Page 31
Commissioning
3.1.2
Operation
If overload release trips After an overload release trip during operation you must reset the circuitbreaker. Step
Procedure
1
Open the transparent cover in the top section of the motor starter.
2
Reset toggle switch from 0 to 1.
3
Check whether any switching contacts have been damaged as a result of a short-circuit.
Disconnecting a load from the power system You can disconnect a load from the electrical power system by resetting the toggle switch on the circuit-breaker from 1 to 0.
Safeguard against accidental opening/unauthorized switching on You can seal the transparent cover of the motor starter in order to safeguard it against accidental opening, for example in order to prevent the overload release current from being altered inadvertently. You can prevent the motor starter from being switched on by unauthorized persons, by fitting the actuating element of the circuit-breaker with a safety lock.
SIMATIC - EM 300 Motor Starters GWA-4NEB 640070302-05
3-3
Page 32
Commissioning
3.1.3
Diagnostics
Diagnosis via the LEDs During operation, the LEDs on the motor starter EM 300 DS and EM 300 RS indicate the following statuses: LED
Indication
DC 24 V
STATE
Status
Steady green light
Auxiliary power applied
Off
Auxiliary power missing
Steady green light
Control signal applied (bus / hand-held controller)
Diagnosis via the user program You can evaluate the input and output signals in your application. Please note that • "DI2" is not driven by the direct starter EM 300 DS, i. e. "DI2" is always 0. • "DO2" is only driven on versions with a braking contact.
Input signals DI0
Manual/automatic mode
DI1
Feedback from contactor*
0
Manual
0
Clockwise rotation on
1
Automatic
1
Clockwise rotation off
DI2
Feedback from contactor*
DI3
Circuit-breaker
0
Anticlockwise rotation on
0
Off
1
Anticlockwise rotation off
1
On
* The feedback signal for the protective circuit-breaker position is by means of positive-action NC contacts. That is why the signal level is inverted here.
SIMATIC - EM 300 Motor Starters
3-4
GWA-4NEB 640070302-05
Page 33
Commissioning
Output signals DI0
Signal to contactor
DI1
Signal to contactor
0
Clockwise rotation off
0
Anticlockwise rotation off
1
Clockwise rotation on
1
Anticlockwise rotation on
DI2
Braking contact, 0
Open braking contact
1
Close braking contact
Caution ! The braking contact is driven via the bus independently of the main current circuit. This allows non-synchronous switching of the motor and brake. Make sure that no dangerous system states can occur (e. g. unwanted coasting or blocking of the motor) by means of the user program. This also applies to local disconnections (e. g. triggered by an overload). You can use input signal DI3 to check the device state.
SIMATIC - EM 300 Motor Starters GWA-4NEB 640070302-05
3-5
Page 34
Commissioning
3.2
Motor Starters EM 300 EDS and EM 300 ERS
3.2.1
Commissioning
Set current Ie Set current Ie for overload tripping before commissioning the motor starter EM 300 EDS/ERS. The setting is made with 2 rotary encoder switches with 8 or 10 switch positions (see figure on page 1-3). The set value in each case is derived from the sum of the two set values.
Set values The set values together with their position on the rotary encoder switch are given in the table below. Position of the rotary encoder switch
Power range 1 0.6 - 2.18 A
Power range 2 2.0 - 5.95 A
Switch 1
Switch 2
Switch 1
Switch 2
0
0.6
0.00
2.0
0.00
1
0.8
0.02
2.5
0.05
2
1.0
0.04
3.0
0.10
3
1.2
0.06
3.5
0.15
4
1.4
0.08
4.0
0.20
5
1.6
0.10
4.5
0.25
6
1.8
0.12
5.0
0.30
7
2.0
0.14
5.5
0.35
8, 0.16, 0.40
9, 0.18, 0.45
Example If you want to set a current of 1.28 A, turn switch 1 to position 3 and switch 2 to position 4. Power range 1: Switch 1 Switch 2
1.28 A =
1.2 A +
0.08 A
Position 3 Position 4
SIMATIC - EM 300 Motor Starters
3-6
GWA-4NEB 640070302-05
Page 35
Commissioning
Electronic overload protection You can set the overload protection mode with the tripping REMOTE/LOCAL rotary encoder switch on the motor starter EM 300 EDS/ERS (see figure on page 1-3). In the user program you can define the response to the signal "FAULT /release signal" (DI2) when the rotary encoder switch is in position tripping REMOTE. Rotary encoder switch position
Overload protection
Response
Tripping REMOTE
Control via the bus
Depending on the settings in the user program:
Tripping LOCAL
Local control
• •
Operation continued inspite of release signal or Remote shutdown (= overload release)
•
Direct shutdown (= overload release)
Caution ! Direct shutdown of the device if a release signal is received is disabled if the rotary encoder switch is in the tripping REMOTE position. In the user program, define a suitable response (usually shutdown of the load circuit) for a signal received at input DI2.
SIMATIC - EM 300 Motor Starters GWA-4NEB 640070302-05
3-7
Page 36
Commissioning
Overload release test You can perform an overload release test either in the initial state or in operating mode. An internal program checks the overload and current flow acquisition. Step
Procedure
1
Open the transparent cover in the top section of the compact starter.
2
Press the TEST/RESET button for at least 2 s.
3a
Press theTEST/RESET button again.
3b
Remedy the cause of the fault.
4
Press the TEST/RESET button again for at least 2 s.
Description
READY LED
OVERLOAD
FAULT LED
LED
On, - Test runs for approx. 10 s. Bus control is disabled.
