The text of a manual · part 7 of 35
MICROMASTER 440 0.12 kW - 250 kW Operating Instructions: 2 Installation, pages 39 to 46
Pages 39 to 46 of 312, from MICROMASTER 440 0.12 kW - 250 kW Operating Instructions
The original document is the PDF (8.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Siemens 6SE6440-2UD13-7AA1
Page 39
Issue 10/06
2 Installation
Hoisting eyes
Shield connection Mains cable PE Cable opening for mains conection U1/L1, V1/L2, W1/L3 Cable opening DCPA, DCNA for connection of an external braking unit
Mains cable Phase U1/L1, V1/L2, W1/L3 Connection to Y-Capacitor Connection DCPA, DCNA for external braking unit Top adjustment rail Top retaining screw Connection for dv/dt filter DCPS, DCNS Status Display Panel Elektronic box
Bottom adjustment rail Bottom retaining screw Fan screws
Fan Shield connection control leads Fan fuses
Transformer adaption Motor cable Phase U2, V2, W2 Motor cable PE Shield connection
Fig. 2-10
MICROMASTER 440 connection drawing - frame size GX
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
39
Page 40
2 Installation
Issue 10/06
Frame Sizes A to F L3 L2 L1 N
Single Phase Contactor
Optional line choke
Optional Filter
MICROMASTER 1)
Motor
Fuse L/L1
U V
N/L2 W PE PE
PE
Three Phase
L3 L2 L1
Contactor
Optional line choke
Optional Filter
MICROMASTER 1)
Motor
Fuse L3
U
L2
V
L1
W PE
PE
PE
Optional Filter
Optional line choke
1) with and without filter
Frame Sizes FX and GX L3 L2 L1 Contactor
MICROMASTER
2)
Motor
Fuse L3
U
L2
V
L1
W PE
PE
3)
2) without filter 3) the commutation choke is to be earthed using the designated earthing point Fig. 2-11
Motor and Power Connections
MICROMASTER 440
40
Operating Instructions 6SE6400-5AW00-0BP0
Page 41
Issue 10/06
2 Installation
Adaptation of fan voltage (only for frame size FX and GX) A transformer is installed to adapt the existing line voltage to the fan voltage. It may be necessary to reconnect the transformer terminals on the primary side to coincide with the existing line power.
0V 1L380V
1L400V 1L440V
1L480V
-
Connect according input voltage
Fig. 2-12
Adaptation of fan voltage
CAUTION If the terminals are not reconnected to the actually present line voltage, the fan fuses can blow.
Replacement for fan fuses Frame size
Fuses (2 each)
Recommended fuses
FX (90 kW CT)
1 A / 600 V / slow-acting
Cooper-Bussmann FNQ-R-1, 600 V or comparable fuse
FX (110 kW CT)
2,5 A / 600 V / slow-acting
Ferraz Gould Shawmut ATDR2-1/2, 600 V or comparable fuse
GX (132-200 kW CT)
4 A / 600 V / slow-acting
Ferraz Gould Shawmut ATDR4, 600 V or comparable fuse
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
41
Page 42
2 Installation
2.4.3
Issue 10/06
Control terminals Permitted cable diameters: 0.08 … 2.5 mm2 (AWG: 28 … 12) Terminal Designation
Function
1
−
Output +10 V
2
−
Output 0 V
3
ADC1+
Analog input 1 (+)
4
ADC1-
Analog input 1 (-)
5
DIN1
Digital input 1
6
DIN2
Digital input 2
7
DIN3
Digital input 3
8
DIN4
Digital input 4
9
−
Isolated output +24 V / max. 100 mA
10
ADC2+
Analog input 2 (+)
11
ADC2-
Analog input 2 (-)
12
DAC1+
Analog output 1 (+)
13
DAC1-
Analog output 1 (-)
14
PTCA
Connection for PTC / KTY84
15
PTCB
Connection for PTC / KTY84
16
DIN5
Digital input 5
17
DIN6
Digital input 6
18
DOUT1/NC
Digital output 1 / NC contact
19
DOUT1/NO
Digital output 1 / NO contact
20
DOUT1/COM
Digital output 1 / Changeover contact
21
DOUT2/NO
Digital output 2 / NO contact
22
DOUT2/COM
Digital output 2 / Changeover contact
23
DOUT3/NC
Digital output 3 / NC contact
24
DOUT3/NO
Digital output 3 / NO contact
25
DOUT3/COM
Digital output 3 / Changeover contact
26
DAC2+
Analog output 2 (+)
27
DAC2-
Analog output 2 (-)
28
−
Isolated output 0 V / max. 100 mA
29
P+
RS485 port
30
N−
RS485 port
Fig. 2-13
Control terminals of MICROMASTER 440
A detailed description of the inputs and outputs is provided in Section 3.6.
