The text of a manual · part 5 of 8
SIMATIC EM 300 Motor Starters Manual, pages 41 to 50
Pages 41 to 50 of 74
The original document is the PDF (917 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Siemens EM-300-RS
Page 41
4
Hand-held Controller Section
Subject
Page
4.1
Functions and View
4-2
4.2
Operation
4-3
4.3
LEDs
4-4
4.4
Buttons
4-5
SIMATIC - EM 300 Motor Starters GWA-4NEB 640070302-05
4-1
Page 42
Hand-held Controller
4.1
Functions and View
Functions You can use the hand-held controller to operate the motor starter independently in the field when a load voltage is applied to ET 200X: • Before commissioning the PROFIBUS-DP and the PLC in order to test the motor, • In order to operate the system in manual mode if the PLC or the bus system fails, • When operating a PLC or bus for autonomous local operator control, • During normal operation in order to test the outputs (diagnosis/monitoring).
View
3RK1 902-0AM00 power stand by right left automatic mode remote manual mode local
Function modes You can operate the hand-held controller in "jogging mode" and "continuous mode". In manual mode, the functions of the left and right buttons differ depending on this setting.
SIMATIC - EM 300 Motor Starters
4-2
GWA-4NEB 640070302-05
Page 43
Hand-held Controller
4.2
Operation
Connection Connect the hand-held controller as follows: Step
Procedure
1
Open the transparent cover of the compact starter.
2
Connect the cable of the hand-held controller to the Sub-D socket.
Switchover to continuous mode The hand-held controller is available in "jogging mode". However, it can also be set to "continuous mode". To do this, proceed as follows: Step
Procedure
1
Switch to "remote" mode on the connected hand-held controller.
2
Keep both the left and right button pressed for approximately 5 s.
3
Release the buttons as soon as the LED remote starts to flash.
"Continuous mode" is maintained as long as the hand-held controller on the on the motor starter is connected to 24 V DC. "Jogging mode" is reestablished as soon as you remove the hand-held controller.
Removing the hand-held controller If you remove the hand-held controller from the motor starter, • actuation via the PROFIBUS-DP remains blocked if "local" mode is set on the hand-held controller, • a motor in operation is switched off again if "local" mode is set on the handheld controller, • "Jogging mode" is set on the hand-held controller again.
Motor starter with braking contact On motor starters with a braking contact, the brake is automatically controlled with the right or left button.
SIMATIC - EM 300 Motor Starters GWA-4NEB 640070302-05
4-3
Page 44
Hand-held Controller
4.3
LEDs
Monitoring You can monitor the functions of the motor starter via the LEDs on the handheld controller: LED
Lights up when ...
Goes out when ...
Power
Auxiliary power is supplied
No auxiliary power is supplied
Standby
Auxiliary power is supplied
Remote or local is pressed on the handheld controller
The direct starter is switched on
The direct starter is switched off
The reversing starter activates the clockwise direction
•
Right
• Left
The reversing starter activates the anticlockwise direction
• •
The reversing starter activates the anticlockwise direction The reversing starter is switched off The reversing starter activates the anticlockwise direction The reversing starter is switched off
Remote
Automatic mode is switched on
The hand-held controller is switched to manual mode
Local
Manual mode is switched on
The hand-held controller is switched to automatic mode
SIMATIC - EM 300 Motor Starters
4-4
GWA-4NEB 640070302-05
Page 45
Hand-held Controller
4.4
Buttons
Remote button You can set the motor starter to automatic mode with the remote button. In this mode you can monitor the status of the bus control. The LED indicates • on a direct starter whether the bus is controlled, • on a reversing starter, the direction currently activated: Clockwise (LED right) or anticlockwise (LED left).
Local button With the local button you can set the motor starter to manual mode. Activation via PROFIBUS-DP is blocked in this mode! If you switch from "remote" to "local", an active motor is switched off. If you disconnect the hand-held controller, • "local" mode is maintained, i. e. activation via PROFIBUS-DP remains blocked. • a motor in operation is switched off.
Right-/left button The table below shows the functions of the right and left button in "local" mode in relation to the function mode of the hand-held controller: Function mode of HHU
"Local" mode
Jogging mode
The motor starter remains switched on while you keep the right or left button (on the reversing starter) pressed.
Continuous mode
You can effect the following actions: •
With a direct starter – Switch on the motor starter by pressing the ”Right” button once, – Switch off the motor starter by pressing the ”Right” button again or by pressing the ”Left” button.
•
With a reversing starter – Activate the ”left” or ”right” direction of rotation by pressing the appropriate button, – Switch off the motor starter by pressing the same button again, – Reverse the direction of rotation directly.
