Page 61

Order Numbers

Reversing Starters EM 300 RS Adjustment range *

Order number

A

Order number extension

Basic version

Version with braking contact 24 V DC

Version with braking contact 500 V DC

0.14 - 0.20

3RK1 300-0BS01- . . . .

1AA0

1AA1

1AA4

0.18 - 0.25

3RK1 300-0CS01- . . . .

1AA0

1AA1

1AA4

0.22 - 0.32

3RK1 300-0DS01- . . . .

1AA0

1AA1

1AA4

0.28 - 0.40

3RK1 300-0ES01- . . . .

1AA0

1AA1

1AA4

0.35 - 0.50

3RK1 300-0FS01- . . . .

1AA0

1AA1

1AA4

0.45 - 0.63

3RK1 300-0GS01- . . . .

1AA0

1AA1

1AA4

0.55 - 0.80

3RK1 300-0HS01- . . . .

1AA0

1AA1

1AA4

0.70 - 1.00

3RK1 300-0JS01- . . . .

1AA0

1AA1

1AA4

0.90 - 1.25

3RK1 300-0KS01- . . . .

1AA0

1AA1

1AA4

1.10 - 1.60

3RK1 300-1AS01- . . . .

1AA0

1AA1

1AA4

1.40 - 2.00

3RK1 300-1BS01- . . . .

1AA0

1AA1

1AA4

1.80 - 2.50

3RK1 300-1CS01- . . . .

1AA0

1AA1

1AA4

2.20 - 3.20

3RK1 300-1DS01- . . . .

1AA0

1AA1

1AA4

2.80 - 4.00

3RK1 300-1ES01- . . . .

1AA0

1AA1

1AA4

3.50 - 5,00

3RK1 300-1FS01- . . . .

1AA0

1AA1

1AA4

4.50 - 6.30

3RK1 300-1GS01- . . . .

1AA0

1AA1

1AA4

5.50 - 8.00

3RK1 300-1HS01- . . . .

1AA0

1AA1

1AA4

7.00 - 10.0

3RK1 300-1JS01- . . . .

1AA0

1AA1

1AA4

9.00 - 12.0

3RK1 300-1KS01- . . . .

1AA0

1AA1

1AA4

* For assignment to performance of 400 V AC squirrel-cage motors see Appendix D

SIMATIC - EM 300 Motor Starters GWA-4NEB 640070302-05

A-3

Page 62

Order Numbers

Accessories for Motor Starters EM 300 Description

No. of items per pack

Order number

Crimping tool - for contact pins and jacks 1.5 to 2.5 mm2 - for contact pins and jacks 2.5 to 4.0 mm2

1 1

3RK1902-0AH00 3RK1902-0CT00

Dismantling tool for contact pins and jacks (for 9-pole inserts)

1

3RK1902-0AJ00

Screw cap for power sockets

1 10

3RK1902-0CK00 3RK1902-0CJ00

Hand-held controller with 0.5 m connecting cable

1

3RK1902-0AM00

Power connecting cable 6 x 2.5 mm2, 0.12 m long

1

3RK1902-0CH00

Power connecting cable 4 x 4.0 mm2, 0.15 m long

1

3RK1902-0CG00

Set of connectors for power supply 2.5 mm2: 1 connector shell with PG 16, 1 socket insert and 6 jacks 2.5 mm2

1

3RK1902-0CA00

Set of connectors for power supply 4.0 mm2: 1 connector shell with PG 16, 1 socket insert and 6 jacks 4.0 mm2

1

3RK1902-0CB00

Set of connectors for looping through power 2.5 mm2: 1 connector shell with PG 16, 1 pin insert and 6 contact pins 2.5 mm2

1

3RK1902-0CC00

Set of connectors for looping through power 4.0 mm2: 1 connector shell with PG 16, 1 pin insert and 6 contact pins 4.0 mm2

1

3RK1902-0CD00

Set of connectors for connecting motor 1.5 mm2: 1 connector shell with PG 16, 1 pin insert and 8 contact pins 1.5 mm2

