Page 167
Issue 10/06
3.8
3 Functions
Fixed frequencies (FF) Number: Parameter range: Warnings Faults Function chart number:
15 P1001 – P1028 FP3200, FP3210
A setpoint can be entered via the analog inputs, the serial communication interfaces, the JOG function, the motorized potentiometer as well as also using fixed frequencies. The fixed frequencies are defined using parameters P1001 – P1015 and selected via binector inputs P1020 – P1023, P1025, P1026. The effective fixed frequency setpoint is available via connector output r1024 which means that it can be connected further. If this is to be used as setpoint source, then either parameter P1000 or P0719 should be modified or BICO parameter r1024 should be connected to the main setpoint P1070 or supplementary setpoint P1075. Contrary to parameter P0719, when parameter P1000 is modified, this implicitly changes BICO parameters P1070, P1075.
Example:
Fixed frequencies as setpoint source a) Standard method → P1000 = 3 b) BICO method → P1070 = 1024, P1075 = 0
3 methods are available when selecting the fixed frequencies.
Direct selection In this particular mode, the control signal directly selects the fixed frequency. This control signal is entered via the binector inputs. If several fixed frequencies are simultaneously active, then the selected frequencies are added. Table 3-22
Example for direct coding via digital inputs DIN6
DIN5
DIN4
DIN3
DIN2
DIN1
FF0
0 Hz
0
0
0
0
0
0
FF1
P1001
0
0
0
0
0
1
FF2
P1002
0
0
0
0
1
0
FF3
P1003
0
0
0
1
0
0
FF4
P1004
0
0
1
0
0
0
FF5
P1005
0
1
0
0
0
0
FF6
P1006
1
0
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
…
…
FF1+FF2
FF1+FF2+FF3+FF4+FF5+FF6
The fixed frequencies can be selected via the digital inputs as well as also via serial communication interfaces. The fixed frequency is selected, when using digital inputs, using 2 techniques. This will be shown in the following example using the fixed frequency P1001 and digital input 1 (refer to Fig. 3-49). a) Standard methods
→
P0701 = 15 b) BICO methods
→
P0701 = 99, P1020 = 722.0, P1016 = 1
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
167
Page 168
3 Functions
Issue 10/06
P0701 = 15 or P0701 = 99, P1020 = 722.0, P1016 = 1 P0702 = 15 or P0702 = 99, P1021 = 722.1, P1017 = 1 P1016 P1020 1 r0722.0 0
2,3
P1017
0
P1021 DIN2
P1001 1 r0722.1 0
+
2,3
....
0
Fig. 3-49 r1024
+
P1002
...
DIN1
Example for directly selecting FF1 via DIN1 and FF2 via DIN2
Direct selection + ON command When this fixed frequency is selected, the fixed frequencies are also directly selected whereby the selection is combined with the ON command. When this technique is used, a separate ON command is not required. The following is obtained essentially analog to the example shown above: a) Standard method
→
P0701 = 16 b) BICO method
→
P0701 = 99, P1020 = 722.0, P1016 = 2
Binary-coded selection + ON command Using this technique up to 16 fixed frequencies can be selected using 4 control signals. These 4 control signals are either entered via digital inputs or a serial communications interface. The fixed frequencies are indirectly selected using the binary coding (refer to Table 3-23, → e.g. selected using the digital DIN inputs), whereby the selection is combined with the ON command. Table 3-23
Example for binary coding via digital inputs DIN4
DIN3
DIN2
DIN1
0 Hz
FF0
0
0
0
0
P1001
FF1
0
0
0
1
P1002
FF2
0
0
1
0
…
…
…
…
…
…
…
…
…
…
…
…
P1014
FF14
1
1
1
0
P1015
FF15
1
1
1
1
MICROMASTER 440
168
Operating Instructions 6SE6400-5AW00-0BP0
Page 169
Issue 10/06
3 Functions
Contrary to "Direct selection + ON command", the ON command is only active if the setting for the first 4 binary inputs is set to "Binary-coded selection + ON command" or P0701 = P0702 = P0703 = P0704 = 17. The following is obtained analog to the above example: a) Standard method
→
P0701 = 17 b) BICO method
→
P0701 = 99, P1020 = 722.0, P1016 = 3
P0701 = 17 or P0701 = 99, P1020 = 722.0, P1016 = 3 P0702 = 17 or P0702 = 99, P1021 = 722.1, P1017 = 3 P1016 P1020 DIN1
1 r0722.0 0
2,3
P1017
P1021 1 r0722.1
. .. .
