3 Functions read at once from an “indexed” parameter (refer to "Index", special setting, index = 255). This setting to variable word-length is made during start-up. (refer to parameter P2013). Parameter ID (PKE) 15
14
13
12
11
10
9
8
7
6
SP M
AK
1st word 5
4
3
2
1
0
PNU1 Parameter index (IND)
15
14
13
12
PNU2
11
Bit No.:
10
RES
9
8
7
6
2nd word 5
TXT
4
3
2
1
0
Bit No.:
2
1
0
Bit No.:
Index
Parameter value (PWE) 15
14
13
12
11
10
9
8
7
6
5
4
3
Parameter value, high
(PWE1)
3rd word
Parameter value, low
(PWE2)
4th word
The following applies: ¾ AK Task or reply ID ¾ SPM Toggle bit for processing of parameter-change reports (MICROMASTER does not support this, SPM = 0) ¾ PNU Parameter number ¾ RES Reserved ¾ TXT Read / write from parameter text (MICROMASTER does not support this, TXT = 0)
CAUTION ¾ Do not use a variable word length if SIMATIC S5 or SIMATIC S7 is the master. ¾ This setting must be made both at the master as well as at the slave – and cannot be changed while the bus is operational. NOTE ¾ The PKW area is transferred in increasing order, always starting with the 1st word. ¾ Reserved fields or functions that are not supported should be specifically preassigned zero in the master implementation. ¾ The bit 11 (SPM) is the toggle bit for parameter change reports. Parameter change reports when reading/writing parameter texts are not supported by MICROMASTER.
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
157
Page 158
3 Functions
Issue 10/06
Task or reply ID (AK): Bits 12 to 15 (AK) contain the task or reply ID. The task IDs are sent in the telegram from the master to the slave. The meaning of the IDs is listed in the following table. Table 3-19
Task IDs (master -> drive converter)
Task ID
Meaning
0
No task
1
Request parameter value
1 or 2
7
2
Change parameter value (word) and save only in RAM
1
7 or 8
3
Change parameter value (double word) and save only in RAM
2
7 or 8
3
7
3
7 or 8
4 or 5
7
4
7 or 8
4 5 6 7
Request descriptive element
Reply ID negative
0
-
1 1
Changing the descriptive element MICROMASTER does not support this 1
Request parameter value (array)
2
Change parameter value (array, word) and save only in RAM 2
8
Change parameter value (array, double word) and save only in RAM
5
7 or 8
9
Request the number of array elements
6
7
10
Reserved
-
-
11
Change parameter value (array, double word) and save in RAM and EEPROM2
5
7 or 8
12
Change parameter value (array, word) and save in RAM 2 and EEPROM
4
7 or 8
13
Change parameter value (double word) and save in RAM and EEPROM
2
7 or 8
14
Change parameter value (word) and save in RAM and EEPROM
1
7 or 8
15
Read or change text MICROMASTER does not support this
15
7 or 8
1
The required element of the parameter description is specified in IND (2nd word)
2
The required element of the indexed parameter is specified in IND (2nd word)
MICROMASTER 440
158 positive
Operating Instructions 6SE6400-5AW00-0BP0
Page 159
Issue 10/06
3 Functions
Correspondingly, the Response IDs are transferred in the telegram from the slave to the master at this position. Depending on the request ID, only specific response IDs are possible. Table 3-20
Response ID (converter -> master)
Response Significance ID
Request ID
0
No response
0
1
Transfer parameter value (word)
1, 2 or 14
2
Transfer parameter value (double word)
3
Transfer descriptive element
4
Transfer parameter value (array, word)
5
Transfer parameter value (array, double word)
6
Transfer the number of array elements
9
7
Request cannot be executed (with fault number)
1 or 15
8
The PKW interface does not have master authority
2, 3, 5, 7, 8, 11-14 or 15
9
Parameter change report (word) MICROMASTER does not support this
-
10
Parameter change report (double word) MICROMASTER does not support this
-
11
Parameter change report (array, word) MICROMASTER does not support this
1, 3 or 13
1
4 or 5 2
6, 7 or 12 2
6, 8 or 11
2
2
12
Parameter change report (array, double word) MICROMASTER does not support this
13
Reserved
-
14
Reserved
-
15
Transfer text MICROMASTER does not support this
15
1
The required element of the parameter description is specified in IND (2nd word)
2
The required element of the indexed parameter is specified in IND (2nd word)
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
-
159
Page 160
3 Functions
Issue 10/06
If the response ID has the value 7 (request cannot be executed), then a fault number is saved in parameter value 2 (PWE2). The fault numbers are documented in the following table. Table 3-21
Fault numbers for the response ID "Request cannot be executed"
Fault No.
