The text of a manual · part 7 of 35

MICROMASTER 440 0.12 kW - 250 kW Operating Instructions: 2 Installation, pages 39 to 46

Pages 39 to 46 of 312, from MICROMASTER 440 0.12 kW - 250 kW Operating Instructions

The original document is the PDF (8.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Siemens 6SE6440-2UD13-7AA1

Page 39

Issue 10/06

2 Installation

Hoisting eyes

Shield connection Mains cable PE Cable opening for mains conection U1/L1, V1/L2, W1/L3 Cable opening DCPA, DCNA for connection of an external braking unit

Mains cable Phase U1/L1, V1/L2, W1/L3 Connection to Y-Capacitor Connection DCPA, DCNA for external braking unit Top adjustment rail Top retaining screw Connection for dv/dt filter DCPS, DCNS Status Display Panel Elektronic box

Bottom adjustment rail Bottom retaining screw Fan screws

Fan Shield connection control leads Fan fuses

Transformer adaption Motor cable Phase U2, V2, W2 Motor cable PE Shield connection

Fig. 2-10

MICROMASTER 440 connection drawing - frame size GX

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

39

Page 40

2 Installation

Issue 10/06

Frame Sizes A to F L3 L2 L1 N

Single Phase Contactor

Optional line choke

Optional Filter

MICROMASTER 1)

Motor

Fuse L/L1

U V

N/L2 W PE PE

PE

Three Phase

L3 L2 L1

Contactor

Optional line choke

Optional Filter

MICROMASTER 1)

Motor

Fuse L3

U

L2

V

L1

W PE

PE

PE

Optional Filter

Optional line choke

1) with and without filter

Frame Sizes FX and GX L3 L2 L1 Contactor

MICROMASTER

2)

Motor

Fuse L3

U

L2

V

L1

W PE

PE

3)

2) without filter 3) the commutation choke is to be earthed using the designated earthing point Fig. 2-11

Motor and Power Connections

MICROMASTER 440

40

Operating Instructions 6SE6400-5AW00-0BP0

Page 41

Issue 10/06

2 Installation

Adaptation of fan voltage (only for frame size FX and GX) A transformer is installed to adapt the existing line voltage to the fan voltage. It may be necessary to reconnect the transformer terminals on the primary side to coincide with the existing line power.

0V 1L380V

1L400V 1L440V

1L480V

-

Connect according input voltage

Fig. 2-12

Adaptation of fan voltage

CAUTION If the terminals are not reconnected to the actually present line voltage, the fan fuses can blow.

Replacement for fan fuses Frame size

Fuses (2 each)

Recommended fuses

FX (90 kW CT)

1 A / 600 V / slow-acting

Cooper-Bussmann FNQ-R-1, 600 V or comparable fuse

FX (110 kW CT)

2,5 A / 600 V / slow-acting

Ferraz Gould Shawmut ATDR2-1/2, 600 V or comparable fuse

GX (132-200 kW CT)

4 A / 600 V / slow-acting

Ferraz Gould Shawmut ATDR4, 600 V or comparable fuse

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

41

Page 42

2 Installation

2.4.3

Issue 10/06

Control terminals Permitted cable diameters: 0.08 … 2.5 mm2 (AWG: 28 … 12) Terminal Designation

Function

1

−

Output +10 V

2

−

Output 0 V

3

ADC1+

Analog input 1 (+)

4

ADC1-

Analog input 1 (-)

5

DIN1

Digital input 1

6

DIN2

Digital input 2

7

DIN3

Digital input 3

8

DIN4

Digital input 4

9

−

Isolated output +24 V / max. 100 mA

10

ADC2+

Analog input 2 (+)

11

ADC2-

Analog input 2 (-)

12

DAC1+

Analog output 1 (+)

13

DAC1-

Analog output 1 (-)

