Page 47
Issue 10/06
3
3 Functions
Functions
This Section includes the following: ¾ Explanation of the MICROMASTER 440 parameters ¾ An overview of the parameter structure of MICROMASTER 440 ¾ A description of the display and operator control elements and communications ¾ A block diagram of MICROMASTER 440 ¾ An overview of the various ways of commissioning the MICROMASTER 440 ¾ A description of the inputs and outputs ¾ Possibilities of controlling (open-loop and closed-loop) the MICROMASTER 440 ¾ A description of the various functions of the MICROMASTER 440 and their implementation ¾ Explanation and information on the protective functions 3.1 3.1.1 3.1.2 3.1.2.1 3.1.2.2 3.1.2.3 3.1.3 3.1.4
Parameters ............................................................................................................. 51 Setting / monitoring parameters and parameter attributes ..................................... 51 Interconnecting signals (BICO technology) ............................................................ 57 Selecting the command source P0700 / selecting the setpoint source P1000....... 57 Selection of command/frequency setpoint P0719 .................................................. 59 BICO technology..................................................................................................... 60 Data sets................................................................................................................. 63 Reference quantities ............................................................................................... 68
3.2 3.2.1 3.2.2 3.2.3 3.2.4
Operator panels for MICROMASTER..................................................................... 70 Description of the BOP (Basic Operator Panel) ..................................................... 70 Description of the AOP (Advanced Operator Panel) .............................................. 71 Keys and their functions on the operator panel (BOP / AOP) ................................ 72 Changing parameters using the operator panel ..................................................... 73
3.3
Block diagram ......................................................................................................... 74
3.4
Factory setting ........................................................................................................ 75
3.5 3.5.1 3.5.2 3.5.3 3.5.4 3.5.5 3.5.6 3.5.7 3.5.7.1 3.5.7.2 3.5.7.3 3.5.7.4 3.5.7.5 3.5.7.6
Commissioning ....................................................................................................... 77 50/60 Hz setting ...................................................................................................... 79 Motor circuit ............................................................................................................ 80 Quick commissioning .............................................................................................. 83 Calculating the motor / control data ........................................................................ 88 Motor data identification.......................................................................................... 91 Magnetizing current ................................................................................................ 95 Commissioning the application ............................................................................... 97 Serial Interface (USS) ............................................................................................. 97 Selection of command source ................................................................................ 98 Digital input (DIN).................................................................................................... 98 Digital output (DOUT) ............................................................................................. 99 Selection of frequency setpoint............................................................................. 100 Analog input (ADC) ............................................................................................... 101
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
47
Page 48
3 Functions
Issue 10/06
3.5.7.7 3.5.7.8 3.5.7.9 3.5.7.10 3.5.7.11 3.5.7.12 3.5.7.13 3.5.7.14 3.5.7.15 3.5.7.16 3.5.7.17 3.5.7.18 3.5.7.19 3.5.7.20 3.5.7.21 3.5.8 3.5.9
Analog output (DAC)............................................................................................. 102 Motor potentiometer (MOP) .................................................................................. 103 Fixed frequency (FF)............................................................................................. 104 JOG....................................................................................................................... 105 Ramp function generator (RFG) ........................................................................... 106 Reference/limit frequencies .................................................................................. 107 Inverter protection ................................................................................................. 108 Motor protection .................................................................................................... 108 Encoder................................................................................................................. 110 V/f control.............................................................................................................. 111 Field-orientated control ......................................................................................... 113 Converter-specific Functions ................................................................................ 118 Command and drive data set................................................................................ 127 Diagnostic parameters.......................................................................................... 130 End of commissioning........................................................................................... 131 Series commissioning ........................................................................................... 132 Parameter reset to the factory setting................................................................... 133
3.6 3.6.1 3.6.2 3.6.3 3.6.4