Significance
0
Inadmissible legal parameter number (PNU); if PNU is not available
1
Parameter value cannot be changed; if the parameter is a visualization parameter
2
Lower or upper limit exceeded
3
Erroneous sub-index
4
No array
5
Incorrect type of data
6
Setting not permitted (can only be reset)
7
Descriptive element cannot be changed; not possible
11
No operator control rights
12
Key word missing, device parameter: ‘access keyl’ and/or ‘special parameter access’ not appropriately set
15
No text array available
17
Request cannot be executed due to operating states; The frequency inverter state presently does not allow the request that was issued
101
Parameter number presently de-activated; In the present frequency inverter state, the parameter has no function (e.g. closed-loop control type)
102
Channel width too small: Only for short channels; the parameterized length of the PKW area has been selected too large due to the restrictions in the device. This fault message can only occur for the USS protocol on the technology module T 100 if basic device parameters are accessed from this interface Incorrect PKW number; only for G-SST 1/2 and SCB interface (USS). The fault number is transferred in the following two cases:
¾ If the request involves all indices of an indexed parameter (request index equal to 103
255) or the complete parameter description is requested and a variable telegram length was not parameterized.
¾ If, for the request issue, the parameterized number of PKW data in the telegram is too low (e.g.: Changing from a double word and PKW number equal to 3 (words). 104
Parameter value not permissible; This fault number is transferred if the parameter value – that is to be transferred – is not assigned any function in the device or at the time of the change it is not able to be transferred for internal reasons (although it lies within the limits).
105
The parameter is indexed e.g. request: ‘PWE, change word’ for indexed parameters
106
Request not implemented
200
New minimum value
201
New maximum value
203
No BOP/AOP display, Parameter cannot be displayed on the BOP or AOP.
204
The ‘BOP/AOP key word’ does not match the parameter access stage.
MICROMASTER 440
160
Operating Instructions 6SE6400-5AW00-0BP0
Page 161
Issue 10/06
3 Functions
Parameter number (PNU) The complete parameter number (refer to the parameter list) is formed from the "basis parameter number” PNU1 and the "page parameter number” PNU2. The following applies: PNU = PNU1 + 2000 • PNU2 With PNU2 definition: PNU2
2nd word
15
14
13
12
Bit No.:
20
23
22
21
Weighting
The parameter areas are mapped using PNU1 and PNU2 as follows: Basis parameter number PNU1 bits 0 – 10 (PKE)
Page parameter number PNU2 bits 12 – 15 (IND)
Parameter number (area)
0 ... 1999
0
0 ... 1999
0 ... 1999
1
2000 ... 3999
0 ... 1999
2
4000 ... 5999
0 ... 1999
3
6000 ... 7999
0 ... 1999
4
8000 ... 9999
...
...
...
0 ... 1999
15
30000 ... 31999
Index The index (bit 0 to 7), depending on the task, describes a definite element: ¾ desired array element in the case of indexed parameters, ¾ desired element of the parameter description, Special significance of index value 255 For the following requests, the index value 255 has a special significance: ¾ "request parameter descriptive element", or. ¾ for the requests to read/write indexed parameters (= arrays) Here, the following applies: Task ID
Meaning
4
The complete parameter description is requested
6
All values of the indexed parameters are requested This request can generate fault message 102.
7, 8, 11 or 12
All values of the indexed parameters should be changed. These requests can generate fault message 102.