DIN2
0
2,3
0 0 0 1
-650.00 ... 650.00 [Hz] P1015.D ( 65.00)
1 1 1 1
. . . Festf requenz 15
Fig. 3-50
...
Festf requenz 1 -650.00 ... 650.00 [Hz] P1001.D ( 0.00)
. . .
CO: IstFestf req. r1024
Example for selecting FF1 via DIN1 and FF2 via DIN2 using the binary-coded method
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
169
Page 170
3 Functions
3.9
Issue 10/06
Motorized potentiometer (MOP) Parameter range: Warnings Faults Function chart number:
P1031 – r1050 FP3100
This function emulates an electromechanical potentiometer to enter setpoints. The motorized potentiometer value is adjusted using the "Raise" and "Lower control signal" which is selected using BICO parameters P1035 and P1036 (refer to Fig. 3-51). The value which has been set is available through connector output r1050 so that it can be further connected and used.
Fig. 3-51
Motorized potentiometer
Selecting via serial interfaces The MOP functionality can be selected via the operator panels (refer to Section 3.2), digital inputs as well as via serial interfaces (refer to the example). Parameterization is also possible directly using BICO parameters P1035 and P1036 as well as also parameters P0700 and P0719. In this case, for a value assigned to P0700, the BICO parameter is appropriately modified.
Example:
Command source via "USS on BOP link" interface a) Standard method
→ b) BICO method
P0700 = 4 →
P1035 = 2032.13 P1036 = 2032.14 :::: (refer to P0700 for a complete list)
MICROMASTER 440
170
Operating Instructions 6SE6400-5AW00-0BP0
Page 171
Issue 10/06
3 Functions
If the motorized potentiometer is to be used as setpoint source, then either parameter P1000 or P0719 should be modified or the BICO parameter r1050 should be connected to the main setpoint P1070 or supplementary setpoint P1075. Contrary to parameter P0719, when parameter P1000 is modified, this implicitly changes BICO parameters P1070, P1075.
Example:
Setpoint via the motorized potentiometer (MOP)
a) Standard method b) BICO method
→
P1000 = 1 →
P1070 = 1050 P1075 = 0 The MOP is configured using the following parameters and has the mode of operation as shown in Table 3-24: ¾ Limits using the minimum frequency P1080 or maximum frequency P1082 ¾ Ramp-up/ramp-down time P1120 or P1121 ¾ Inhibits MOP reversing function P1032 ¾ Saves the MOP setpoint P1031 ¾ MOP setpoint P1040 Table 3-24
Mode of operation of the MOP
Motorized potentiometer Lower Raise
Function
0
0
Setpoint is frozen
0
1
Raise setpoint
1
0
Lower setpoint
1
1
Setpoint is frozen
Selecting via BOP or AOP The following settings / operator actions should be made when selecting the motorized potentiometer using the BOP or AOP: Table 3-25
Selecting the motorized potentiometer
Parameters / keys Command source
P0700
Setpoint source
P1000
BOP
AOP (at the BOP link)
1
4 1
P1035
-
2032.13 (2032.D)
P1036
-
2032.14 (2032.E)
Raise MOP output frequency Lower MOP output frequency
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
171
Page 172
3 Functions
3.10
Issue 10/06
JOG Parameter range: Warnings Faults Function chart number:
P1055 – P1061 A0923 FP5000
The JOG function is used as follows: ¾ To check the functionality of the motor and drive inverter after commissioning has been completed (the first traversing motion, checking the direction of rotation, etc.) ¾ Positioning a drive / a driven load into a specific position ¾ Traversing a drive, e.g. after a program has been interrupted The drive is traversed using this function by entering fixed frequencies P1058, P1059. The JOG mode can be selected either using the operator panel (refer to Section 3.2), digital inputs or also via the serial interfaces (refer to the example). An ON/OFF command is not used to move the drive, but when the "JOG keys" are pressed. These "JOG keys" are selected using the BICO parameters P1055 and P1056. A0923