Inputs / outputs ..................................................................................................... 135 Digital inputs (DIN)................................................................................................ 135 Digital outputs (DOUT) ......................................................................................... 138 Analog inputs (ADC) ............................................................................................. 140 Analog outputs (D/A converter) ............................................................................ 142
3.7 3.7.1 3.7.1.1 3.7.1.2 3.7.1.3
Communications ................................................................................................... 144 Universal serial interface (USS)............................................................................ 146 Protocol specification and bus structure ............................................................... 148 The structure of net data....................................................................................... 155 USS bus configuration via COM link (RS485) ...................................................... 164
3.8
Fixed frequencies (FF).......................................................................................... 167
3.9
Motorized potentiometer (MOP) ........................................................................... 170
3.10
JOG....................................................................................................................... 172
3.11 3.11.1 3.11.1.1 3.11.1.2 3.11.1.3
PID controller (technological controller)................................................................ 173 Closed-loop PID control ........................................................................................ 175 PID motorized potentiometer (PID-MOP) ............................................................. 177 PID fixed setpoint (PID-FF)................................................................................... 178 PID dancer roll control .......................................................................................... 179
3.12 3.12.1 3.12.2 3.12.3 3.12.4
Setpoint channel ................................................................................................... 181 Summation and modification of the frequency setpoint (AFM)............................. 181 Ramp-function generator (RFG) ........................................................................... 183 OFF/braking functions .......................................................................................... 186 Manual / automatic operation ............................................................................... 189
3.13
Free function blocks (FFB) ................................................................................... 191
3.14
Motor holding brake (MHB)................................................................................... 196
3.15 3.15.1 3.15.2 3.15.3
Electronic brakes .................................................................................................. 202 DC braking ............................................................................................................ 202 Compound braking................................................................................................ 205 Dynamic braking ................................................................................................... 206
3.16
Automatic restart................................................................................................... 211
3.17
Flying restart ......................................................................................................... 213
MICROMASTER 440
48
Operating Instructions 6SE6400-5AW00-0BP0
Page 49
Issue 10/06
3 Functions
3.18 3.18.1 3.18.2
Closed-loop Vdc control........................................................................................ 215 Vdc_max controller ............................................................................................... 215 Kinetic buffering (Vdc_min controller)................................................................... 218
3.19
Positioning down ramp ......................................................................................... 219
3.20 3.20.1 3.20.2
Monitoring functions / messages .......................................................................... 221 General monitoring functions / messages ............................................................ 221 Load torque monitoring......................................................................................... 223
3.21 3.21.1 3.21.2
Thermal motor protection and overload responses .............................................. 227 Thermal motor model............................................................................................ 229 Temperature sensor.............................................................................................. 230
3.22 3.22.1 3.22.2
Power module protection ...................................................................................... 232 General overload monitoring ................................................................................ 232 Thermal monitoring functions and overload responses........................................ 233
3.23 3.23.1 3.23.1.1 3.23.1.2 3.23.1.3 3.23.1.4 3.23.1.5 3.23.2 3.23.2.1 3.23.2.2 3.23.2.3 3.23.2.4 3.23.2.5
Open-loop/closed-loop control technique ............................................................. 235 V/f control.............................................................................................................. 235 Voltage boost ........................................................................................................ 237 Slip compensation................................................................................................. 239 V/f resonance damping......................................................................................... 240 V/f open-loop control with flux current control (FCC)............................................ 241 Current limiting (Imax controller)........................................................................... 242 Vector control........................................................................................................ 243 Vector control without speed encoder (SLVC) ..................................................... 245 Vector control with speed encoder (VC) ............................................................... 247 Speed controller.................................................................................................... 248 Closed-loop torque control.................................................................................... 253 Limiting the torque setpoint................................................................................... 254
