Manual · Siemens
SIMATIC EM 300 Motor Starters Manual
Manual74 pagesPDF 917 KB
Manual for the Siemens SIMATIC EM 300 DS, RS, EDS and ERS motor starters used on the ET 200X distributed I/O device.
Covers · 1 model
The models it covers
Summary
What is in it
The manual for the Siemens SIMATIC EM 300 motor starters (EM 300 DS, RS, EDS and ERS), expansion modules for the ET 200X distributed I/O device. It explains what each starter is, wiring with and without a braking contact, commissioning, operation and diagnostics, the hand-held controller, technical specifications and SIGUARD Safety Integrated circuits, with order numbers, dimension drawings and a selection help in the appendices.
Its parts
- Product Overview
- Wiring
- Commissioning
- Hand-held Controller
- Technical Specifications
- SIGUARD Safety Integrated
- Order Numbers
- Dimension Drawings
- Configuration Frame
- Selection Help
From the manual
Key facts from this manual
Each line names its page in the PDF.
Siemens SIMATIC manual (edition 03/2010) for the EM 300 motor starters that plug onto the ET 200X distributed I/O device as expansion modules: the electromechanical EM 300 DS and EM 300 RS and the electronic EM 300 EDS and EM 300 ERS. It covers wiring, commissioning, diagnostics, the hand-held controller, technical specifications, order numbers and dimension drawings. A reader can use it to set up, wire and order parts for these starters.
- Type
- EM 300 RS: electromechanical reversing motor starter, an expansion module for the ET 200X; up to six per basic module p. 8, 48
- Motor rating
- EM 300 DS/RS: three-phase loads up to 5.5 kW at 400 V AC, 12 A rated operating current p. 8, 51
- Circuit-breaker
- EM 300 DS/RS: class 10, 12 A max.; setting range by version, from 0.14-0.20 A up to 9.00-12.0 A p. 51, 61
- Short-circuit capacity
- EM 300 DS/RS: Icu max. 50 kA at 400 V AC, 10 kA at 440 V AC, 3 kA at 500 V AC p. 30
- Order numbers
- EM 300 RS: 3RK1 300-0BS01-1AA0 (0.14-0.20 A) to 3RK1 300-1KS01-1AA0 (9.00-12.0 A); ending 1AA1 with 24 V DC braking contact, 1AA4 with 500 V DC p. 61
- Braking contact
- EM 300 DS/RS option: 24 V DC, max. 3 A (DC-13, brake coil up to 70 W), or 500 V DC, max. 0.2 A p. 8, 50
- Contactor
- EM 300 DS/RS: AC-2, AC-3; up to 80 starts per hour (0.1 s starting time, 50% ON period); mechanical life > 10 Mill. cycles p. 51
- Electronics supply
- 24 V DC (1L+) for electronics and sensors, reverse polarity and short-circuit protected p. 49
- Main circuit
- Rated insulation voltage 690 V AC; 50/60 Hz p. 49
- Dimensions
- 120 x 265 x 134 mm (W x H x D) p. 48
- Enclosure
- IP 65 when the starter is completely closed p. 48
- Temperature
- 0 to 55 °C operating (100% rated current below 40 °C, 87% from 40 to 55 °C); -40 to +70 °C shipping and storage p. 53, 54
- Hand-held controller
- 3RK1902-0AM00, with 0.5 m connecting cable p. 62
- Motor cables
- 4 x 1.5 mm2 with plug: 3 m 3RK1902-0CM00, 5 m 3RK1902-0CP00, 10 m 3RK1902-0CQ00; 6 x 1.5 mm2: 3 m 3RK1902-0CN00, 5 m 3RK1902-0CR00, 10 m 3RK1902-0CS00 p. 62
What this manual walks you through
- Choosing motor cable cross-sections and wiring the power connectors p. 14, 15
- Making up connecting cables for starters without a braking contact p. 16
- Setting the overload trip current Ie on an EM 300 DS or RS p. 30
- Testing the overload release p. 30
- Resetting after an overload trip and locking the starter off p. 31
- Reading the LEDs and the input and output signals p. 32, 33
- Technical specifications, braking circuit and environment conditions p. 48, 49, 50, 51, 52, 53, 54
- Order numbers of starters and accessories p. 59, 60, 61, 62
- Which ET 200X manual holds which topic p. 10, 11, 12
Good to know
- On an EM 300 RS, a stop interval of more than 200 ms is needed when reversing; the user program sets it. p. 30
- Where the short-circuit current exceeds the breaker's rating, external protection (fuse or circuit-breaker) is required. p. 30
- The braking contact is switched over the bus apart from the main circuit, so the user program must prevent dangerous states. p. 33
- Seal unused connections with screw caps (3RK1902-0CK00 single, 3RK1902-0CJ00 pack of 10) to keep IP 65. p. 15, 62
- The 24 V DC brake supply must come from a power supply unit with safe electrical isolation (PELV). p. 15
Questions this manual answers
What is a Siemens EM 300 RS?
An electromechanical reversing motor starter that fits the ET 200X distributed I/O device as an expansion module, for three-phase loads up to 5.5 kW at 400 V AC. p. 8
How do I set the trip current on an EM 300 RS?
Open the transparent cover in the top section and set the current Ie on the circuit-breaker scale with a screwdriver. p. 30
How long must an EM 300 RS wait before reversing?
More than 200 milliseconds between directions, set in the user program. p. 30
What do the LEDs on an EM 300 RS mean?
DC 24 V steady green means auxiliary power is applied (off means missing); STATE steady green means a control signal is applied from the bus or hand-held controller. p. 32
What is the order number of a 9 to 12 A EM 300 RS?
3RK1 300-1KS01-1AA0 for the basic version; 1AA1 replaces 1AA0 for a 24 V DC braking contact and 1AA4 for 500 V DC. p. 61
Contents
Chapters and sections
Each line opens the PDF at its page.
The whole text · 8 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
The file