Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 6 of 35

MICROMASTER 440 0.12 kW - 250 kW Operating Instructions: 2 Installation, pages 30 to 38

Pages 30 to 38 of 312, from MICROMASTER 440 0.12 kW - 250 kW Operating Instructions

The original document is the PDF (8.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Siemens 6SE6440-2UD13-7AA1

Page 30

2 Installation

Table 2-1 Frame-Size

Issue 10/06

Dimensions and Torques of MICROMASTER 440 Overall Dimensions

Fixing Method

Tightening Torque mm

73 x 173 x 149 inch

2,87 x 6,81 x 5,87

2 M4 Bolts 4 M4 Nuts 4 M4 Washers or fitting on a standard rail

2,5 Nm with washers fitted

4 M4 Bolts 4 M4 Nuts 4 M4 Washers

2,5 Nm with washers fitted

4 M5 Bolts 4 M5 Nuts 4 M5 Washers

2,5 Nm with washers fitted

4 M8 Bolts 4 M8 Nuts 4 M8 Washers

3,0 Nm with washers fitted

4 M8 Bolts 4 M8 Nuts 4 M8 Washers

3,0 Nm with washers fitted

4 M8 Bolts 4 M8 Nuts 4 M8 Washers

3,0 Nm with washers fitted

6 M8 Bolts 6 M8 Nuts 6 M8 Washers

13 Nm +30 % with washers fitted

6 M8 Bolts 6 M8 Nuts 6 M8 Washers

13 Nm +30 % with washers fitted

A

Width x Height x Depth Width x Height x Depth mm

149 x 202 x 172

B inch

5,87 x 7,95 x 6,77

Width x Height x Depth mm

185 x 245 x 195

C inch

7,28 x 9,65 x 7,68

Width x Height x Depth mm

275 x 520 x 245

D inch

10,82 x 20,47 x 9,65

Width x Height x Depth mm

275 x 650 x 245

E inch

10,82 x 25,59 x 9,65 mm

F

Width x Height x Depth

350 x 850 mm x 320 height with filter 1150 inch

13,78 x 33,46 x 12,60 height with filter 45,28

Width x Height x Depth mm

326 x 1400 x 356

FX inch

12,80 x 55,12 x 12,83

Width x Height x Depth mm

326 x 1533 x 545

GX inch

12,80 x 60,35 x 21,46

MICROMASTER 440

30

Operating Instructions 6SE6400-5AW00-0BP0

Page 31

Issue 10/06

2.3.1

2 Installation

Mounting onto standard rail, Frame Size A

Mounting the inverter onto a 35 mm standard rail (EN 50022) Release Mechanism

Upper rail latch

1. Locate the inverter on the mounting rail using the upper rail latch 2. Using a flat blade screwdriver, press the release mechanism downwards and engage the inverter into the lower rail latch.

Lower rail latch

Removing the Inverter from the rail 1. To disengaged the release mechanism of the inverter, insert a screwdriver into the release mechanism. 2. Apply a downward pressure and the lower rail latch will disengage. 3. Pull the inverter from the rail.

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

31

Page 32

2 Installation

2.3.2

Issue 10/06

Installing communication options and/or pulse encoder evaluation module

Sizes A to F NOTE When installing the following options – PROFIBUS module, DeviceNet module, CANopen option module and/or pulses encoder evaluation module, the mounting depth of the drive inverter is increased! Please refer to the relevant Operating Instructions for the actual procedure.

Sizes FX and GX The front cover of the MICROMASTER 440 is designed so that the control module (normally the SDP) is almost flush with the opening in the front cover. If more than one option is to be installed in the electronic box, it is necessary to position the entire electronic box further to the rear Installing the options ¾ Remove the front cover: • Unscrew two screws at the bottom side of the front cover. • Lift front cover up and out. ¾ Remove retaining screws on the electronic box. ¾ Screw on electronic box in correct installation position as shown in Fig. 2-7 ¾ Install additional options. ¾ Reinstall front cover. Installation position 2 Installation position 1 Standard installation

Standard installation Installation position 1 Installation position 2

Fig. 2-7

Options for the electronic box

MICROMASTER 440

32

Operating Instructions 6SE6400-5AW00-0BP0

Page 33

Issue 10/06

2.4

2 Installation

Electrical installation WARNING The inverter must always be grounded. ¾ To ensure the safe operation of the equipment, it must be installed and commissioned by qualified personnel in full compliance with the warnings laid down in these operating instructions. ¾ Take particular note of the general and regional installation and safety regulations regarding work on dangerous voltage installations (e.g. EN 50178), as well as the relevant regulations regarding the correct use of tools and personal protective gear. ¾ Never use high voltage insulation test equipment on cables connected to the inverter. ¾ The mains input, DC and motor terminals, can carry dangerous voltages even if the inverter is inoperative; wait 5 minutes to allow the unit to discharge after switching off before carrying out any installation work. ¾ If the front cover (Frame Sizes FX and GX) has been removed, the fan impeller is exposed. There is danger of injury when the fan is running. CAUTION The control, power supply and motor leads must be laid separately. Do not feed them through the same cable conduit/trunking.

