For the Siemens EM-300-RS

Page 51

Technical Specifications

5.4

Specifications of Motor Starters EM 300 DS/RS

Circuit-breaker Tripping class

Class 10

Max. rated current

12 A

Adjustment ranges • Thermal overload release • Undelayed overcurrent release

0.14-0.2 A to 9-12 A 12 x Irated (fixed)

Rated ultimate short-circuit braking capacity up to Irated = 12 A

50 kA

Mechanical life

> 100,000 switching cycles

Utilization category to VDE 0660, Part 102 and IEC 60947-4.1

AC-2, AC-3

Max. permissible output of three-phase motors (with 400 V AC )

5.5 kW

Rated operating current Ie

12 A

Contactor

Max. permissible switching rate at motor starting time 80/h t a = 0.1 s and 50% relative ON period Mechanical life

> 10 Mill. switching cycles

Operating delay of auxiliary contact (including input delay of module) • From 0 to 1 • From 1 to 0

29 to 59 ms 26 to 34 ms switching cycles at 400 V

Switching cycles

Ia = Breaking current

Ie = Rated operating current PN = Permissible output of three phase motors at 400 V

SIMATIC - EM 300 Motor Starters GWA-4NEB 640070302-05

5-5

Page 52

Technical Specifications

5.5 Specifications of Motor Starters EM 300 EDS/ERS Electronic overload protection Tripping class

Class 10

Max. rated current

2.18 A or 5.95 A

Setting ranges

0.6 to 2.18 A 2.0 to 5.95 A

Short-circuit protection (fuses) Rated ultimate short-circuit breaking capacity

100 kA

Electronic switchgear unit (2-phase) Utilization category to IEC 60947-4.2

AC-53b

Rated operating current Ie

2.18 A or 5.95 A

Modes of operation

S1, S2, S3, S4

Shortest ON period

300 ms

Shortest pause between 2 switching operations

1s

Maximum switching rate Maximum switching rate

2000 1800

Schaltungen /h /h switching rate

1600 ta = 0,1 s

1400 1200 1000 ta = 0,25 s

800 600 ta = 0,5 s

400 ta = 1 s

200 ta = Motor starting time

0 99%

80%

60%

40%

20%

10%

6%

4% relative Einschaltdauer relative ON period

SIMATIC - EM 300 Motor Starters

5-6

GWA-4NEB 640070302-05

Page 53

Technical Specifications

5.6

Shipping and Storage Conditions

Shipping and storage conditions The motor starters surpasses the requirements of IEC 61131, Part 2, with regard to shipping and storage conditions. The following details apply to modules that are shipped and stored in their original packing.

Type of condition

Admissible range

Free fall

0.4 m

Temperature from -40 °C to +70 °C

Temperature variation

20 K/h

Air pressure from 1,080 to 660 hPa (corresponds to an altitude of -1,000 to 3,500 m)

Relative humidity from 5 to 95%, without condensation

SIMATIC - EM 300 Motor Starters GWA-4NEB 640070302-05

5-7

Page 54

Technical Specifications

5.7

Mechanical and Climatic Environment Conditions

Mechanical environment conditions Oscillation test to IEC 60068, Part 2-6 (Sine) •

•

Oscillation type:

frequency sweeps with a rate of change of 1 octave per minute

– 10 Hz < f < 58 Hz constant amplitude: 0.15 mm

– 58 Hz < f < 150 Hz constant acceleration: 2 g

Oscillation time:

10 frequency sweeps per axis in all of the three perpendicular axes

Shock test to IEC 60068, Part 2-27 • • •

Type of shock: Force of shock: Direction of shock:

Half sine 15 g peak value, 11 ms duration 3 shocks per +/– direction in all of the three perpendicular axes

Climatical environment conditions Temperature

From 0 to 55 °C

Temperature variation

10 K/h

Permissible rated current

100% at 0 °C ≤ Tenv < 40 °C 87% at 40 °C ≤ Tenv < 55 °C

Relative humidity

From 5 to 100%

Air pressure

From 1080 to 795 hPa

All installation positions

Corresponds to an altitude of -1,000 to 2,000 m

Contaminant concentration SO2 : < 0.5 ppm rel. humidity < 60%, no moisture condensation

Test: 10 ppm; 4 days

H2 S: < 0.1 ppm rel. humidity < 60%, no moisture condensation

1 ppm; 4 days

SIMATIC - EM 300 Motor Starters

5-8

GWA-4NEB 640070302-05

Page 55

SIGUARD Safety Integrated

Section

Subject

6 Page

6.1

Suggested Circuits

6-2

6.1.1

Safety category 1 (EN 954-1)

6-2

6.1.2

Safety category 2 (EN 954-1)

6-2

6.1.3

Safety category 3 (EN 954-1)

6-3

6.1.4

Safety category 4 (EN 954-1)

6-3

SIMATIC - EM 300 Motor Starters GWA-4NEB 640070302-05

6-1

Page 56

SIGUARD Safety Integrated

6.1

Suggested Circuits

6.1.1

Safety category 1 (EN 954-1)