MICROMASTER 440
42
Operating Instructions 6SE6400-5AW00-0BP0
Page 43
Issue 10/06
2.4.4
2 Installation
Avoiding Electro-Magnetic Interference (EMI) The inverters are designed to operate in an industrial environment where a high level of EMI can be expected. Usually, good installation practices will ensure safe and trouble-free operation. If you encounter problems, follow the guidelines stated below.
Action to Take ¾ Ensure that all equipment in the cubicle is well grounded using short, thick grounding cable connected to a common star point or busbar ¾ Make sure that any control equipment (such as a PLC) connected to the inverter is connected to the same ground or star point as the inverter via a short thick link. ¾ Connect the return ground from the motors controlled by the inverters directly to the ground connection (PE) on the associated inverter ¾ Flat conductors are preferred as they have lower impedance at higher frequencies ¾ Terminate the ends of the cable neatly, ensuring that unscreened wires are as short as possible ¾ Separate the control cables from the power cables as much as possible, using separate trunking, if necessary at 90º to each other. ¾ Whenever possible, use screened leads for the connections to the control circuitry ¾ Ensure that the contactors in the cubicle are suppressed, either with R-C suppressors for AC contactors or 'flywheel' diodes for DC contactors fitted to the coils. Varistor suppressors are also effective. This is important when the contactors are controlled from the inverter relay ¾ Use screened or armored cables for the motor connections and ground the screen at both ends using the cable clamps WARNING Safety regulations must not be compromised when installing inverters!
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
43
Page 44
2 Installation
2.4.5
Issue 10/06
Screening Methods
Frame Sizes A, B and C For frame sizes A, B and C the Gland Plate Kit is supplied as an option. It allows easy and efficient connection of the necessary screening. See the Gland Plate Installation Instructions contained on the Document CD-ROM, supplied with the MICROMASTER 440.
Screening without a Gland Plate Should a Gland Plate not be available, then the inverter can be screened using the methodology shown in Fig. 2-14.
1 Mains power input 2 Control cable 3 Motor cable 4 Footprint filter 5 Metal back plate 6 Use suitable clips to fix motor and control cable screens securely to metal back plate 7 Screening cables
Fig. 2-14
Wiring Guidelines to Minimize the Effects of EMI
MICROMASTER 440
44
Operating Instructions 6SE6400-5AW00-0BP0
Page 45
Issue 10/06
2 Installation
Frame Sizes D and E The Gland Plate is factory fitted. If the installation conditions are restricted, the shield of the motor cable can also be attached outside the cabinet, as shown in Fig. 2-14, for example.Frame Sizes FX and GX
Frame size F The gland plate for the control cables is factory-fitted. Devices without filter: The shield of the motor cable must be attached outside the cabinet, as shown in Fig. 2-14, for example. Devices with filter: The gland plate for the motor cable is factory-fitted.
Frame Sizes FX and GX Connect the wire shields to the shield connection points shown in the connection drawing (see Fig. 2-9 and Fig. 2-10) . Twist the shields of the motor cables and screw them to the PE connection for the motor cable. When using an EMI filter, a power commutating choke is required. The wire shields should be fastened to the metallic mounting surface as close as possible to the components.
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
45
Page 46
2 Installation
Issue 10/06
MICROMASTER 440
46
Operating Instructions 6SE6400-5AW00-0BP0