On
Flashes fast, a) Test successful
On
Flashes slowly, Bus control enabled again.
On
Off, b) Fault during test
Off
Flashes slowly
On
Test is restarted.
On
Flashes fast, a) Test successful: See step 3 for how to continue procedure 3.
On
Flashes slowly, Safeguard against accidental opening You can apply a lead seal or place a lock on the transparent cover of the motor starter EM 300 EDS/ERS to prevent unauthorized setting of the rotary encoder switch, for example.
3.2.2
Operation
Remote reset Remote reset causes the following: • If the rotary encoder switch in in position tripping LOCAL: Resets overload release as soon as the motor model has fallen below the release threshold. • If the rotary encoder switch is in position tripping LOCAL or tripping REMOTE: Resets a FAULT signal if the cause of the fault has been remedied.
SIMATIC - EM 300 Motor Starters
3-8
GWA-4NEB 640070302-05
Page 37
Commissioning
Local reset If you press the TEST/RESET button during a local reset, various responses are triggered depending on how long the button is depressed (see the following table).
Reset after signal "FAULT/release signal" (DI2) After a release signal (device continues operation) resp. overload release (device is shut down) the OVERLOAD LED lights up. After a FAULT signal (device is shut down) the FAULT LED lights up. You can reset the OVERLOAD resp. the FAULT display and the DI2 signal with a local or remote reset in which case the LEDs goes out. Rotary encoder switch setting
Reset
Tripping REMOTE
Local reset
Tripping LOCAL
Procedure
•
Press the RESET/RESET button for less than 2 s: – A pending FAULT signal is reset if the cause of the fault has been remedied.
•
Press the TEST/RESET button for more than 2 s: – Fast discharge of the motor model, i. e. the motor model is reset without a delay, – Device self-test is triggered. Press the TEST/RESET button again as soon as the READY LED lights up again.
Auto reset
The release signal is reset automatically as soon as the motor model is below the release threshhold again.
Local reset
•
Press the RESET/RESET button for less than 2 s: – The release signal is reset as soon as the motor model is below the release threshhold again, – A pending FAULT signal is reset if the cause of the fault has been remedied.
•
Press the TEST/RESET button for more than 2 s: – Fast discharge of the motor model, i. e. the motor model is reset without a delay, – Device self-test is triggered. Press the TEST/RESET button again as soon as the READY LED lights up again.
Remote Reset
In the user program set output DO3 to "1" and then to "0" again.
Communication failure If communication fails, the circuit outputs are reset after approx. 100 ms. Restart is automatic. Note If the 24 V DC supply voltage for electronic motor starters is interrupted for longer than 5 seconds, a waiting period of t > 50 s for normal operation must be observed before switching back on.
SIMATIC - EM 300 Motor Starters GWA-4NEB 640070302-05
3-9
Page 38
Commissioning
3.2.3
Diagnostics
Diagnosis via LEDs During operation, the LEDs on the motor starter EM 300 EDS/ERS indicate the following statuses: LED DC 24 V
Function Auxiliary power
Indication
Status
Steady green light
Auxiliary power applied
Off
Auxiliary power missing
STATE (from Version 2)
Control by bus/ hand-held controller
Steady green light
Control signal applied
READY
Initial state
Steady green light
Device ready for operation
RUN
Operating state
Steady yellow light
Main circuit on if current flow > 20 % In
FAULT
Fault
Steady red light
Main circuit off, e.g. after • • • •
OVERLOAD failure of two phases motor connector pulled out supply voltage dip (< 18 V) simultaneous activation of clockwise and anticlockwise rotation
Overcurrent signal
Flashing red
Main circuit on
Overload release test
Flashing red Flashes quickly Flashes slowly
Main circuit off Test running Test completed
Overload release
Steady red light
Main circuit off •
•
Overload signal
Steady red light
Rotary encoder switch in position tripping LOCAL: Direct shutdown Rotary encoder switch in position tripping REMOTE: Remote shutdown if the relevant settings have been made in the user program
Main circuit on •
Rotary encoder switch in position tripping REMOTE: Operation is continued if the relevant settings have been made in the user program.
SIMATIC - EM 300 Motor Starters
3-10
GWA-4NEB 640070302-05
Page 39
Commissioning
Diagnosis via the user program You can evaluate the input and output signals in your application. Please note that "DO2" is only triggered on versions with a braking contact.
Input signals DI0
Manual/automatic mode
DI1
Current flow signal
0
Manual
0
No current flow
1
Automatic
1
Current flow
DI2
FAULT/release signal
DI3
Overcurrent signal
0
Not released
0
No overcurrent
1
Rotary encoder switch in position tripping LOCAL: • Direct shutdown (= overload release) • FAULT shutdown
1
Overcurrent
Rotary encoder switch in position tripping REMOTE: if the relevant settings have been made in the user program • Remote shutdown (= overload release) • Continued operation (= release signal) • FAULT shutdown
Output signals DO0
Activation of main circuit
DO1
Activation of main circuit
0
Clockwise rotation off
0
Anticlockwise rotation off
1
Clockwise rotation on
1
Anticlockwise rotation on
DO2
Braking contact
DO3
Remote reset
0
Open braking contact
0
Remote reset off
1
Close braking contact
1
Remote reset on
SIMATIC - EM 300 Motor Starters GWA-4NEB 640070302-05
3-11
Page 40
Commissioning
SIMATIC - EM 300 Motor Starters
3-12
GWA-4NEB 640070302-05