For the Siemens EM-300-RS
Page 21
Wiring
2.3.2
Wiring the Power Connectors
Pinout The diagram and the table below indicate the pinout of the power connector and the two power sockets on a motor starter with a 24 V DC braking contact.
2
1
6
7
7
4
5
4
Pinout
6
3
5
1
8
8
2
3
3
2
1
5 8
4 6
7
Plug X1
Socket X2
Connecting load supply voltage
Connecting load with brake
Looping through load supply voltage and brake voltage
1, Phase 1, 2
Phase 2, Phase 2
3, Phase 3, 4
GND
GND
+ 24 V DC
5
+ 24 V DC
+
GND
6
Phase 1, Phase 3
7, Phase 2, 8
Phase 3, Phase 1 e
PE
PE
PE
SIMATIC - EM 300 Motor Starters GWA-4NEB 640070302-05
Socket X3
2-9
Page 22
Wiring
Power connectors The power connectors of a motor starter EM 300 with a 24 V DC braking contact consist of the following components: Power socket • for connecting load supply voltage
Power connector • for connecting the load with a brake • for looping through the load supply voltage and the braking voltage connector shell connector shell jacks contact pins socket insert pin insert
Installing and wiring power connectors Install the power connectors of a motor starter with a 24 V DC braking contact as follows. Please note the wiring rules described in Chapter 2.1 Step
Procedure Socket for X2
Connector for X2
Connector for X3
1
Feed the cable through the gland, the appropriately-sized sealing ring supplied and the connector shell.
2
Fasten the jacks to the cores
Fasten the contact pins to the cores
• • •
• • • for phases 1 to 3 for the brake for PE for phases 1 to 3 for the brake for PE
3
Press the jacks into the socket insert until they snap into place.
Press the contact pins into the pin insert until they snap into place.
4
Withdraw the cable sufficiently to be able to screw the socket or pin insert tightly inside the connector shell with the enclosed screws.
5
Screw the gland tight.
SIMATIC - EM 300 Motor Starters
2-10
GWA-4NEB 640070302-05
Page 23
Wiring
2.3.3
Electrical Design
Suggested circuit The following diagram suggests one way of controlling the motor with a 24 V DC brake via an electronic compact starter EM 300 EDS/ERS.
L1 L2 L3 K1
+24 V DC M
A1
A2
Galvanic isolation
6
2
8
X3 8 2 6
1
7
3
4
X1 4
5
4
5
5
X2
1 W 1 V 1 U
M 3
P E
Motor with 24 V DC brake
Galvanic isolation An external isolating contactor must be fitted to ensure galvanic isolation from the power supply system!
SIMATIC - EM 300 Motor Starters GWA-4NEB 640070302-05
2-11
Page 24
Wiring
2.4
Motor Starters EM 300 with a 400 V AC resp. 500 V DC Braking Contact
2.4.1
Making up Connecting Cables
Accessories If you want to make up your own connecting cable for motor starters EM 300 with a 400 V AC resp. 500 V DC braking contact, you will need one crimping tool for contact pins/jacks (alternatively, they can be soldered) and the following components. You need ... For connecting load supply voltage
X1
For connecting load with brake 400 V AC resp. 500 V DC
X2
For looping through load supply voltage
One flexible 4-core copper cable 2.5 mm2 / 4.0 mm2 (3 conductors + PE)
One flexible 6-core copper cable 1.5 mm2 / 2.5 mm2 (3 conductors + PE + 2 conductors)
One flexible 4-core copper cable 2.5 mm2 / 4.0 mm2 (3 conductors + PE)
One set of connectors
One set of connectors
One set of connectors
• •
2.5 mm2: 3RK1902-0CA00 4.0 mm2: 3RK1902-0CB00, • •
1.5 mm2: 3RK1902-0CE00 2.5 mm2: 3RK1902-0CC00
• •
X3
2.5 mm2: 3RK1902-0CC00 4.0 mm2: 3RK1902-0CD00 resp.
resp.
one motor connecting cable with plug, 4 x 1.5 mm2 one power connecting cable with plug and socket
• • •
•
3 m: 3 RK1 902-0CN00 5 m: 3 RK1 902-0CR00 10 m: 3 RK1 902-0CS00
•
6 x 2.5 mm2, 0.12 m: 3 RK1 902-0CH00 4 x 4.0 mm2, 0.15 m: 3 RK1 902-0CG00
SIMATIC - EM 300 Motor Starters
2-12
GWA-4NEB 640070302-05
Page 25
Wiring
2.4.2
Wiring the Power Connectors
Pinout The diagram and the table below indicate the pinout of the power connector and the two power sockets on a motor starter EM 300 with a braking contact 400 V AC resp. 500 V DC.