A0923
"1" DIN
JOG right P1055 (0)
BOP USS BOP link USS COM link CB COM link t "0" "1"
JOG left P1056 t
"0" (0)
f P1082 P1058
Fig. 3-52
P1061
P1060
P1060
P1059 -P1082
P1061 t
JOG counter-clockwise and JOG clockwise
If both JOG keys are simultaneously pressed, then the instantaneous frequency is kept (constant velocity phase) and alarm A0923 is output. When a key is pressed, the drive inverter accelerates the motor to the fixed frequency in the time entered in P1060. This frequency is only exited after the key has been cancelled and the drive then brakes down to 0 Hz in the time entered in P1061. In addition to the explicit parameterization (P1055 and P1056), the JOG functionality is also enabled via parameter P0700 or P0719 (implicit parameterization). In this case, if a value is assigned to P0700, the BICO parameter is appropriately modified.
MICROMASTER 440
172
Operating Instructions 6SE6400-5AW00-0BP0
Page 173
Issue 10/06
3 Functions
Example:
3.11
Command source via "USS on BOP link" interface a) Standard method
→
P0700 = 4 b) BICO method
→
P1055 = 2032.8 P1056 = 2032.9 :::: (refer to P0700 for a complete list)
PID controller (technological controller) Parameter range: Warnings Faults Function chart number: Features: - cycle time:
P2200 P2201 – P2355 FP3300, FP3400, FP5100 8 ms
In addition to the open-loop/closed-loop control of a three-phase motor (standard application for a frequency inverter), MICROMASTER has a technology controller. This can be used to control process quantities – such as pressure or level. Depending on the application, different control structures are required to control process quantities. For MICROMASTER, the following structures have been integrated; these can be selected or de-selected using parameters P2200, P2251 (also refer to Fig. 3-53): a) Variable-speed drive (VSD) b) Closed-loop PID control c) Closed-loop dancer roll control The PID controller – integrated in MICROMASTER – is required for control structures b) and c). The frequency inverter can address many new applications using the higher-level control (closed-loop PID/dancer roll control). The following typical applications can be implemented: ¾ Closed-loop pressure control for extruders ¾ Closed-loop water level control for pump drives ¾ Closed-loop temperature control for fan drives ¾ Closed-loop dancer roll position control for winder applications ¾ And similar control tasks
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
173
Page 174
3 Functions
Issue 10/06
Application
Control structure SUM setpoint
1
3
AFM
Motor control
RFG v Variable speed drive (VSD)
2 p2*
PID setpoint p2
PID feedback
PID RFG
PID −
PID limit
AFM
RFG p2 v2
PID control v2*
SUM setpoint x2*
PID setpoint x2
PID feedback v1
4
Motor control x2
SUM
AFM PID RFG
PID −
Motor control
RFG
PID limit
Dancer control
Setpoint via PID controller
RFG
PID-RFG
1
P2200 = 0:0 2) P2251 = 0
VSD
−
ON: active OFF1/3: active
ON: OFF1/3:
2
P2200 = 1:0 2) P2251 = 0
−
PID control
ON: OFF1/3: active
ON: active OFF1/3: -
3
P2200 = 0:0 1) P2251 = 1
VSD
−
ON: active OFF1/3: active
ON: OFF1/3:
4
P2200 = 1:0 1) P2251 = 1
ON: active OFF1/3: active
ON: active OFF1/3: active
Dancer control
-
-
1) will take change with drive running 2) change only taken when drive stopped
Fig. 3-53
Structure of the technology controller
MICROMASTER 440
174