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

33

Page 34

2 Installation

2.4.1

Issue 10/06

General WARNING The inverter must always be grounded. If the inverter is not grounded correctly, extremely dangerous conditions may arise within the inverter which could prove potentially fatal.

Operation with ungrounded (IT) supplies Filtered The use of filtered MICROMASTER 4 drives on unearthed mains supplies is not permitted. Unfiltered In the case of non-grounded networks, the 'Y' capacitor of the device must be made ineffective. The procedure is described in Appendix D. If the MICROMASTER is to remain in operation in non-grounded networks when a ground fault occurs during the input or output phase, an output reactor must be installed.

Operation with Residual Current Device (Frame Sizes A to F) If an RCD (also referred to as ELCB or RCCB) is fitted, the MICROMASTER inverters will operate without nuisance tripping, provided that: ¾ A type B RCD is used. ¾ The trip limit of the RCD is 300 mA. ¾ The neutral of the supply is grounded. ¾ Only one inverter is supplied from each RCD. ¾ The output cables are less than 50 m (screened) or 100 m (unscreened). NOTE The residual current operated circuit-breakers used must provide protection against direct-current components in the fault current and must be suitable for briefly suppressing power pulse current peaks. It is recommended to protect the frequency inverter by fuse separately. The regulations of the individual country (e.g. VDE regulations in Germany) and the regional power suppliers must be observed!

MICROMASTER 440

34

Operating Instructions 6SE6400-5AW00-0BP0

Page 35

Issue 10/06

2.4.2

2 Installation

Power and motor connections WARNING The inverter must always be grounded. ♦ Isolate the mains electrical supply before making or changing connections to the unit. ♦ Ensure that the inverter is configured for the correct supply voltage: MICROMASTERS must not be connected to a higher voltage supply. ♦ When synchronous motors are connected or when coupling several motors in parallel, the inverter must be operated with V/f control characteristic (P1300 = 0, 2 or 3). CAUTION After connecting the power and motor cables to the proper terminals, make sure that the front covers have been replaced properly before supplying power to the unit! NOTICE ♦ ♦

Ensure that the appropriate circuit-breakers/fuses with the specified current rating are connected between the power supply and inverter (see chapter 5, Tables 5-5). Use Class 1 60/75 oC copper wire only (for UL compliance). For tightening torque see Table 5-2.

Operation with long cables All inverters will operate at full specification with cable lengths as follows: Frame Sizes

A to F

FX and GX screened

50 m

100 m unscreened

100 m

150 m

Using the output chokes specified in catalogue DA 51.2, the following cable lengths are possible for the appropriate frame sizes: Supply Voltage

200 V … 240 V ± 10%

380 V … 400 V ± 10 %

401 V … 480 V ± 10 %

Frame Sizes

A…F

A…B

C

C

D…F screened

200 m

150 m

200 m

200 m

300 m

100 m

200 m

300 m

100 m

200 m unscreened

300 m

225 m

300 m

300 m

450 m

150 m

300 m

450 m

150 m

300 m

D … F FX, GX A … C D … F FX, GX

500 V … 600 V ± 10%

CAUTION If using output chokes operation is only permissible with a pulse frequency of 4 kHz. Make shure that the automatic pulse frequency reductions are disabled. Coercing required parameter adjusting: P1800 = 4 kHz , P0290 = 0 or 1.

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

35

Page 36

2 Installation

Issue 10/06

Access to the power and motor terminals Access to the power supply and motor terminals is possible by removing the front covers (See Fig. 2-8 to Fig. 2-10). See also Appendix B. After removing the front covers and exposing the terminals, complete power and motor connections as shown in Fig. 2-11.

Connection of braking unit (only for framesize FX and GX) A passage opening for access to the intermediate circuit connections has been provided on the top side of the inverter. It is possible to connect an external braking unit (refer to Catalog DA65.11 or DA65.10) to these terminals. The position is shown in Fig. 2-9 and Fig. 2-10. The maximum cross section of connections is 50 mm², but only provided the crimped area of cable shoes on the equipment side is provided with a heatshrinkable sleeve. This measure is important to ensure that air gaps and creep distances are observed.

MICROMASTER 440

36

Operating Instructions 6SE6400-5AW00-0BP0

Page 37

Issue 10/06

Fig. 2-8

2 Installation

MICROMASTER 440 Connection Terminals

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

37

Page 38

2 Installation

Issue 10/06

Hoisting eyes Shield connection Mains cable PE Cable opening for mains conection U1/L1, V1/L2, W1/L3 Cable opening DCPA, DCNA for connection of an external braking unit Mains cable Phase U1/L1, V1/L2, W1/L3 Connection to Y-Capacitor

Connection DCPA, DCNA for external braking unit Top adjustment rail Top retaining screw Connection for dv/dt filter DCPS, DCNS

Status Display Panel Elektronic box

Bottom adjustment rail Bottom retaining screw Fan screws

Fan Shield connection control leads

Fan fuses Transformer adaption Motor cable Phase U2, V2, W2 Motor cable PE Shield connection

Fig. 2-9

MICROMASTER 440 connection drawing – frame size FX

MICROMASTER 440

38

Operating Instructions 6SE6400-5AW00-0BP0