The text of a manual · part 21 of 35

MICROMASTER 440 0.12 kW - 250 kW Operating Instructions: 3 Functions, pages 177 to 186

Pages 177 to 186 of 312, from MICROMASTER 440 0.12 kW - 250 kW Operating Instructions

The original document is the PDF (8.9 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Siemens 6SE6440-2UD13-7AA1

Page 177

Issue 10/06

3.11.1.1

3 Functions

PID motorized potentiometer (PID-MOP) Parameter range: Warnings Faults Function chart number:

P2231 – r2250 FP3400

The PID controller has a PID motorized potentiometer which can be separately adjusted. The functionality is identical with the motorized potentiometer (refer to Section 3.9), whereby the PID parameters are emulated in the range from P2231 – r2250 (refer to the comparison → Table 3-26). Table 3-26

Correspondence between the parameters

PID motorized potentiometer P2231[3]

Motorized potentiometer

Setpoint memory of PID-MOP

P1031[3]

P2232

Inhibit rev. direct. of PID-MOP

P1032

Inhibit reverse direction of MOP

P2235[3]

BI: Enable PID-MOP (UP-CMD)

P1035[3]

BI: Enable MOP (UP command)

P2236[3]

BI: Enable PID-MOP (DOWNCMD)

P1036[3]

BI: Enable MOP (DOWN command)

P2240[3]

Setpoint of PID-MOP

P1040[3]

Setpoint of the MOP r2250

CO: Output setpoint of PID-MOP r1050

CO: Act. output freq. of the MOP

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

Setpoint memory of the MOP

177

Page 178

3 Functions

3.11.1.2

Issue 10/06

PID fixed setpoint (PID-FF) Number: Parameter range: Warnings Faults Function chart number:

15 P2201 – P2228 FP3300, FP3310

Analog to the fixed frequencies (refer to Section 3.7), the PID controller has separate programmable PID fixed setpoints. The values are defined using parameters P2201 – P2215 and are selected using binector inputs P2220 – P2223, P2225, P2226. The selected PID fixed setpoint is available via connector output r2224 where it can be further processed (e.g. as PID main setpoint → P2253 = 2224). 3 methods are available to select the PID fixed setpoints, analog to the fixed frequencies (Section 3.7): ¾ Direct selection ¾ Direct selection + ON command ¾ Binary-coded selection + ON command The methods are selected using parameters P2216 – P2219, P2225, P2227. P0701 = 15 or P0701 = 99, P2220 = 722.0, P2216 = 1

P2216 P2220 DIN1

1 r0722.0

....

0

....

2,3

0 P2201

.... Fig. 3-56

Example to directly select the PID fixed frequency of fixed frequency 1 via DIN1

MICROMASTER 440

178 r2224

Operating Instructions 6SE6400-5AW00-0BP0

Page 179

Issue 10/06

3.11.1.3

3 Functions

PID dancer roll control For various continuous production processes, e.g. in the paper and pulp industry, or in the manufacture of cables, it is necessary to control (closed-loop) the velocity of stations along the production process so that the continuous material web is not subject to any inadmissible tension levels. It is also important that no folds or creases are formed. For applications such as these, it is practical to provide a type of material buffer in the form of a loop with a defined tension. This provides a decoupling between the individual drive locations. This loop represents the difference between the material fed-in and that fed-out and therefore indicates the process quality. Using the PID dancer roll control, with MICROMASTER 440 it is possible to ensure that continuous material webs have a constant tension.

Structure

Application v2 v1 x2 v2*

SUM setpoint x2*

PID setpoint x2

PID feedback

Fig. 3-57

AFM PID RFG

PID −

RFG

Motor control

PID limit

PID dancer roll control

The velocity v1 is assumed to be an independent disturbance; the input velocity v2 should be controlled using drive rolls A2 so that the length x2 of the loop corresponds, as far as possible, to the setpoint. The structure and important parameters for the PID dancer roll control are listed in Fig. 3-58 and Table 3-27.

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

179

Page 180

3 Functions

Issue 10/06

P2253

PID PT1

USS COM link CB COM link

P2264

ADC2

P2200

P2280

PID RFG

PID − ∆PID

PIDOutput

&

PID PT1

PID SCL

P2265

P2271

P2251 =1

Structure of the closed-loop PID-dancer roll control

Table 3-27

Important parameters for the PID dancer roll control

P1070

Parameter text CI: Main setpoint

Setting

Meaning

1024

Fixed setpoint (FF)

1050

MOP

755.0

Analog input 1

2015.1

USS on BOP link

2019.1

USS on COM link

2050.1 P2200

BI: Enable PID controller

P2251

PID mode

P2253

CI: PID setpoint

1.0 722.x

P2264

CI: PID feedback

1

CB on COM link PID controller always active Digital input x PID as trim

1024

Fixed setpoint (FF)

