Page 167

Issue 10/06

3.8

3 Functions

Fixed frequencies (FF) Number: Parameter range: Warnings Faults Function chart number:

15 P1001 – P1028 FP3200, FP3210

A setpoint can be entered via the analog inputs, the serial communication interfaces, the JOG function, the motorized potentiometer as well as also using fixed frequencies. The fixed frequencies are defined using parameters P1001 – P1015 and selected via binector inputs P1020 – P1023, P1025, P1026. The effective fixed frequency setpoint is available via connector output r1024 which means that it can be connected further. If this is to be used as setpoint source, then either parameter P1000 or P0719 should be modified or BICO parameter r1024 should be connected to the main setpoint P1070 or supplementary setpoint P1075. Contrary to parameter P0719, when parameter P1000 is modified, this implicitly changes BICO parameters P1070, P1075.

Example:

Fixed frequencies as setpoint source a) Standard method → P1000 = 3 b) BICO method → P1070 = 1024, P1075 = 0

3 methods are available when selecting the fixed frequencies.

Direct selection In this particular mode, the control signal directly selects the fixed frequency. This control signal is entered via the binector inputs. If several fixed frequencies are simultaneously active, then the selected frequencies are added. Table 3-22

Example for direct coding via digital inputs DIN6

DIN5

DIN4

DIN3

DIN2

DIN1

FF0

0 Hz

0

0

0

0

0

0

FF1

P1001

0

0

0

0

0

1

FF2

P1002

0

0

0

0

1

0

FF3

P1003

0

0

0

1

0

0

FF4

P1004

0

0

1

0

0

0

FF5

P1005

0

1

0

0

0

0

FF6

P1006

1

0

0

0

0

0

0

0

0

0

1

1

1

1

1

1

1

1

…

…

FF1+FF2

FF1+FF2+FF3+FF4+FF5+FF6

The fixed frequencies can be selected via the digital inputs as well as also via serial communication interfaces. The fixed frequency is selected, when using digital inputs, using 2 techniques. This will be shown in the following example using the fixed frequency P1001 and digital input 1 (refer to Fig. 3-49). a) Standard methods

→

P0701 = 15 b) BICO methods

→

P0701 = 99, P1020 = 722.0, P1016 = 1

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

167

Page 168

3 Functions

Issue 10/06

P0701 = 15 or P0701 = 99, P1020 = 722.0, P1016 = 1 P0702 = 15 or P0702 = 99, P1021 = 722.1, P1017 = 1 P1016 P1020 1 r0722.0 0

2,3

P1017

0

P1021 DIN2

P1001 1 r0722.1 0

+

2,3

....

0

Fig. 3-49 r1024

+

P1002

...

DIN1

Example for directly selecting FF1 via DIN1 and FF2 via DIN2

Direct selection + ON command When this fixed frequency is selected, the fixed frequencies are also directly selected whereby the selection is combined with the ON command. When this technique is used, a separate ON command is not required. The following is obtained essentially analog to the example shown above: a) Standard method

→

P0701 = 16 b) BICO method

→

P0701 = 99, P1020 = 722.0, P1016 = 2

Binary-coded selection + ON command Using this technique up to 16 fixed frequencies can be selected using 4 control signals. These 4 control signals are either entered via digital inputs or a serial communications interface. The fixed frequencies are indirectly selected using the binary coding (refer to Table 3-23, → e.g. selected using the digital DIN inputs), whereby the selection is combined with the ON command. Table 3-23

Example for binary coding via digital inputs DIN4

DIN3

DIN2

DIN1

0 Hz

FF0

0

0

0

0

P1001

FF1

0

0

0

1

P1002

FF2

0

0

1

0

…

…

…

…

…

…

…

…

…

…

…

…

P1014

FF14

1

1

1

0

P1015

FF15

1

1

1

1

MICROMASTER 440

168

Operating Instructions 6SE6400-5AW00-0BP0

Page 169

Issue 10/06

3 Functions

Contrary to "Direct selection + ON command", the ON command is only active if the setting for the first 4 binary inputs is set to "Binary-coded selection + ON command" or P0701 = P0702 = P0703 = P0704 = 17. The following is obtained analog to the above example: a) Standard method

