number must be entered into the appropriate CI parameter (e.g.: P2016[0] = 52). b) When interconnecting a single digital signal, in addition to the CO/BO parameter number, the bit number must also be entered into the BI parameter (e.g.: P0731 = 52.3) Abbreviation and symbol

Name

CI

Connector input (signal receiver)

Function Data flow Pxxxx Function CI: ...

Connector output (signal source)

CO

Data flow rxxxx Function CO: ...

Binector/connector output (signal source)

CO BO

Data flow rxxxx Functions CO/BO: ...

Fig. 3-5

Connectors

In order to interconnect two signals, a BICO setting parameter (signal receiver) must be assigned the required BICO monitoring parameter (signal source). A typical BICO interconnection is shown using the following examples (refer to Fig. 3-6).

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

61

Page 62

3 Functions

Issue 10/06

Connector output (CO)

===>

Connector input (CI) CI: Main setpoint P1070

Function CO: Act. ADC after scal. [4000h] r0755

FB

Function (755)

P1070 = 755

Binector output (BO)

===>

Binector input (BI) BI: ON/OFF1

FB

Function

P0840 P0840 (751:0) (751:0)

BO: Status word of ADC r0751

FB

Function

P0840 = 751.0

CI: PZD to CB

Connector output / Binector output (CO/BO)

P2051 = 52

P2051

FB

Function (52)

CO/BO: Act. status word 1

FB

Function r0052 r0052 BI: Function of digital output 1 P0731 P0731 Function (52:3)

FB

P0731 = 52.3 Fig. 3-6

BICO connections (examples)

NOTE BICO parameters with the CO, BO or CO/BO attributes can be used a multiple number of times.

MICROMASTER 440

62

Operating Instructions 6SE6400-5AW00-0BP0

Page 63

Issue 10/06

3.1.3

3 Functions

Data sets For many applications it is advantageous if several parameters can be simultaneously changed, during operation or in the ready state, using an external signal.

Examples: ¾ The drive inverter should be switched-over from motor 1 to motor 2. Motor 1

M2

Motor 2

K1

M1

K2

MM4

Fig. 3-7

Example: Changeover from motor 1 to motor 2

¾ The control source (e.g. terminal → BOP) or setpoint (frequency) source (e.g. ADC → MOP) should be changed-over using a terminal signal (e.g. DIN4) as function of an external event (e.g. the higher-level control unit fails). A typical example in this case is a mixer, which may not come to an uncontrolled stop when the control fails. Control source: Setpoint (frequency source):

Terminal → BOP ADC → MOP

P0810 = 722.3 DIN4 Terminals BOP ADC MOP

Fig. 3-8

P0700[0] = 2

0

P0700[1] = 1

1

P1000[0] = 2

0

P1000[1] = 1

1

Sequence control

Setpoint channel

Motor control

Example: Changing-over between the control and setpoint (frequency) source

This functionality can be elegantly implemented using indexed parameters (refer to Section 3.1.1). In this case, as far as the functionality is concerned, the parameters are combined to form groups / data sets and are indexed. By using indexing, several different settings can be saved for each parameter which can be activated by changing-over the data set (i.e. toggling between data sets). The following data sets apply: CDS Command Data Set DDS Drive Data Set

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

63

Page 64

3 Functions

Issue 10/06

3 independent settings are possible for each data set. These settings can be made using the index of the particular parameter: CDS1 ... CDS3 DDS1 ... DDS3 Those parameters (connector and binector inputs) which are used to control the drive and enter a setpoint, are assigned to the command data set (CDS). The signal sources for the control commands and setpoints are interconnected using BICO technology (refer to Section 3.1.2.3). In this case, the connector and binector inputs are assigned as signal sources corresponding to the connector and binector outputs. A command data set includes: ¾ Command sources and binector inputs for control commands (digital signals) e.g.: ♦ Selects the command source ♦ ON/OFF1 ♦ OFF2 ♦ Enable JOG right ♦ Enable JOG left

P0700 P0840 P0844 P1055 P1056

¾ Setpoint sources and connector inputs for setpoints (analog signals) e.g.: ♦ Selection of frequency setpoint ♦ Selection of main setpoint ♦ Selection of additional setpoint

