MICROMASTER 440 0.12 kW - 250 kW Operating Instructions: 2 Installation, pages 21 to 29

Pages 21 to 29 of 312, from MICROMASTER 440 0.12 kW - 250 kW Operating Instructions

The original document is the PDF (8.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Siemens 6SE6440-2UD13-7AA1

Page 21

Issue 10/06

2

2 Installation

Installation

This Chapter contains: ¾ ¾ ¾ ¾

General data relating to installation Dimensions of Inverter Wiring guidelines to minimize the effects of EMI Details concerning electrical installation

2.1

Installation after a Period of Storage ...................................................................... 23

2.2

Ambient operating conditions ................................................................................. 24

2.3

Mechanical installation............................................................................................ 26

2.4

Electrical installation ............................................................................................... 33

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

21

Page 22

2 Installation

Issue 10/06

WARNING ¾ Work on the device/system by unqualified personnel or failure to comply with warnings can result in severe personal injury or serious damage to material. Only suitably qualified personnel trained in the setup, installation, commissioning and operation of the product should carry out work on the device/system. ¾ Only permanently-wired input power connections are allowed. This equipment must be grounded (IEC 536 Class 1, NEC and other applicable standards). ¾ Only type B ELCBs should be used with FSA to FSF. Machines with a threephase power supply, fitted with EMC filters, must not be connected to a supply via an ELCB (Earth Leakage Circuit-Breaker - see DIN VDE 0160, section 5.5.2 and EN50178 section 5.2.11.1). ¾ The following terminals can carry dangerous voltages even if the inverter is inoperative: ♦ the power supply L/L1, N/L2, L3 resp. U1/L1, V1/L2, W1/L3 ♦ the motor terminals U, V, W resp. U2, V2, W2 ♦ and depending on the frame size the terminals DC+/B+, DC-, B-, DC/R+ resp. DCPS, DCNS, DCPA, DCNA ¾ Always wait 5 minutes to allow the unit to discharge after switching off before carrying out any installation work. ¾ This equipment must not be used as an ‘emergency stop mechanism’ (see EN 60204, 9.2.5.4) ¾ The minimum size of the earth-bonding conductor must be equal to or greater than the cross-section of the power supply cables. ¾ If the front cover (Frame Sizes FX and GX) has been removed, the fan impeller is exposed. There is danger of injury when the fan is running. CAUTION The connection of power, motor and control cables to the inverter must be carried out as shown in Fig. 2-11 on page 44, to prevent inductive and capacitive interference from affecting the correct functioning of the inverter.

MICROMASTER 440

22

Operating Instructions 6SE6400-5AW00-0BP0

Page 23

Issue 10/06

2.1

2 Installation

Installation after a Period of Storage Following a prolonged period of storage, you must reform the capacitors in the inverter.

Frame Sizes A to F Voltage [%] 100

75

50

0,5

Fig. 2-1

1

2

Storage period less than 1 year:

No action necessary

Storage period 1 to 2 years:

Prior to energizing, connect to voltage for one hour

Storage period 2 to 3 years:

Prior to energizing, form according to the curve

Storage period 3 and more years:

Prior to energizing, form according to the curve

4

6

8

Time t [h]

Forming

Frame Sizes FX and GX Reforming the capacitors can be accomplished by applying 85% of the rated input voltage for at least 30 minutes without load.

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

23

Page 24

2 Installation

2.2

Issue 10/06

Ambient operating conditions

Temperature Frame Sizes A to F:

Frame Sizes FX and GX:

Permissible output current [%]

Permissible output current [%] 100

100

95 75 90 50

85 constant torque

25

-10

0

Fig. 2-2 variable torque

10

20

30

60 40 50 Ambient temperature

[°C]

0

10

20

30

40 45 50 55 [°C] Ambient temperature

Ambient operating temperature

Humidity Range Relative air humidity ≤ 95 % Non-condensing

Altitude If the inverter is to be installed at an altitude > 1000 m or > 2000 m above sea level, derating will be required: Permissible output current 100 %

Permissible input voltage Frame Sizes 100 FX and GX Frame Sizes % A to F

85 80

80 77

0 1000 2000 3000 4000 Installation altitude in m above sea level

Fig. 2-3

2000 0 1000 3000 4000 Installation altitude in m above sea level

Installation altitude

Shock and Vibration Do not drop the inverter or expose to sudden shock. Do not install the inverter in an area where it is likely to be exposed to constant vibration. Mechanical strength to EN 60721-33 ¾ Deflection: 0.075 mm (10 ... 58 Hz) ¾ Acceleration: 9.8 m/s2 (> 58 ... 200 Hz)

Electromagnetic Radiation Do not install the inverter near sources of electromagnetic radiation.