1
2
Pinout
7
7
4
5
4 6
6
3
5
1
8
Plug X1
8
2
3
3
2
1
5 8
Socket X2
4 6
7
Socket X3
Connecting load supply voltage
Connecting load with brake
Looping through load supply voltage
1, Phase 1, 2
Phase 2, Phase 2
3, Phase 3, 4, L1 / +OUT, 5, L3 / +IN, 6
Phase 1, Phase 3
7, Phase 2, 8
Phase 3, Phase 1 e
PE
PE
PE
SIMATIC - EM 300 Motor Starters GWA-4NEB 640070302-05
2-13
Page 26
Wiring
Installing and wiring power connectors The power connectors of a motor starter EM 300 with a braking contact 400 V AC resp. 500 V DC consist of the following components: Power socket • for connecting load supply voltage
Power connector • for connecting the load with a brake • for looping through the load supply voltage connector shell connector shell jacks contact pins socket insert pin insert
Installing and wiring power connectors Install the power connectors of a motor starter with a braking contact 400 V AC resp. 500 V DC as follows. Please note the wiring rules described in Chapter 2.1. Step
Procedure Socket for X1
Connector for X2
Connector for X3
1
Feed the cable through the gland, the appropriately-sized sealing ring supplied and the connector shell.
2
Fasten the jacks to the cores • • for phases 1 to 3 for PE
Fasten the contact pins to the cores
Fasten the contact pins to the cores
• • •
• • for phases 1 to 3 for the brake for PE for phases 1 to 3 for PE
3
Press the jacks into the socket insert until they snap into place.
Press the contact pins into the pin insert until they snap into place.
4
Withdraw the cable sufficiently to be able to screw the socket or pin insert tightly inside the connector shell with the enclosed screws.
5
Screw the gland tight.
SIMATIC - EM 300 Motor Starters
2-14
GWA-4NEB 640070302-05
Page 27
Wiring
2.4.3
Electrical Design
Suggested circuit 400 V AC brake The following diagram shows you a way of controlling a pole-changing motor for two directions with a 400 V AC brake by two electronic motor starters EM 300 EDS/ERS. L1 L2 L3 K1 A1
Galvanic isolation
X1
A2 6
2
8
8
1
7
3
4
2
X3
X1
X3
6
5
6
2
8
1
7
3
8
2
6
X2
X2
1 W
2 U
1 V 1 U
M 3
2 V 2 W
P E
Motor with separate windings and brake 400 V AC
Galvanic isolation An external isolating contactor must be fitted to ensure galvanic isolation from the power supply system!
SIMATIC - EM 300 Motor Starters GWA-4NEB 640070302-05
2-15
Page 28
Wiring
Suggested circuit 500 V DC brake The following diagram shows you a way of controlling a motor with a 500 V DC brake by one electronic motor startermotor starter EM 300.
L1 L2 L3 K1 A1
X1
A2
Galvanic isolation
X3
6
2
8
8
2 6
1
7
3
5
4
X2 + -
1 W
1 V 1 U
M 3
P E
Motor with brake 500 V DC
Galvanic isolation An external isolating contactor must be fitted to ensure galvanic isolation from the power supply system!
SIMATIC - EM 300 Motor Starters
2-16
GWA-4NEB 640070302-05
Page 29
3
Commissioning
Section
Subject
Page
3.1
Motor Starters EM 300 DS and EM 300 RS
3-2
3.1.1
Commissioning
3-2
3.1.2
Operation
3-3
3.1.3
Diagnostics
3-4
3.2
Motor Starters EM 300 EDS and EM 300 ERS
3-6
3.2.1
Commissioning
3-6
3.2.2
Operation
3-8
3.2.3
Diagnostics
3-10
SIMATIC - EM 300 Motor Starters GWA-4NEB 640070302-05
3-1
Page 30
Commissioning
3.1
Motor Starters EM 300 DS and EM 300 RS
3.1.1
Commissioning
Set current Ie Before you commission the motor starter, you must set the current Ie for tripping the overload release. Step
Procedure
1
Open the transparent cover in the top section of the motor starter.
2
Set the current Ie on the circuit-breaker scale with a screw-driver (see figure on page 1-2).
External short-circuit protection If the short-circuit current at the point at which the motor starter is installed is greater than the rated ultimate short-circuit breaking capacity of the circuitbreaker (see table), you must provide external short-circuit protection (fuse or circuit-breaker; see Catalog). Ue
Icu max
400 V AC
50 kA
440 V AC
10 kA
500 V AC
3 kA
Overload release test You can test the overload release function. Step
Procedure
1
Open the transparent cover in the top section of the motor starter.
2
Reset the toggle switch from 0 to 1.
3
Insert a screwdriver in the test opening (see figure on page 1-2) and press it over to the left. The overload release function is working if the toggle switch is switched back from 1 to 0.
Reversing starter EM 300 RS When switching over from right to left or back again, a stop interval of more than 200 milliseconds must be observed. This interval has to be set via the user program.
SIMATIC - EM 300 Motor Starters
3-2
GWA-4NEB 640070302-05