→

P0701 = 17 b) BICO method

→

P0701 = 99, P1020 = 722.0, P1016 = 3

P0701 = 17 or P0701 = 99, P1020 = 722.0, P1016 = 3 P0702 = 17 or P0702 = 99, P1021 = 722.1, P1017 = 3 P1016 P1020 DIN1

1 r0722.0 0

2,3

P1017

P1021 1 r0722.1

. .. .

DIN2

0

2,3

0 0 0 1

-650.00 ... 650.00 [Hz] P1015.D ( 65.00)

1 1 1 1

. . . Festf requenz 15

Fig. 3-50

...

Festf requenz 1 -650.00 ... 650.00 [Hz] P1001.D ( 0.00)

. . .

CO: IstFestf req. r1024

Example for selecting FF1 via DIN1 and FF2 via DIN2 using the binary-coded method

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

169

Page 170

3 Functions

3.9

Issue 10/06

Motorized potentiometer (MOP) Parameter range: Warnings Faults Function chart number:

P1031 – r1050 FP3100

This function emulates an electromechanical potentiometer to enter setpoints. The motorized potentiometer value is adjusted using the "Raise" and "Lower control signal" which is selected using BICO parameters P1035 and P1036 (refer to Fig. 3-51). The value which has been set is available through connector output r1050 so that it can be further connected and used.

Fig. 3-51

Motorized potentiometer

Selecting via serial interfaces The MOP functionality can be selected via the operator panels (refer to Section 3.2), digital inputs as well as via serial interfaces (refer to the example). Parameterization is also possible directly using BICO parameters P1035 and P1036 as well as also parameters P0700 and P0719. In this case, for a value assigned to P0700, the BICO parameter is appropriately modified.

Example:

Command source via "USS on BOP link" interface a) Standard method

→ b) BICO method

P0700 = 4 →

P1035 = 2032.13 P1036 = 2032.14 :::: (refer to P0700 for a complete list)

MICROMASTER 440

170

Operating Instructions 6SE6400-5AW00-0BP0

Page 171

Issue 10/06

3 Functions

If the motorized potentiometer is to be used as setpoint source, then either parameter P1000 or P0719 should be modified or the BICO parameter r1050 should be connected to the main setpoint P1070 or supplementary setpoint P1075. Contrary to parameter P0719, when parameter P1000 is modified, this implicitly changes BICO parameters P1070, P1075.

Example:

Setpoint via the motorized potentiometer (MOP)

a) Standard method b) BICO method

→

P1000 = 1 →

P1070 = 1050 P1075 = 0 The MOP is configured using the following parameters and has the mode of operation as shown in Table 3-24: ¾ Limits using the minimum frequency P1080 or maximum frequency P1082 ¾ Ramp-up/ramp-down time P1120 or P1121 ¾ Inhibits MOP reversing function P1032 ¾ Saves the MOP setpoint P1031 ¾ MOP setpoint P1040 Table 3-24

Mode of operation of the MOP

Motorized potentiometer Lower Raise

Function

0

0

Setpoint is frozen

0

1

Raise setpoint

1

0

Lower setpoint

1

1

Setpoint is frozen

Selecting via BOP or AOP The following settings / operator actions should be made when selecting the motorized potentiometer using the BOP or AOP: Table 3-25

Selecting the motorized potentiometer

Parameters / keys Command source

P0700

Setpoint source

P1000

BOP

AOP (at the BOP link)

1

4 1

P1035

-

2032.13 (2032.D)

P1036

-

2032.14 (2032.E)

Raise MOP output frequency Lower MOP output frequency

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

171

Page 172

3 Functions

3.10

Issue 10/06

JOG Parameter range: Warnings Faults Function chart number:

P1055 – P1061 A0923 FP5000

The JOG function is used as follows: ¾ To check the functionality of the motor and drive inverter after commissioning has been completed (the first traversing motion, checking the direction of rotation, etc.) ¾ Positioning a drive / a driven load into a specific position ¾ Traversing a drive, e.g. after a program has been interrupted The drive is traversed using this function by entering fixed frequencies P1058, P1059. The JOG mode can be selected either using the operator panel (refer to Section 3.2), digital inputs or also via the serial interfaces (refer to the example). An ON/OFF command is not used to move the drive, but when the "JOG keys" are pressed. These "JOG keys" are selected using the BICO parameters P1055 and P1056. A0923

A0923

"1" DIN

JOG right P1055 (0)

BOP USS BOP link USS COM link CB COM link t "0" "1"

JOG left P1056 t

"0" (0)

f P1082 P1058

Fig. 3-52

P1061

P1060

P1060

P1059 -P1082

P1061 t

JOG counter-clockwise and JOG clockwise

If both JOG keys are simultaneously pressed, then the instantaneous frequency is kept (constant velocity phase) and alarm A0923 is output. When a key is pressed, the drive inverter accelerates the motor to the fixed frequency in the time entered in P1060. This frequency is only exited after the key has been cancelled and the drive then brakes down to 0 Hz in the time entered in P1061. In addition to the explicit parameterization (P1055 and P1056), the JOG functionality is also enabled via parameter P0700 or P0719 (implicit parameterization). In this case, if a value is assigned to P0700, the BICO parameter is appropriately modified.

MICROMASTER 440

172

Operating Instructions 6SE6400-5AW00-0BP0

Page 173

Issue 10/06

3 Functions

Example:

3.11

Command source via "USS on BOP link" interface a) Standard method

→

P0700 = 4 b) BICO method

→

P1055 = 2032.8 P1056 = 2032.9 :::: (refer to P0700 for a complete list)

PID controller (technological controller) Parameter range: Warnings Faults Function chart number: Features: - cycle time:

P2200 P2201 – P2355 FP3300, FP3400, FP5100 8 ms

In addition to the open-loop/closed-loop control of a three-phase motor (standard application for a frequency inverter), MICROMASTER has a technology controller. This can be used to control process quantities – such as pressure or level. Depending on the application, different control structures are required to control process quantities. For MICROMASTER, the following structures have been integrated; these can be selected or de-selected using parameters P2200, P2251 (also refer to Fig. 3-53): a) Variable-speed drive (VSD) b) Closed-loop PID control c) Closed-loop dancer roll control The PID controller – integrated in MICROMASTER – is required for control structures b) and c). The frequency inverter can address many new applications using the higher-level control (closed-loop PID/dancer roll control). The following typical applications can be implemented: ¾ Closed-loop pressure control for extruders ¾ Closed-loop water level control for pump drives ¾ Closed-loop temperature control for fan drives ¾ Closed-loop dancer roll position control for winder applications ¾ And similar control tasks

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

173

Page 174

3 Functions

Issue 10/06

Application

Control structure SUM setpoint

1

3

AFM

Motor control

RFG v Variable speed drive (VSD)

2 p2*

PID setpoint p2

PID feedback

PID RFG

PID −

PID limit

AFM

RFG p2 v2

PID control v2*

SUM setpoint x2*

PID setpoint x2

PID feedback v1

4

Motor control x2

SUM

AFM PID RFG

PID −

Motor control

RFG

PID limit

Dancer control

Setpoint via PID controller

RFG

PID-RFG

1

P2200 = 0:0 2) P2251 = 0

VSD

−

ON: active OFF1/3: active

ON: OFF1/3:

2

P2200 = 1:0 2) P2251 = 0

−

PID control

ON: OFF1/3: active

ON: active OFF1/3: -

3

P2200 = 0:0 1) P2251 = 1

VSD

−

ON: active OFF1/3: active

ON: OFF1/3:

4

P2200 = 1:0 1) P2251 = 1

ON: active OFF1/3: active

ON: active OFF1/3: active

Dancer control

-

-

1) will take change with drive running 2) change only taken when drive stopped

Fig. 3-53

Structure of the technology controller

MICROMASTER 440

174

Operating Instructions 6SE6400-5AW00-0BP0

Page 175

Issue 10/06

3.11.1

3 Functions

Closed-loop PID control MICROMASTER has a technology controller (PID controller, enabled using P2200); this can be used to execute basic, higher-level control functions. The technological setpoints and actual values can be entered via the PID motorized potentiometer (PID-MOP), PID fixed setpoint (PID-FF), analog inputs (ADC, ADC2) or via serial interfaces (USS on BOP link, USS on COM link, CB on COM link) (refer to the example). The appropriate parameterization of the BICO parameter defines which setpoints or actual values are to be used (refer to Fig. 3-54). PID MOP ADC P2254 PID FF

P2253

0

PID SUM

PID RFG

PID PT1

PID −

USS BOP link USS COM link CB COM link

P2264

PID PT1

∆PID

Motor control

1

PIDOutput

&

PID SCL

P2200 P2251

ADC2

Fig. 3-54

Structure of the technological controller (PID controller)

Important parameter settings for the setpoint and actual value sources of the closed-loop PID control: Parameter

Parameter text

P2200

BI: Enable PID controller

P2251

PID mode

P2253

CI: PID setpoint

Setting

Meaning

1.0

PID controller always active

722.x

P2264

CI: PID feedback

0

Digital input x PID as setpoint

2224

Fixed PID setpoint (PID-FF)

2250

PID-MOP

755.0

Analog input 1

2015.1

USS on BOP link

2019.1

USS on COM link

2050.1

CB on COM link

755.0

Analog input 1

755.1

Analog input 2

NOTICE Changes in parameter P2200 take effect only after a fresh ON command.

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

175

Page 176

3 Functions

Issue 10/06

Example:

Permanent PID controller should fulfill the following secondary conditions: PID controller enable and PID setpoint input via PID fixed frequencies and PID actual value via the analog input Parameterization: a) Permanent PID controller enable: P2200 = 1.0 b) Setpoint input via PID-FF: P2253 = 2224 c) Actual value input via analog input ADC: P2264 = 755 d) Setpoint input via PID: P2251 = 0

The supplementary (additional) setpoint is added to the main setpoint (PID-SUM) and the sum is fed to the setpoint filter (PID-PT1) at the setpoint-actual value summation point via the PID ramp-function generator (PID-RFG). The source of the supplementary setpoint (BICO parameter P2254), the ramp-up / ramp-down times of the PID ramp-function generator (P2257, P2258) as well as also the filter time (P2261) can be adapted to the particular application by appropriately parameterizing the corresponding parameters. Similar to the PID setpoint branch, the actual value branch of the technological controller has a filter (PID-PT1) which can be set using parameter P2265. In addition to the smoothing, the actual value can be modified using a scaling unit (PID-SCL). The technological controller can be parameterized as either P, I, PI or PID controller using parameters P2280, P2285 or P2274. P2293

P2291

P2263

PID setpoint

P2280 P2285

0 d dt

+ 1

- r2262 P2274 PID feedback

+

Kp y

Tn x

+ r2273

Motor control r2294

P2292 r2272 P2293

Fig. 3-55

PID controller

For specific applications, the PID output quantity can be limited to defined values. This can be achieved using the fixed limits - P2291 and P2292. In order to prevent the PID controller output exercising large steps at power-on, these PID output limits are ramped-up with ramp time P2293 from 0 to the corresponding value P2291 (upper limit for the PID output) and P2292 (lower limit for the PID output). As soon as these limits have been reached, the dynamic response of the PID controller is no longer limited by this ramp-up/ramp-down time (P2293).

MICROMASTER 440

176

Operating Instructions 6SE6400-5AW00-0BP0