1050

MOP

755.0

Analog input 1

2015.1

USS on BOP link

2019.1

USS on COM link

2050.1

CB on COM link

755.0

Analog input 1

755.1

Analog input 2

MICROMASTER 440

180

Motor control

1

Fig. 3-58

Parameter

0

0 PID SUM

P2270

USS BOP link

P2254

RFG

P2269

FF

P2257

ADC

AFM

P2261

SUM

P2258

P1075

P2285

P1070 MOP

P1121

P1120

NOTE When selecting the closed-loop dancer roll control it should be noted that neither PID-MOP nor PID-FF should be used - but instead the MOP (motorized potentiometer, refer to Section 3.9) or the FF (fixed frequencies, refer to Section 3.7).

Operating Instructions 6SE6400-5AW00-0BP0

Page 181

Issue 10/06

3.12

3 Functions

Setpoint channel The setpoint channel (refer to Fig. 3-59) forms the coupling element between the setpoint source and the closed-loop motor control. MICROMASTER has a special characteristic which allows the setpoint to be entered simultaneously from two setpoint sources. The generation and subsequent modification (influencing the direction, suppression frequency, up/down ramp) of the complete setpoint is carried-out in the setpoint channel.

MOP ADC Additonal setpoint

FF USS BOP link USS COM link CB COM link

SUM

AFM

Limit

RFG

Motor control

Main setpoint

ADC2 Setpoint source

Fig. 3-59

3.12.1

Setpoint channel

Motor control

Setpoint channel

Summation and modification of the frequency setpoint (AFM) Parameter range: Warnings Fault Function chart number:

P1070 – r1114 FP5000, FP5200

For applications where the control quantities are generated from central control systems, fine tuning is often required locally on-site (correction quantity). For MICROMASTER, this can be very elegantly realized using the summation point where the main and supplementary (additional) setpoint are added in the setpoint channel. In this case, both quantities are simultaneously read-in via two separate or one setpoint source and summed in the setpoint channel. Depending on external circumstances, the supplementary setpoint can be dynamically disconnected or switched-in to the summation point (refer to Fig. 3-60). This functionality can be used to advantage, especially for discontinuous processes.

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

181

Page 182

3 Functions

Issue 10/06

CI: Main setpoint P1070.C (755:0) CI: Main setp scal P1071.C r1078

(1:0) +

AFM

Limit

RFG

+

Motor control

BI: Disab.add.setp 0

P1074.C

1

(0:0) CI: Add. setp.scal P1076.C (1:0) CI: Add. setpoint P1075.C (0:0)

Fig. 3-60

Summation

MICROMASTER has the following possibilities to select the setpoint source: 1. P1000 – selecting the frequency setpoint source 2. P0719 – selecting the command / setpoint source 3. BICO parameterization - P1070 CI: Main setpoint - P1075 CI: Additional setpoint Further, the main setpoint as well as the supplementary (additional) setpoint can be scaled independently of one another. In this case, for example, a user can simply implement an override function using the appropriate parameterization. A scan sequence is generally associated with a forwards and a backwards motion. When selecting the reversing functionality, after reaching the end position, a direction of rotation reversal can be initiated in the setpoint channel (refer to Fig. 3-61). On the other hand, if it is to be prevented that a direction of rotation reversal or a negative frequency setpoint is to be entered via the setpoint channel, then this can be inhibited using BICO parameter P1110. r1078

SUM

-1

P1113

P1110 P1091

0

0

1

1

... P1094 P1080 P1082 Skip

Limit

RFG

P1101

Fig. 3-61

Modifying the frequency setpoint

Driven machines can have one or several resonance points in the range from 0 Hz up to the reference frequency. These resonance points result in oscillations which, under worst case conditions, can damage the driven load. Using suppression frequencies, MICROMASTER allows these resonant frequencies to be passed through as quickly as possible. This means that the suppression frequencies increase the availability of the driven load over the long term.

MICROMASTER 440

182

Operating Instructions 6SE6400-5AW00-0BP0

Page 183

Issue 10/06

3.12.2

3 Functions

Ramp-function generator (RFG) Parameter range:

P1120, P1121 r1119, r1170 P1130 – P1142 FP5000, FP5300

Warnings Faults Function chart number:

The ramp-function generator is used to limit the acceleration when the setpoint changes according to a step function. This therefore helps to reduce the stressing on the mechanical system of the machine. An acceleration ramp and a braking ramp can be set independently of one another using the ramp-up time P1120 and the ramp-down time P1121. This allows a controlled transition when the setpoint is changed (refer to Fig. 3-62). f