Operating Instructions 6SE6400-5AW00-0BP0
Page 175
Issue 10/06
3.11.1
3 Functions
Closed-loop PID control MICROMASTER has a technology controller (PID controller, enabled using P2200); this can be used to execute basic, higher-level control functions. The technological setpoints and actual values can be entered via the PID motorized potentiometer (PID-MOP), PID fixed setpoint (PID-FF), analog inputs (ADC, ADC2) or via serial interfaces (USS on BOP link, USS on COM link, CB on COM link) (refer to the example). The appropriate parameterization of the BICO parameter defines which setpoints or actual values are to be used (refer to Fig. 3-54). PID MOP ADC P2254 PID FF
P2253
0
PID SUM
PID RFG
PID PT1
PID −
USS BOP link USS COM link CB COM link
P2264
PID PT1
∆PID
Motor control
1
PIDOutput
&
PID SCL
P2200 P2251
ADC2
Fig. 3-54
Structure of the technological controller (PID controller)
Important parameter settings for the setpoint and actual value sources of the closed-loop PID control: Parameter
Parameter text
P2200
BI: Enable PID controller
P2251
PID mode
P2253
CI: PID setpoint
Setting
Meaning
1.0
PID controller always active
722.x
P2264
CI: PID feedback
0
Digital input x PID as setpoint
2224
Fixed PID setpoint (PID-FF)
2250
PID-MOP
755.0
Analog input 1
2015.1
USS on BOP link
2019.1
USS on COM link
2050.1
CB on COM link
755.0
Analog input 1
755.1
Analog input 2
NOTICE Changes in parameter P2200 take effect only after a fresh ON command.
MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0
175
Page 176
3 Functions
Issue 10/06
Example:
Permanent PID controller should fulfill the following secondary conditions: PID controller enable and PID setpoint input via PID fixed frequencies and PID actual value via the analog input Parameterization: a) Permanent PID controller enable: P2200 = 1.0 b) Setpoint input via PID-FF: P2253 = 2224 c) Actual value input via analog input ADC: P2264 = 755 d) Setpoint input via PID: P2251 = 0
The supplementary (additional) setpoint is added to the main setpoint (PID-SUM) and the sum is fed to the setpoint filter (PID-PT1) at the setpoint-actual value summation point via the PID ramp-function generator (PID-RFG). The source of the supplementary setpoint (BICO parameter P2254), the ramp-up / ramp-down times of the PID ramp-function generator (P2257, P2258) as well as also the filter time (P2261) can be adapted to the particular application by appropriately parameterizing the corresponding parameters. Similar to the PID setpoint branch, the actual value branch of the technological controller has a filter (PID-PT1) which can be set using parameter P2265. In addition to the smoothing, the actual value can be modified using a scaling unit (PID-SCL). The technological controller can be parameterized as either P, I, PI or PID controller using parameters P2280, P2285 or P2274. P2293
P2291
P2263
PID setpoint
P2280 P2285
0 d dt
+ 1
- r2262 P2274 PID feedback
+
Kp y
Tn x
+ r2273
Motor control r2294
P2292 r2272 P2293
Fig. 3-55
PID controller
For specific applications, the PID output quantity can be limited to defined values. This can be achieved using the fixed limits - P2291 and P2292. In order to prevent the PID controller output exercising large steps at power-on, these PID output limits are ramped-up with ramp time P2293 from 0 to the corresponding value P2291 (upper limit for the PID output) and P2292 (lower limit for the PID output). As soon as these limits have been reached, the dynamic response of the PID controller is no longer limited by this ramp-up/ramp-down time (P2293).
MICROMASTER 440
176