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
49
Page 50
3 Functions
Issue 10/06
WARNING ¾ MICROMASTER drive inverters operate with high voltages. ¾ When electrical equipment is operated, then specific parts of this equipment are at hazardous voltage levels. ¾ The following terminals can carry dangerous voltages even if the inverter is inoperative: ♦ the power supply L/L1, N/L2, L3 resp. U1/L1, V1/L2, W1/L3 ♦ the motor terminals U, V, W resp. U2, V2, W2 ♦ and depending on the frame size the terminals DC+/B+, DC-, B-, DC/R+ resp. DCPS, DCNS, DCPA, DCNA ¾ Emergency switching-off devices in compliance with EN 60204 IEC 204 (VDE 0113) must remain functional in all operating modes of the control device. When the Emergency switching-off device is reset, then it is not permissible that the equipment runs-up again in an uncontrolled or undefined way. ¾ In cases and situations where short-circuits in the control device can result in significant material damage or even severe bodily injury (i.e. potentially hazardous short-circuits), then additional external measures or devices/equipment must be provided in order to ensure or force operation without any potential hazards, even if a short-circuit occurs (e.g. independent limit switches, mechanical interlocks etc.). ¾ Certain parameter settings can mean that the drive inverter automatically restarts after the power supply voltage fails and then returns. ¾ The motor parameters must be precisely configured in order to ensure perfect motor overload protection. ¾ The drive inverter provides internal motor overload protection according to 2 UL508C, Section 42. I t monitoring is enabled in the default setting (refer to P0610 and P0335). The motor overload protection can also be guaranteed using an external PTC or KTY84. ¾ This equipment is suitable for use in a circuit capable of delivering not more than 10,000 (Frame Sizes A to C) or 42,000 (Frame Sizes D to GX) symmetrical amperes (rms), for a maximum voltage of 230 V / 460 V / 575 V when protected by an H, J or K type fuse, a circuit breaker or self-protected combination motor controller (for more details see Appendix F). ¾ The drive unit may not be used as 'Emergency switching-off device' (refer to EN 60204, 9.2.5.4). CAUTION Only qualified personnel may commission (start-up) the equipment. Safety measures and warnings must be always extremely carefully observed and fulfilled.
MICROMASTER 440
50
Operating Instructions 6SE6400-5AW00-0BP0
Page 51
Issue 10/06
3 Functions
3.1
Parameters
3.1.1
Setting / monitoring parameters and parameter attributes The drive inverter is adapted to the particular application using the appropriate parameters. This means that each parameter is identified by a parameter number , parameter text and specific attributes (e.g. readable, can be written into, BICO attribute, group attribute etc.). Within any one particular drive system, the parameter number is unique. On the other hand, an attribute can be assigned a multiple number of times so that several parameters can have the same attribute. For MICROMASTER, parameters can be accessed using the following operator units: ¾ BOP (option) ¾ AOP (option) ¾ PC-based commissioning (start-up) tool "Drive Monitor" or "STARTER". These PC-based tools are supplied on the CD-ROM. The parameter types are the main differentiating feature of the parameters. Parameter Read (r....)
"normal" Read parameters
Fig. 3-1
BICO output
Write/Read (P....)
"normal" Write-/Read parameters
BICO input
Parameter types
Setting parameters Parameters which can be written into and read – "P" parameters These are activated/de-activated in the individual functions or parameters directly influence the behavior of a function. The value of this parameter is saved in a nonvolatile memory (EEPROM) as long as the appropriate option was selected (nonvolatile data save). Otherwise, these values are saved in the non-volatile memory (RAM) of the processor, which are lost after power failure or power-off/power-on operations. Notation: P0927 setting parameter 927 P0748.1 setting parameter 748, bit 01 P0719[1] setting parameter 719 index 1 P0013[0...19] setting parameter 13 with 20 indices (indices 0 to 19) Abbreviated notation P0013[20] setting parameter 13 with 20 indices (indices 0 to 19)
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
51
Page 52
3 Functions
Issue 10/06
Monitoring parameters These can only be read – "r" parameters These parameters are used to display internal quantities, for example states and actual values. These parameters are absolutely necessary, especially for diagnostics. Notation: r0002 r0052.3 monitoring parameter 2 monitoring parameter 52, bit 03 r0947[2] monitoring parameter 947 index 2 r0964[0...4] monitoring parameter 964 with 5 indices (indices 0 to 4) Abbreviated notation r0964[5] monitoring parameter 964 with 5 indices (indices 0 to 4) NOTE ¾ A parameter (e.g. P0013[20]) with x consecutive elements (in this case: 20) is defined using an index. x is defined by the numerical index value. When transferred to a parameter this means that an indexed parameter can assume several values. The values are addressed via the parameter number including the index value (e.g. P0013[0], P0013[1], P0013[2], P0013[3], P0013[4], ...). Index parameters, for example, are used for: ƒ ƒ ƒ
P0013[0] P0013[1] P0013[2] .. . P0013[18] P0013[19]
Drive data sets Command data sets Sub-functions
In addition to the parameter number and parameter text, every setting and monitoring parameter has different attributes which are used to individually define the properties/characteristics of the parameter. The attributes are listed in the following Table which are used for MICROMASTER. Table 3-1 Attribute group
Parameter attributes Attribute
Data types
Description The data type of a parameter defines the maximum possible value range. 3 data types are used for MICROMASTER. They either represent an unsigned integer value (U16, U32) or a floating-point value (float). The value range is frequently restricted by a minimum, maximum value (min, max) or using drive inverter/motor quantities.