1

3RK1902-0CE00

Motor connecting cable 4 x 1.5 mm2, 3 m long, with plug

1

3RK1902-0CM00

Motor connecting cable 4 x 1.5 mm2, 5 m long, with plug

1

3RK1902-0CP00

Motor connecting cable 4 x 1.5 mm2, 10 m long, with plug

1

3RK1902-0CQ00

Motor connecting cable 6 x 1.5 mm2, 3 m long, with plug

1

3RK1902-0CN00

Motor connecting cable 6 x 1.5 mm2, 5 m long, with plug

1

3RK1902-0CR00

Motor connecting cable 6 x 1.5 mm2, 10 m long, with plug

1

3RK1902-0CS00

SIMATIC - EM 300 Motor Starters

A-4

GWA-4NEB 640070302-05

Page 63

Dimension Drawings

B

Motor starters EM 300 The diagram below is a dimension drawing of the motor starters EM 300.

SIMATIC - EM 300 Motor Starters GWA-4NEB 640070302-05

B-1

Page 64

Dimension Drawings

SIMATIC - EM 300 Motor Starters

B-2

GWA-4NEB 640070302-05

Page 65

C

Configuration Frame DP Identifiers (Special Identifier Format)

The identifiers serve to distinguish between the modules that are used on the PROFIBUS-DP. The following table contains all special DP identifiers for the motor starters, that are used as expansion modules on the ET 200X distributed I/O device. Motor starter

Order number

Identifiers (hexadecimal) Byte 0

Byte 1

Byte 2

Byte 3

Byte 4

EM 300 DS

3RK1 300- . .S01-0AA .

C2

00

00

CF

C9

EM 300 RS

3RK1 300- . .S01-1AA .

C2

00

00

DF

C9

EM 300 EDS

3RK1 300- . .S10-0AA .

C2

00

00

EF

C9

EM 300 ERS

3RK1 300- . .S10-1AA .

C2

00

00

FF

C9

DP Identifiers (Normal Identifier Format) The identifiers serve to distinguish between the modules that are used on the PROFIBUS-DP. The following table contains all normal DP identifiers for the motor starters, that are used as expansion modules on the ET 200X distributed I/O device. Motor starter

Order number

Identifiers (hexadecimal) Byte 0

EM 300 DS

3RK1 300- . .S00-0AA .

30

EM 300 RS

3RK1 300- . .S00-1AA .

30

EM 300 EDS

3RK1 300- . .S10-0AA .

30

EM 300 ERS

3RK1 300- . .S10-1AA .

30

SIMATIC - EM 300 Motor Starters GWA-4NEB 640070302-05

C-1

Page 66

Configuration Frame

Byte assignment The diagram below shows the byte for the input and output signals. Bits X.4 to X.7 have no meaning. X.3

X.0

Bit no.

Byte X Input signal DI0 or output signal DO0 Input signal DI1 or output signal DO1 Input signal DI2 or output signal DO2 Input signal DI3 or output signal DO3

Evaluation The following is an extract from an application for interrogating signals. The address of the motor starter is 4 in the example. STL

Label: Ende: On:

Description . . UN SPB U SPBN . . S U L U SPB . . BE UN SPBN SPA

Manual: . . SPA Error: . . SPA

Custom application E 4.3 Error E 4.0

Has circuit-breaker tripped (E4)? If so, branch to error handling Interrogate operating mode (E1) Branch if manual Program section for driving clockwise rotation output A 4.0 Activate clockwise rotation output(A1) A 4.0 Generate positive edge for timer 0 S5T#60ms Load delay time until contactor ”safely on” T0 If timer 0 expires On Continue here if time not elapsed Remainder of Program E 4.1 Error Label

Interrogate feedback from contactor (E2) Branch if error

Program section for manual mode End Program section for error handling End

SIMATIC - EM 300 Motor Starters

C-2

GWA-4NEB 640070302-05

Page 67

D

Selection Help Application examples

The table below contains various applications together with the type and number of motor starters EM 300 that you need for each application. You can actuate both pole-changing motors and motors with separate windings.