14

PTCA

Connection for PTC / KTY84

15

PTCB

Connection for PTC / KTY84

16

DIN5

Digital input 5

17

DIN6

Digital input 6

18

DOUT1/NC

Digital output 1 / NC contact

19

DOUT1/NO

Digital output 1 / NO contact

20

DOUT1/COM

Digital output 1 / Changeover contact

21

DOUT2/NO

Digital output 2 / NO contact

22

DOUT2/COM

Digital output 2 / Changeover contact

23

DOUT3/NC

Digital output 3 / NC contact

24

DOUT3/NO

Digital output 3 / NO contact

25

DOUT3/COM

Digital output 3 / Changeover contact

26

DAC2+

Analog output 2 (+)

27

DAC2-

Analog output 2 (-)

28

−

Isolated output 0 V / max. 100 mA

29

P+

RS485 port

30

N−

RS485 port

Fig. 2-13

Control terminals of MICROMASTER 440

A detailed description of the inputs and outputs is provided in Section 3.6.

MICROMASTER 440

42

Operating Instructions 6SE6400-5AW00-0BP0

Page 43

Issue 10/06

2.4.4

2 Installation

Avoiding Electro-Magnetic Interference (EMI) The inverters are designed to operate in an industrial environment where a high level of EMI can be expected. Usually, good installation practices will ensure safe and trouble-free operation. If you encounter problems, follow the guidelines stated below.

Action to Take ¾ Ensure that all equipment in the cubicle is well grounded using short, thick grounding cable connected to a common star point or busbar ¾ Make sure that any control equipment (such as a PLC) connected to the inverter is connected to the same ground or star point as the inverter via a short thick link. ¾ Connect the return ground from the motors controlled by the inverters directly to the ground connection (PE) on the associated inverter ¾ Flat conductors are preferred as they have lower impedance at higher frequencies ¾ Terminate the ends of the cable neatly, ensuring that unscreened wires are as short as possible ¾ Separate the control cables from the power cables as much as possible, using separate trunking, if necessary at 90º to each other. ¾ Whenever possible, use screened leads for the connections to the control circuitry ¾ Ensure that the contactors in the cubicle are suppressed, either with R-C suppressors for AC contactors or 'flywheel' diodes for DC contactors fitted to the coils. Varistor suppressors are also effective. This is important when the contactors are controlled from the inverter relay ¾ Use screened or armored cables for the motor connections and ground the screen at both ends using the cable clamps WARNING Safety regulations must not be compromised when installing inverters!

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

43

Page 44

2 Installation

2.4.5

Issue 10/06

Screening Methods

Frame Sizes A, B and C For frame sizes A, B and C the Gland Plate Kit is supplied as an option. It allows easy and efficient connection of the necessary screening. See the Gland Plate Installation Instructions contained on the Document CD-ROM, supplied with the MICROMASTER 440.

Screening without a Gland Plate Should a Gland Plate not be available, then the inverter can be screened using the methodology shown in Fig. 2-14.

1 Mains power input 2 Control cable 3 Motor cable 4 Footprint filter 5 Metal back plate 6 Use suitable clips to fix motor and control cable screens securely to metal back plate 7 Screening cables

Fig. 2-14

Wiring Guidelines to Minimize the Effects of EMI

MICROMASTER 440

44

Operating Instructions 6SE6400-5AW00-0BP0

Page 45

Issue 10/06

2 Installation

Frame Sizes D and E The Gland Plate is factory fitted. If the installation conditions are restricted, the shield of the motor cable can also be attached outside the cabinet, as shown in Fig. 2-14, for example.Frame Sizes FX and GX

Frame size F The gland plate for the control cables is factory-fitted. Devices without filter: The shield of the motor cable must be attached outside the cabinet, as shown in Fig. 2-14, for example. Devices with filter: The gland plate for the motor cable is factory-fitted.

Frame Sizes FX and GX Connect the wire shields to the shield connection points shown in the connection drawing (see Fig. 2-9 and Fig. 2-10) . Twist the shields of the motor cables and screw them to the PE connection for the motor cable. When using an EMI filter, a power commutating choke is required. The wire shields should be fastened to the metallic mounting surface as close as possible to the components.

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

45

Page 46

2 Installation

Issue 10/06

MICROMASTER 440

46

Operating Instructions 6SE6400-5AW00-0BP0