U16
Unsigned, integer value with a size of 16 bits, max. value range: 0 .... 65535
U32
Unsigned, integer value with a size of 32 bits max. value range: 0 .... 4294967295
Float
A simple precise floating point value according to the IEEE standard format +38 +38 max. value range: -3.39e – +3.39e
MICROMASTER 440
52
Operating Instructions 6SE6400-5AW00-0BP0
Page 53
Issue 10/06
Attribute group
3 Functions
Attribute
Description The value range, which is specified as a result of the data type, is restricted/limited by the minimum, maximum value (min, max) and using drive inverter/motor quantities. Straightforward commissioning (start-up) is guaranteed in so much that the parameters have a default value. These values (min, def, max) are permanently saved in the drive inverter and cannot be changed by the user.
Value range
Min Def Max Unit
No value entered (e.g.: "r parameter") Minimum value Default value Maximum value For MICROMASTER, the units of a particular parameter involve the physical quantity (e.g. m, s, A). Quantities are measurable properties/characteristics of physical objects, operations, states and are represented using characters of a formula (e.g. V = 9 V).
% A V
No dimension Percentage Ampere Volt
Ohm us ms s Hz kHz
Ohm Microseconds Milliseconds Seconds Hertz Kilohertz
1/min m/s Nm W kW Hp kWh
Revolutions per minute [RPM] Meters per second Newton meter Watt Kilowatt Horse power Kilowatt hours
°C m kg °
Degrees Celsius Meter Kilograms Degrees (angular degrees)
Access level
The access level is controlled using parameter P0003. In this case, only those parameters are visible at the BOP or AOP, where the access level is less than or equal to the value assigned in parameter P0003. On the other hand, for DriveMonitor and STARTER, only access levels 0 and 4 are relevant. For example, parameters with access level 4 cannot be changed if the appropriate access level has not been set. The following access levels are implemented in the family of MICROMASTER drive units: 0 1
User-defined parameter list (refer to P0013) Standard access to the most frequently used parameters
2 3 4
Extended access, e.g. to drive inverter I/O functions Expert access only for experienced users Service access only for authorized service/maintenance personnel – with password protection. As far as the ability to visualize the parameters is concerned, the group assignment of the individual parameters must be taken into account. Parameter P0004 is used for the control (refer to the Grouping).
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
53
Page 54
3 Functions
Attribute group
Issue 10/06
Attribute
Description The parameters are sub-divided into groups according to their functionality. This increases the transparency and allows a parameter to be quickly searched for. Furthermore, parameter P0004 can be used to control the ability to be visualized for the BOP / AOP. Main parameter area:
Grouping
ALWAYS INVERTER MOTOR
0 2 3
ENCODER
4
TECH_APL COMMANDS
5 7 all parameters drive inverter parameters motor parameters 0600 .... 0699 speed encoder
0200 .... 0299 0300 .... 0399 and 0400 .... 0499 0500 .... 0599 0700 .... 0749 and
TERMINAL SETPOINT FUNC technical applications / units control commands, digital I/O 0800 .... 0899 8 Analog inputs/outputs 10 Setpoint channel and ramp-function gen. 12 Drive inverter functions
CONTROL COMM ALARMS TECH
13 Motor open-loop/closed-loop control 20 Communications 21 Faults, warnings, monitoring functions" 22 Technological controller (PID controller)
1300 .... 1799 2000 .... 2099 2100 .... 2199 2200 .... 2399
BICO
0750 .... 0799 1000 .... 1199 1200 .... 1299
Description for Binector Input (BI), Binector Output (BO), Connector Input (CI), Connector Output (CO) and Connector Output / Binector Output (CO/BO), refer to Section 3.1.2.3 BI BO CI CO CO/BO
Data sets
Binector Input Binector Output Connector Input Connector Output Connector Output / Binector Output Description for the command data set (CDS) and drive data set (DDS) refer to Section 3.1.3
CDS DDS Change state
Command data set Drive data set "P" parameters can only be changed depending on the drive state. The parameter value is not accepted if the instantaneous state is not listed in the parameter attribute "Change state". For instance, the commissioning (start-up) parameter P0010 with the attribute "CT" can only be changed in quick start-up "C" or ready "T" but not in run "U".