MICROMASTER 440

24

Operating Instructions 6SE6400-5AW00-0BP0

Page 25

Issue 10/06

2 Installation

Atmospheric Pollution Do not install the inverter in an environment, which contains atmospheric pollutants such as dust, corrosive gases, etc.

Water Take care to site the inverter away from potential water hazards, e.g. do not install the inverter beneath pipes that are subject to condensation. Avoid installing the inverter where excessive humidity and condensation may occur.

Installation and cooling CAUTION The inverters MUST NOT be mounted horizontally. The inverters can be mounted without any clearance at either side. When mounting inverters one above the other, the specified environmental conditions must not be exceeded. Independent of this, these minimum distances must be observed. ¾ Frame Size A, B, C above and below 100 mm ¾ Frame Size D, E above and below 300 mm ¾ Frame Size F above and below 350 mm ¾ Frame Size FX, GX above 250 mm below 150 mm in front 40 mm (FX), 50 mm (GX) No equipment that could have a negative effect on the flow of cooling air should be installed in this area. Make sure that the cooling vents in the inverter are positioned correctly to allow free movement of air.

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

25

Page 26

2 Installation

2.3

Issue 10/06

Mechanical installation WARNING ¾ To ensure the safe operation of the equipment, it must be installed and commissioned by qualified personnel in full compliance with the warnings laid down in these operating instructions. ¾ Take particular note of the general and regional installation and safety regulations regarding work on dangerous voltage installations (e.g. EN 50178), as well as the relevant regulations regarding the correct use of tools and personal protective equipment (PPE). ¾ The mains input, DC and motor terminals, can carry dangerous voltages even if the inverter is inoperative; wait 5 minutes to allow the unit to discharge after switching off before carrying out any installation work. ¾ The inverters can be mounted without any clearance at either side. When mounting inverters one above the other, the specified environmental conditions must not be exceeded. Independent of this, these minimum distances must be observed. • Frame Size A, B, C above and below 100 mm • Frame Size D, E above and below 300 mm

• Frame Size F above and below 350 mm

• Frame Size FX, GX above 250 mm below 150 mm in front 40 mm (FX), 50 mm (GX) ¾ If the front cover (Frame Sizes FX and GX) has been removed, the fan impeller is exposed. There is danger of injury when the fan is running. ¾ IP20 protection is only against direct contact, always use these products within a protective cabinet. 4

Removing from transport pallet (only for frame sizes FX and GX) During transport, the inverter is fastened on the transport pallet with the aid of two iron brackets. WARNING Note that the center of gravity of the inverter is not in the middle of the unit. When lifting the pallet, the unit can therefore suddenly change position and swing to the side. 1. Fasten the hoisting crane cable to the hoisting eyes on the inverter (2 eyes, see Fig. 2-9 and Fig. 2-10). 2. Remove the two retaining bolts at the top of the front cover. 3. Unscrew the bolts in the iron brackets on the transport pallet and lift the inverter off the pallet. 4. Once installation has been completed and the inverter connected, fasten the two retaining bolts for the front cover at the bottom side of the door.

MICROMASTER 440

26

Operating Instructions 6SE6400-5AW00-0BP0

Page 27

Issue 10/06

2 Installation

Frame Sizes A to F Frame Size A

Frame Size B

Frame Size C Ø 5.5 mm 0.22"

Ø 4.8 mm 0.19"

55 mm 2.2"

204 mm 8.03"

174 mm 6.85"

160 mm 6.30"

138 mm 5.43"

Ø 4.5 mm 0.17"

Frame Size D

174 mm 6.85"

Frame Size E

Frame Size F

Ø 17.5 mm 0.68"

Ø 17.5 mm 0.68"

Ø 15 mm 0.59"

486 mm 19.13" 616.4 mm 24.27" 810 mm 31.89" with filter 1110 mm 43.70"

235 mm 9.25"

235 mm 9.25"

300 mm 11.81"

Fig. 2-4

Drill pattern for MICROMASTER 440

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

27

Page 28

2 Installation

Issue 10/06

Frame Size FX

Fig. 2-5

Installation dimensions for MICROMASTER 440 Frame size FX

MICROMASTER 440

28

Operating Instructions 6SE6400-5AW00-0BP0

Page 29

Issue 10/06

2 Installation

Frame Size GX

Fig. 2-6

Installation dimensions for MICROMASTER 440 Frame size GX

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

29