P1000 P1070 P1075

The parameters, combined in a command data set, are designated with [x] in the parameter list in the index field. Index: Pxxxx[0] : 1st command data set (CDS) Pxxxx[1] : 2nd command data set (CDS) Pxxxx[2] : 3rd command data set (CDS)

NOTE A complete list of all of the CDS parameters can be taken from the parameter list. It is possible to parameterize up to three command data sets. This makes it easier to toggle between various pre-configured signal sources by selecting the appropriate command data set. A frequent application involves, for example, the ability to toggle between automatic and manual operation. MICROMASTER has an integrated copy function which is used to transfer command data sets. This can be used to copy CDS parameters corresponding to the particular application. The copy operation is controlled with P0809 as follows (refer to Fig. 3-9): 1. P0809[0] = Number of the command data set which is to be copied (source) 2. P0809[1] = Number of the command data set into which data is to be copied (target) 3. P0809[2] = 1 →

Copying is started Copying has been completed, if P0809[2] = 0.

MICROMASTER 440

64

Operating Instructions 6SE6400-5AW00-0BP0

Page 65

Issue 10/06

3 Functions

P0809[0] = 0 P0809[1] = 2 P0809[2] = 1

1. CDS 3. CDS Start copy

P0700 P0701 P0702 P0703 P0704

.. .. .

[0]

[1]

[2]

.. .. .

.. .. .

.. .. .

P2253 P2254 P2264 1. CDS

Fig. 3-9

2. CDS 3. CDS

Copying from CDS

The command data sets are changed-over using the BICO parameter P0810 and P0811, whereby the active command data set is displayed in parameter r0050 (refer to Fig. 3-10). Changeover is possible both in the "Read" as well as in the "Run" states. Selection of CDS BI: CDS bit 1 P0811

CO/BO: Act CtrlWd2

3 r0055 .15 r0055 .15

(0:0)

2 BI: CDS b0 loc/rem

CO/BO: Act CtrlWd1

1

P0810 r0054 .15 r0054 .15

(0:0)

0 CDS active r0050 t Switch-over time aprox. 4 ms

Switch-over time aprox. 4 ms

3 2 1 0

Fig. 3-10 t

Changing-over CDS

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

65

Page 66

3 Functions

Issue 10/06

The drive data set (DDS) contains various setting parameters which are of significance for the open-loop and closed-loop control of a drive: ¾ Motor and encoder data, e.g.: ♦ Select motor type P0300 ♦ Rated motor voltage P0304 ♦ Main inductance P0360 ♦ Select encoder type P0400 ¾ Various closed-loop control parameters, e.g.: ♦ Fixed frequency 1 P1001 ♦ Min. frequency P1080 ♦ Ramp-up time P1120 ♦ Control mode P1300 The parameters, combined in a drive data set, are designated with an [x] in the parameter list in the index field: Pxxxx[0] : 1st drive data set (DDS) Pxxxx[1] : 2nd drive data set (DDS) Pxxxx[2] : 3rd drive data set (DDS)

NOTE A complete list of all of the DDS parameters can be taken from the parameter list. It is possible to parameterize several drive data sets. This makes it easier to toggle between various drive configurations (control mode, control data, motors) by selecting the appropriate drive data set. Just like the command data sets, it is possible to copy drive data sets within the MICROMASTER. P0819 is used to control the copy operation as follows: 1. P0819[0] = Number of the drive data set which is to be copied (source) 2. P0819[1] = Number of the drive data set into which data is to be copied (target) 3. P0819[2] = 1 →

Copying is started Copying has been completed, if P0819[2] = 0.

P0819[0] = 0 P0819[1] = 2 P0819[2] = 1

1. DDS 3. DDS Start copy

P0005 P0291 P0300 P0304 P0305

.. .. .

[0]

[1]

[2]

.. .. .

.. .. .

.. .. .

P2484 P2487 P2488 1. DDS

Fig. 3-11

2. DDS 3. DDS

Copying from DDS

Drive data sets are changed-over using the BICO parameter P0820 and P0821 whereby the active drive data set is displayed in parameter r0051 (refer to Fig.

MICROMASTER 440

66

Operating Instructions 6SE6400-5AW00-0BP0