C U T QC.
Quick commissioning (start-up) Operation (run) Ready This parameter attribute identifies as to whether the parameter is included in the quick commissioning (start-up) (P0010 = 1).
No
The parameter is not included in the quick commissioning (start-up)
Yes
The parameter is included in the quick commissioning (start-up)
Active
This attribute is only of importance in conjunction with a BOP. The "Immediate" attribute indicates that this value is already accepted when scrolling (when changing or ). Especially parameters which are used for optimization the value with functions have this property (e.g. constant voltage boost P1310 or filter time constants). On the other hand, for parameters with the attribute "After actuation", the . These include, for example, value is only accepted after first actuating the key parameters where the parameter value can have different settings/meanings (e.g. selecting the frequency setpoint source P1000). Immediately
The value becomes valid by either scrolling with
After actuation
The value is only accepted by pressing or
MICROMASTER 440
54
Operating Instructions 6SE6400-5AW00-0BP0
Page 55
Issue 10/06
3 Functions
The attributes and groups are shown, in the parameter list, in the header line of the parameter. This is shown as an example in Fig. 3-2 using parameter P0305. Index BICO (if available)
P0305[3]
Rated motor current CStat: C P-Group: MOTOR Group CStat
Fig. 3-2
Access level
Datatype: Float Active: first confirm Active Datatypes
Unit A QuickComm. Yes QuickComm. Unit
Min: 0.01 Def: 3.25 10000.0 Max: 0
Level:
1
Value range
Header line for parameter P0305
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
55
Page 56
3 Functions
Issue 10/06
The interrelationship between access level P0003 and the grouping P0004 is schematically shown in Fig. 3-3.
User access level P0003 = 1 Standard 2 Extended 3 Expert 4 Service
P0004 = 2 Inverter Unit P0004 = 2, P0003 = 1 Parameters level 1 concerning the inverter unit P0004 = 2, P0003 = 2
P0004 = 0 (no filter function) allows direct access to the parameters. For BOP and AOP depending on the selected access level
Parameters level 1 and 2 concerning the inverter unit
P0004 = 2, P0003 = 3 Parameters level 1, 2 and 3 concerning the inverter unit
P0004 = 2, P0003 = 4 Parameters level 1, 2, 3 and 4 concerning the inverter unit
P0004 = 22 PID Controller
P0004 = 21
P0004 = 2 Inverter Unit P0200 ... P0299
P0004 = 3
P0003 = 1
Alarms, Warnings & Monitoring
Motor Data P0300 ... P0399 P0600 ... P0699
P0003 = 2 P0003 = 3
P0004 = 20 Communication P2000 ... P2099
P0004 = 4 Speed sensor P0400 ... P0499
P0003 = 4
P0004 = 5 P0004 = 13
Technology Application / units P0400 ... P0499
Motor Control P1300 ... P1799
P0004 = 7
P0004 = 12 Drive Features P1200 ... P1299
P0004 = 10 Setpoint Channel & Ramp Generator P1000 ... P1199
Fig. 3-3
P0004 = 8 Analogue I/O P0750 ... P0799
Commands and Digital I/O P0700 ... P0749 P0800 ... P0899
Parameter grouping / access
MICROMASTER 440
56
Operating Instructions 6SE6400-5AW00-0BP0