L1+/L-

L2+/L-

AC 400V

+ -

+ -X1

-X3

-X1

-X3

-X1

-X3

Emergency trip Out 0

IN0

Out 0

IN1

IN0

IN1

-X2

IN1

-X2

M

6.1.2

Out 0

IN0

-X2

M

M

Safety category 2 (EN 954-1) Emergency trip 1

L1+/L-

L2+/L-

AC 400V

+ -

+ -

1 1

Safety relay, e.g. SIGUARD 3TK28

-X1

-X3

Emergency trip 2

Reset -X1

-X3

-X1

-X3

I>

Out 0

IN0

Out 0

IN0

On

Run

IN1 -X2

IN0

IN1 -X2

M

Out 0

IN1 -X2

M

M

SIMATIC - EM 300 Motor Starters

6-2

GWA-4NEB 640070302-05

Page 57

SIGUARD Safety Integrated

6.1.3

Safety category 3 (EN 954-1)

L1+/L-

L2+/L-

AC 400V

+ -

+ -

Emergency trip 2

Emergency trip 1 Safety relay, e.g. SIGUARD 3TK28

1 1 2 2

-X1

-X3

Reset -X1

-X3

-X1

-X3

I>

Out 0

IN0

Out 0

IN0

On

Run

IN1

IN0

IN1

-X2

IN1

-X2

M

6.1.4

Out 0

-X2

M

M

Safety category 4 (EN 954-1) Emergency trip

L1+/L-

L2+/L-

AC 400V

+ -

+ -

Safety relay, e.g. SIGUARD 3TK28

1 1 2 2

-X1

-X3

Reset -X1

-X3

-X1

-X3

I>

Out 0

IN0

Out 0

IN0

On

Run

IN1 -X2

SIMATIC - EM 300 Motor Starters GWA-4NEB 640070302-05

IN0

IN1 -X2

M

Out 0

IN1 -X2

M

M

6-3

Page 58

SIGUARD Safety Integrated

SIMATIC - EM 300 Motor Starters

6-4

GWA-4NEB 640070302-05

Page 59

A

Order Numbers Direct Starters EM 300 EDS Adjustment range *

Order number

A

Order number extension

Basic version

Versions with braking contact 24 V DC

400 V AC

500 V DC

0.6 - 2.18

3RK1 300-0AS10- . . . .

0AA0

0AA1

0AA3

0AA4

2.0 - 5.95

3RK1 300-0BS10- . . . .

0AA0

0AA1

0AA3

0AA4

Reversing Starters EM 300 ERS Adjustment range *

Order number

A

Order number extension

Basic version

Versions with braking contact 24 V DC

400 V AC

500 V DC

0.6 - 2.18

3RK1 300-0AS10- . . . .

1AA0

1AA1

1AA3

1AA4

2.0 - 5.95

3RK1 300-0BS10- . . . .

1AA0

1AA1

1AA3

1AA4

* For assignment to performance of 400 V AC squirrel-cage motors see Appendix D

SIMATIC - EM 300 Motor Starters GWA-4NEB 640070302-05

A-1

Page 60

Order Numbers

Direct Starters EM 300 DS Adjustment range *

Order number

A

Order number extension

Basic version

Version with braking contact 24 V DC

Version with braking contact 500 V DC

0.14 - 0.20

3RK1 300-0BS01- . . . .

0AA0

0AA1

0AA4

0.18 - 0.25

3RK1 300-0CS01- . . . .

0AA0

0AA1

0AA4

0.22 - 0.32

3RK1 300-0DS01- . . . .

0AA0

0AA1

0AA4

0.28 - 0.40

3RK1 300-0ES01- . . . .

0AA0

0AA1

0AA4

0.35 - 0.50

3RK1 300-0FS01- . . . .

0AA0

0AA1

0AA4

0.45 - 0.63

3RK1 300-0GS01- . . . .

0AA0

0AA1

0AA4

0.55 - 0.80

3RK1 300-0HS01- . . . .

0AA0

0AA1

0AA4

0.70 - 1.00

3RK1 300-0JS01- . . . .

0AA0

0AA1

0AA4

0.90 - 1.25

3RK1 300-0KS01- . . . .

0AA0

0AA1

0AA4

1.10 - 1.60

3RK1 300-1AS01- . . . .

0AA0

0AA1

0AA4

1.40 - 2.00

3RK1 300-1BS01- . . . .

0AA0

0AA1

0AA4

1.80 - 2.50

3RK1 300-1CS01- . . . .

0AA0

0AA1

0AA4

2.20 - 3.20

3RK1 300-1DS01- . . . .

0AA0

0AA1

0AA4

2.80 - 4.00

3RK1 300-1ES01- . . . .

0AA0

0AA1

0AA4

3.50 - 5,00

3RK1 300-1FS01- . . . .

0AA0

0AA1

0AA4

4.50 - 6.30

3RK1 300-1GS01- . . . .

0AA0

0AA1

0AA4

5.50 - 8.00

3RK1 300-1HS01- . . . .

0AA0

0AA1

0AA4

7.00 - 10.0

3RK1 300-1JS01- . . . .

0AA0

0AA1

0AA4

9.00 - 12.0

3RK1 300-1KS01- . . . .

0AA0

0AA1

0AA4

* For assignment to performance of 400 V AC squirrel-cage motors see Appendix D

SIMATIC - EM 300 Motor Starters

A-2

GWA-4NEB 640070302-05