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
161
Page 162
3 Functions
Issue 10/06
Parameter value (PWE) The parameter value (PWE) is transferred, depending on the parameterization of the word length (refer to parameter "USS-PKW length" P2013) of the PKW area as word or double word (32 bit). Only one parameter value can be transferred in a telegram. If the word length of the PKW area is parameterized with 3 words (P2013 = 3), then only 16-bit parameters can be transferred. Parameter descriptive elements, that are greater than 16 bit cannot be transferred. If the word length of the PKW area is parameterized to be 4 words (P2013 = 4), then 16 and 32-bit parameters can be transferred. Parameter descriptive elements that exceed 32 bits cannot be transferred. If the word length of the PKW area is parameterized with "variable length" (P2013 = 127), then 16, 32-bit parameter and parameter descriptive elements can be transferred. Further, all elements of an indexed parameter can be read or changed with a single request, as well as the complete parameter description requested if the index corresponds to the value 255 (index = 255). Transferring one 16-bit parameter value: 1. Fixed PKW area, 3 words: The value is in PWE1 2. Fixed PKW area, 4 words: The value is in PWE2 (least significant word, 4th word); PWE1 is set to 0. 3. Variable PKW area: The value is in PWE1. PWE2 and higher not available! Transferring one 32-bit parameter value: 1. Fixed PKW area, 3 words: Request is rejected with fault message 103. 2. Fixed PKW area, 4 words: PWE1 (most significant word; 3rd word) contains the high word of the double word, PWE2 (least significant word; 4th word) contains the low word of the double word. 3. Variable PKW area: As for 2.; PWE3 and higher not available!
Process data area (PZD) Process data is continually exchanged between the master and slaves in this area. At the start of communications it is configured as to which process data is to be exchanged with a slave. For instance, for slave x, the current setpoint is to be transferred in the second PZD (= PZD2). This setting remains for the complete data transfer. 1 word
1 word
1 word
1 word
PZD1
PZD2
PZD3
PZD4
1 word .....
PZD8
PZD1 – PZD8 = process data = control / status word(s) and setpoint / actual value(s)); The control / status word(s), setpoints and actual values required for the automation are transferred in this area. The length of the PZD area is defined by the number of PZD elements (P2012). Contrary to the PKW area, that can be variable, the length of this area between the communication partners (master and slave) must always be permanently declared.
MICROMASTER 440
162
Operating Instructions 6SE6400-5AW00-0BP0
Page 163
Issue 10/06
3 Functions
The maximum number of PZD words per telegram is, for MICROMASTER, limited to 8 words (USS-PZD length in MICROMASTER is set using parameter P2012). If only PKW data are to be transferred in the net data block, then the number of the PZD can also be 0! Depending on the data transfer direction, always control word 1 or status word 1 are to be transferred in the PZD1. Depending on the data transfer direction, the main setpoint or the main actual value is always transferred in PZD 2. Additional setpoints or actual values are set in the following process data PZD3 to PZDn. For MICROMASTER, if required, control word 2 or status word 2 should be transferred in PZD4. Request telegram, master ⇒ slave PZD1
PZD2
PZD3
PZD4
.....
PZD8
Control word 1
Setpoint 1
Control word 2
Setpoint 2
.....
Setpoint 6
PZD4
.....
PZD8
Response telegram, slave ⇒ master PZD1
PZD2
Status word 1
Main actual value 1
PZD3 Actual value 2 status word 2
Actual value
3
.....
Actual value
7
NOTE ¾ A maximum of 8 PZD words ¾ A minimum of 0 PZD words - i.e. no PZD area in the net data area ¾ On the USS bus, PZD n is always transferred before PZD n+1. ¾ For MICROMASTER, double words cannot be transferred in the PZD section. ¾ Data received from MICROMASTER is always interpreted as 16-bit words. The appropriate de-normalization is implemented by assigning the appropriate parameters. ¾ If MICROMASTER sends data to the master via the PZD area, then for physical quantities, a normalization is made to a 16-bit value (4000 hex notation). ¾ The setpoint can be freely assigned to the actual value; This means for example that the frequency setpoint is transferred in the request telegram in PZD2 so the actual frequency value can be signaled back in PZD2 in the response telegram (this also makes sense from a technological/process perspective); or however, also another actual value – such as the actual torque value, actual voltage actual value or actual current value. The setpoint can be freely assigned to the actual value; for example the frequency setpoint is transferred in the request telegram in PZD2, which means that the actual frequency value can be signaled back in the response telegram in PZD2 (this also makes sense from a technological/process perspective) – or also another actual value – such as actual torque value, actual voltage value or actual current value.