SIMATIC - EM 300 Motor Starters GWA-4NEB 640070302-05
4-5
Page 46
Hand-held Controller
SIMATIC - EM 300 Motor Starters
4-6
GWA-4NEB 640070302-05
Page 47
5
Technical Specifications
Section
Subject
Page
5.1
General Technical Specifications of Motor Starters
5-2
5.2
Voltages and Currents
5-3
5.3
Braking Current Circuit
5-4
5.4
Specifications of Motor Starters EM 300 DS/RS
5-5
5.5
Specifications of Motor Starters EM 300 EDS/ERS
5-6
5.6
Shipping and Storage Conditions
5-7
5.7
Mechanical and Climatic Environment Conditions
5-8
SIMATIC - EM 300 Motor Starters GWA-4NEB 640070302-05
5-1
Page 48
Technical Specifications
5.1
General Technical Specifications of Motor Starters Dimensions W x H x D (mm)
120 x 265 x 134
Weight • Direct starter EM 300 DS • Reversing starter EM 300 RS • Direct starter EM 300 EDS • Reversing starter EM 300 ERS
1.5 kg 1.9 kg 1.5 kg 1.6 kg
Assignment type • Type 1 up to Irated < 12 A •
Type 2 up to Irated < 1.6 A
IEC 60947-4-1, DIN VDE 0660, Part 102 (does not applie to motor starters EM 300 EDS/ERS)
Pollution severity 3
IEC 60664 (IEC 61131)
Safety class I
IEC 60536 (VDE 0106, Part 1)
Degree of protection IP 65
IEC 60529
• •
Protection against the ingress of dust and complete protection against electric shock Protection against water jets from nozzles which are aimed at the casing from all directions. (There must be no harmful effects from the water.)
Note
The degree of protection IP 65 is only warranted when the compact starter is completely closed. Therefore: Seal off any terminal connections which are not required with screw caps.
Insulation strength Circuits with a rated voltage Ue to other circuits or to ground
Test voltage in accordance with IEC 61131, Part 2
0 V < Ue < 50 V
500 V DC
300 V < Ue < 600 V
2.6 kV DC to ground
SIMATIC - EM 300 Motor Starters
5-2
GWA-4NEB 640070302-05
Page 49
Technical Specifications
5.2
Voltages and Currents
Voltages Rated supply voltage for electronics and sensors (1L+) 24 V DC Reverse polarity protection yes Short-circuit protection yes Rated load voltage (2L+) for contactor coil resp. electronics and hand-held controller Reverse polarity protection Short-circuit protection
24 V DC no yes
Braking voltage • EM 300 DS/RS • EM 300 EDS/ERS
24 V DC resp. 500 V DC 24 V DC, 400 V AC, 500 V DC
Reverse polarity protection Short-circuit protection yes yes
Safe isolation between main circuit and auxiliary circuit to DIN VDE 0106, Part 101/Part 101 A1
400 V
Currents Aggregate current of motor starters • at 55 °C – with 2.5 mm2 connection – with 4.0 mm2 connection • at 40 °C – with 2.5 mm2 connection – with 4.0 mm2 connection
Power input • from supply voltage 1L+ • from load voltage 2L+ (without hand-held controller) Minimum tripping current if a phase fails (= 100% current unbalance)
20 A 30 A 25 A 35 A typ. 70 mA typ. 170 mA 0.85 x Ie
Main circuit Rated operating voltage Ue • to IEC 60947-1, EN 60947-1 • to CSA and UL
500 V AC; tolerance range to 575 V AC up to 600 V AC
Rated insulation voltage Ui
690 V AC
Rated impulse strength Uimp • EM 300 DS/RS • EM 300 EDS/ERS
6 kV 2.5 kV
Rated frequency
50/60 Hz
SIMATIC - EM 300 Motor Starters GWA-4NEB 640070302-05
5-3
Page 50
Technical Specifications
Caution Large EMC faults can occur as a result of three-phase motors being operated when connected in star formation (particularly when < 1 kW). Faults above the IEC limit values can lead to impairment of function or failure of the electronics. We recommend using motors featuring EMC protective circuits in the case of high EMC faults. (Exception: Electronic starters must not be operated with an EMC protective circuit). The best filter effect is achieved using 3-phase RC interference suppression modules. Varistor interference suppression modules should not be used, as these do not filter out rapid transients to a sufficient extent.
5.3
Braking Current Circuit
Version with a 24 V DC braking contact Utilization category to VDE 0660, Part 102 and IEC 60947-4.1
DC-13
Max. permissible output of the brake coil
70 W
Rated operational current Ie
3A
Version with a 400 V AC braking contact Utilization category to VDE 0660, Part 102 and IEC 60947-4.1
AC-15
Max. permissible output of the brake coil
200 VA
Rated operational current Ie
0.5 A
Version with a 500 V DC braking contact Utilization category to VDE 0660, Part 102 and IEC 60947-4.1
AC-13
Max. permissible output of the brake coil
100 W
Rated operational current Ie
0.2 A
SIMATIC - EM 300 Motor Starters
5-4
GWA-4NEB 640070302-05