Without brake

Application

Direct starter EM 300 DS, EM 300 EDS

One dir. of rotation One speed

1 starter

Two dir. of rotation One speed One dir. of rotation Two speeds

Direct starter with braking contact

2 st.1) 2 st. 1)

One dir. of rotation One speed

1 st.

Two dir. of rotation One speed One dir. of rotation Two speeds Two dir. of rotation Two speeds

Reversing starter with braking contact

1 st.

Two dir. of rotation Two speeds With brake

Reversing starter EM 300 RS, EM 300 ERS

1 st. 1 st.2)

1 st. 2) 2 st. 3) 1 st. 2)

1 st. 2) 2 st. 3)

Notes 1) The two speeds must be mutually interlocked in the user program with the feedback contactor of the other starter. 2) see 1), but in addition the output brake of one starter must remain set during switchover and activation of the other starter. 3) This version is suitable if you want to loop the 24 V DC braking voltage through to the next drive. The 24 V DC braking voltage cannot be looped through via a motor starter without braking contact.

SIMATIC - EM 300 Motor Starters GWA-4NEB 640070302-05

D-1

Page 68

Selection Help

Motor list The following tables contain the operating values of squirrel-cage motors of basic design. Source: Siemens Three-Phase AC Low-Voltage Motors Catalog 1996“. Speed 3000 rpm two-pole 50 Hz 400 V

Speed 1500 rpm four-pole 50 Hz 400 V

Rated power kW

Rated speed min-1

Efficiency %

Power factor cos ϕ

Rated current A

0.18

2680

60

0.83

0.52

0.25

2725

64

0.82

0.69

0.37

2750

67

0.80

1.00

0.55

2790

71

0.81

1.38

0.75

2850

74

0.83

1.76

1.1

2835

76

0.84

2.45

1.5

2860

78

0.82

3.40

2.2

2850

80

0.85

4.65

3

2895

83

0.86

6.10

4

2895

85

0.87

7.80

5.5

2910

84

0.84

11.30

0.18

1315

59

0.76

0.58

0.25

1325

61

0.73

0.81

0.35

1375

66

0.77

1.05

0.55

1395

71

0.79

1.42

0.75

1395

74

0.79

1.86

1.1

1410

74

0.81

2.65

1.5

1410

74

0.81

3.60

2.2

1420

78

0.78

5.20

3

1430

80

0.80

6.80

4

1435

83

0.79

9.00

5.5

1450

86

0.81

11.40

SIMATIC - EM 300 Motor Starters

D-2

GWA-4NEB 640070302-05

Page 69

Selection Help

Speed 1000 rpm six-pole 50 Hz 400 V

Speed 750 rpm eight-pole 50 Hz 400 V

Rated power kW

Rated speed min-1

Efficiency %

Power factor cos ϕ

Rated current A

0.18

830

53

0.71

0.69

0.25

825

59

0.74

0.83

0.35

910

62

0.72

1.19

0.55

900

65

0.73

1.67

0.75

895

67

0.77

2.10

1.1

900

71

0.75

3.00

1.5

930

72

0.75

4.00

2.2

945

76

0.72

5.80

3

945

70

0.75

7.30

4

940

79

0.75

9.70

0.12

655

51

0.59

0.58

0.18

675

51

0.66

0.78

0.25

670

52

0.62

1.12

0.35

655

61

0.76

1.16

0.55

650

65

0.76

1.62

0.75

665

65

0.77

2.15

1.1

675

72

0.76

2.90

1.5

710

72

0.71

4.25

2.2

695

76

0.71

5.90

3

700

79

0.69

7.90

4

715

77

0.72

10.40

SIMATIC - EM 300 Motor Starters GWA-4NEB 640070302-05

D-3

Page 70

Selection Help

SIMATIC - EM 300 Motor Starters

D-4

GWA-4NEB 640070302-05