Without rounding fmax f2 f1

P1120 t

P1121 f fmax f2

With rounding f1

P1130 for

P1131 tup tdown

P1133 t

1 f 2 - f1 ⋅ P1120 ≥ (P1130 + P1131) P1082 2 t up = for

P1132

1 (P1130 + P1131) + f 2 f 1 ⋅ P1120 P1082 2

1 f 2 - f1 ⋅ P1121 ≥ (P1132 + P1133) P1082 2 t down =

1 f -f (P1132 + P1133) + 2 1 ⋅ P1121 2 P1082

Where the rounding times are increased to be greater than the ramp period then the ramp period is determined by the following equations:

(

)

⎛ 2 ⋅ (f 2 − f 1) ⋅ P1120 ⋅ P11302 ⎞ ⎛ ⎟ ⋅ ⎜1 + P1131 ⎞⎟ tup = ⎜⎜ ⎟ ⎜⎝ P1130 ⎟⎠ P 1130 P 1131 ( ) ⋅ + f max ⎝ ⎠

(

)

⎛ 2 ⋅ (f 2 − f 1) ⋅ P1120 ⋅ P11322 ⎞ ⎛ P1133 ⎞ ⎟ ⋅ ⎜1 + t down = ⎜⎜ ⎟⎟ ⎟ ⎜ ⎝ f max ⋅ (P1132 + P1133 ) ⎠ ⎝ P1132 ⎠

Fig. 3-62

Ramp-function generator

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

183

Page 184

3 Functions

Issue 10/06

In order to avoid torque surges at the transitions (constant velocity phase ←→ accelerating / braking phase), additional rounding-off times P1130 – P1133 can be programmed. This is especially important for applications (e.g. transporting/pumping liquids or for cranes) which require an especially "soft", jerkfree acceleration and braking. If the OFF1 command is initiated while the drive is accelerating, then rounding-off can be activated or de-activated using parameter P1134 (refer to Fig. 3-63). These rounding-off times are defined using parameters P1132 and P1133. P1132 > 0 P1133 > 0 f Setpoint reached f Set

Setpoint not reached

P1134 = 0 t P1132

P1133

P1132

P1133 f

Setpoint reached f Set Setpoint not reached

P1134 = 1 t P1132

P1133

P1133

ON OFF1

Fig. 3-63 t

Rounding off after an OFF1 command

In addition to the rounding-off times, the ramp-function generator can be influenced using external signals. The ramp-function generator provides the following functionality using BICO parameters P1140, P1141 and P1142 (refer to Table 3-28).

MICROMASTER 440

184

Operating Instructions 6SE6400-5AW00-0BP0

Page 185

Issue 10/06

3 Functions

Table 3-28

BICO parameters for ramp-function generator Parameter

Description

P1140

BI: RFG enable

The ramp-function generator output is set to 0 if the binary signal = 0.

P1141

BI: RFG start

The ramp-function generator output keeps its actual value if the binary signal = 0.

P1142

BI: RFG enable setpoint

If the binary signal = 0, then the ramp-function generator input is set to 0 and the output is reduced to 0 via the ramp-function generator ramp.

The ramp-function generator itself is enabled after the pulses have been enabled (inverter enable) and after the excitation time has expired (P0346). After limiting to the maximum speeds for the positive and negative directions of rotation (P1082, P1082 or 0 Hz for the direction of rotation inhibit) the setpoint speed for the control is obtained (r1170).

NOTE The maximum frequency of the setpoint channel is set using parameter P1080. In V/f mode the maximum frequency is 650 Hz. In vector mode the maximum frequency it is limited to 200 Hz (r1084).

MICROMASTER 440 Operating Instructions 6SE6400-5AW00-0BP0

185

Page 186

3 Functions

3.12.3

Issue 10/06

OFF/braking functions Parameter range:

Warnings Faults Function chart number:

P1121, P1135, P2167, P2168 P0840 – P0849 r0052 bit 02 -

The drive inverter and the user must respond to an extremely wide range of situations and stop the drive. In this case, both requirements relating to operations as well as drive inverter protective functions (e.g. electrical and thermal overload) and man-machine protective functions have to be taken into account. As a result of the different OFF/braking functions (OFF1, OFF2, OFF3) MICROMASTER can flexibly respond to the requirements mentioned above.

OFF1 The OFF1 command is closely coupled to the ON command. When the ON command is withdrawn, then OFF1 is directly activated. The drive is braked by OFF1 with the ramp-down time P1121. If the output frequency falls below the parameter value P2167 and if the time in P2168 has expired, then the inverter pulses are cancelled. f act P1082 fmax OFF1 f2

P2167 t P2168 r0052 Bit02 tdown,AUS1 P1121

Operation Pulse ncellation

Fig. 3-64 t t down, AUS1 = P1121 ⋅

OFF1

MICROMASTER 440

186 f2 P1082

Operating Instructions 6SE6400-5AW00-0BP0