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
163
Page 164
3 Functions
3.7.1.3
Issue 10/06
USS bus configuration via COM link (RS485) In order to ensure disturbance-free USS operation, the bus cable must be terminated at both ends using bus terminating resistors. In this case, the bus cable from the first USS device [node] up to the last USS device [node] should be considered as one bus cable – so that the USS bus should be terminated twice. For the first bus node [device] (e.g. master) and last bus node [device] (e.g. drive converter), th bus terminating resistor must be switched-in.
NOTE ♦ When supplied, the bus terminating resistors are not switched-in! ♦ Please note that you only switch-in the bus terminating at the first bus node [device] and last bus note [device]! The bus terminating resistors should be always set with the system in a no-voltage state (e.g. powered-down)! ♦ Data transfer errors on the bus are possible! In active bus operation, devices where the terminating resistor is switched-in, may not be in a no-voltage state. The terminating resistor draws the voltage from the connected device. This is the reason that the terminating resistor is no longer effective when the device is in a no-voltage state (e.g. when powered down) .
The following diagram shows the structure of a bus connection through terminals 29, 30:
RS485 terminator
RS485 terminator
Potential equilization cable
Master
0V (M)
Screening
Screening
Screening
− a terminating resistor must be connected at the first and last devices [nodes] on the bus cable
− no bus termination for other devices [nodes]
Fig. 3-47
Connecting the USS bus cable
MICROMASTER 440
164
Operating Instructions 6SE6400-5AW00-0BP0
Page 165
Issue 10/06
3 Functions
When the MICROMASTER is used in an RS485 bus communications network the following is required: 1. A power supply 2. A terminating resistor between P+ and N- at both bus ends (refer to Fig. 3-48) Control terminals +10 V 0 V
1
2
P+
N-
29
30
RS485 terminator to terminal 2 of the next slave
Fig. 3-48
Connecting the RS485 terminator
If the frequency inverter is the last slave on the bus (refer to Fig. 3-47), then the P+ and N- of the RS485 terminator provided must be connected there to the RS485 terminals (refer to Fig. 3-48). P10 and 0 V can be connected to terminals 1 and 2 for the power supply. If the frequency inverter is the first slave, then the bus should only be terminated there with P+ and N- (120 Ω). If the first or last bus node is not a MICROMASTER 4, then the bus between P+ and N– must be terminated with a resistor (between 120 Ω and 220 Ω). The bus must be operated with a bias on one or on both ends (pull-up resistance from P+ to P5 or P10, pull-down resistance from N– to 0 V). If the first or last bus node is not a MICROMASTER 4 (e.g. a controller of the S7-200 series), the bus can then be biased by connecting 390 Ω resistors from P+ to P5 and from N– to 0 V. If the first or last bus node is a controller of the S7-200 series, SIMATIC PROFIBUS connectors, e.g. 6ES7972-0BA41-0XA0, can be used for the bias and the termination.
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
165
Page 166
3 Functions
Issue 10/06
NOTE ¾ When making the installation it must be ensured that EMC disturbances/noise cannot result in communication failures/errors or damage to the RS485 drivers. As a minimum, the following measures must be taken: 1) Shield the motor cable and correctly ground the shield at both ends. If at all possible, avoid interruptions in the cables. If this cannot be avoided, then it must be ensured that the shield continues in an EMC-correct fashion at the connecting locations. 2) All node points must be well grounded (EMC ground). 3) All relay coils must be provided with noise suppression elements. 4) The cables should be routed - as far as possible - separately from other cables. For RS485 cables it is especially important that they are kept well away from motor cables. 5) The shields of RS485 cables must be correctly grounded. ¾ If the AOP communicates via the USS protocol, then contrary to the BOP, the appropriate USS parameters (Table 3-13 and Table 3-14) should be set. ¾ For error-free communications, the appropriate communication parameters must be harmonized with one another and correctly set - in the frequency inverter, the connected device and/or in the connected option board. Please refer to the corresponding Operating Instructions for the AOP and for the communications modules. ¾ While RS485 communications is operational the power supply must always be available using pull-up/pull-down resistors.