The text of a manual · part 7 of 8
SIMATIC EM 300 Motor Starters Manual, pages 61 to 70
Pages 61 to 70 of 74
The original document is the PDF (917 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Siemens EM-300-RS
Page 61
Order Numbers
Reversing Starters EM 300 RS Adjustment range *
Order number
A
Order number extension
Basic version
Version with braking contact 24 V DC
Version with braking contact 500 V DC
0.14 - 0.20
3RK1 300-0BS01- . . . .
1AA0
1AA1
1AA4
0.18 - 0.25
3RK1 300-0CS01- . . . .
1AA0
1AA1
1AA4
0.22 - 0.32
3RK1 300-0DS01- . . . .
1AA0
1AA1
1AA4
0.28 - 0.40
3RK1 300-0ES01- . . . .
1AA0
1AA1
1AA4
0.35 - 0.50
3RK1 300-0FS01- . . . .
1AA0
1AA1
1AA4
0.45 - 0.63
3RK1 300-0GS01- . . . .
1AA0
1AA1
1AA4
0.55 - 0.80
3RK1 300-0HS01- . . . .
1AA0
1AA1
1AA4
0.70 - 1.00
3RK1 300-0JS01- . . . .
1AA0
1AA1
1AA4
0.90 - 1.25
3RK1 300-0KS01- . . . .
1AA0
1AA1
1AA4
1.10 - 1.60
3RK1 300-1AS01- . . . .
1AA0
1AA1
1AA4
1.40 - 2.00
3RK1 300-1BS01- . . . .
1AA0
1AA1
1AA4
1.80 - 2.50
3RK1 300-1CS01- . . . .
1AA0
1AA1
1AA4
2.20 - 3.20
3RK1 300-1DS01- . . . .
1AA0
1AA1
1AA4
2.80 - 4.00
3RK1 300-1ES01- . . . .
1AA0
1AA1
1AA4
3.50 - 5,00
3RK1 300-1FS01- . . . .
1AA0
1AA1
1AA4
4.50 - 6.30
3RK1 300-1GS01- . . . .
1AA0
1AA1
1AA4
5.50 - 8.00
3RK1 300-1HS01- . . . .
1AA0
1AA1
1AA4
7.00 - 10.0
3RK1 300-1JS01- . . . .
1AA0
1AA1
1AA4
9.00 - 12.0
3RK1 300-1KS01- . . . .
1AA0
1AA1
1AA4
* For assignment to performance of 400 V AC squirrel-cage motors see Appendix D
SIMATIC - EM 300 Motor Starters GWA-4NEB 640070302-05
A-3
Page 62
Order Numbers
Accessories for Motor Starters EM 300 Description
No. of items per pack
Order number
Crimping tool - for contact pins and jacks 1.5 to 2.5 mm2 - for contact pins and jacks 2.5 to 4.0 mm2
1 1
3RK1902-0AH00 3RK1902-0CT00
Dismantling tool for contact pins and jacks (for 9-pole inserts)
1
3RK1902-0AJ00
Screw cap for power sockets
1 10
3RK1902-0CK00 3RK1902-0CJ00
Hand-held controller with 0.5 m connecting cable
1
3RK1902-0AM00
Power connecting cable 6 x 2.5 mm2, 0.12 m long
1
3RK1902-0CH00
Power connecting cable 4 x 4.0 mm2, 0.15 m long
1
3RK1902-0CG00
Set of connectors for power supply 2.5 mm2: 1 connector shell with PG 16, 1 socket insert and 6 jacks 2.5 mm2
1
3RK1902-0CA00
Set of connectors for power supply 4.0 mm2: 1 connector shell with PG 16, 1 socket insert and 6 jacks 4.0 mm2
1
3RK1902-0CB00
Set of connectors for looping through power 2.5 mm2: 1 connector shell with PG 16, 1 pin insert and 6 contact pins 2.5 mm2
1
3RK1902-0CC00
Set of connectors for looping through power 4.0 mm2: 1 connector shell with PG 16, 1 pin insert and 6 contact pins 4.0 mm2
1
3RK1902-0CD00
Set of connectors for connecting motor 1.5 mm2: 1 connector shell with PG 16, 1 pin insert and 8 contact pins 1.5 mm2
1
3RK1902-0CE00
Motor connecting cable 4 x 1.5 mm2, 3 m long, with plug
1
3RK1902-0CM00
Motor connecting cable 4 x 1.5 mm2, 5 m long, with plug
1
3RK1902-0CP00
Motor connecting cable 4 x 1.5 mm2, 10 m long, with plug
1
3RK1902-0CQ00
Motor connecting cable 6 x 1.5 mm2, 3 m long, with plug
1
3RK1902-0CN00
Motor connecting cable 6 x 1.5 mm2, 5 m long, with plug
1
3RK1902-0CR00
Motor connecting cable 6 x 1.5 mm2, 10 m long, with plug
1
3RK1902-0CS00
SIMATIC - EM 300 Motor Starters
A-4
GWA-4NEB 640070302-05
Page 63
Dimension Drawings
B
Motor starters EM 300 The diagram below is a dimension drawing of the motor starters EM 300.
SIMATIC - EM 300 Motor Starters GWA-4NEB 640070302-05
B-1
Page 64
Dimension Drawings
SIMATIC - EM 300 Motor Starters
B-2
GWA-4NEB 640070302-05
Page 65
C
Configuration Frame DP Identifiers (Special Identifier Format)
The identifiers serve to distinguish between the modules that are used on the PROFIBUS-DP. The following table contains all special DP identifiers for the motor starters, that are used as expansion modules on the ET 200X distributed I/O device. Motor starter
Order number
Identifiers (hexadecimal) Byte 0
Byte 1
Byte 2
Byte 3
Byte 4
EM 300 DS
3RK1 300- . .S01-0AA .
C2
00
00
CF
C9
EM 300 RS
3RK1 300- . .S01-1AA .
C2
00
00
DF
C9
EM 300 EDS
3RK1 300- . .S10-0AA .
C2
00
00
EF
C9
EM 300 ERS
3RK1 300- . .S10-1AA .
C2
00
00
FF
C9
DP Identifiers (Normal Identifier Format) The identifiers serve to distinguish between the modules that are used on the PROFIBUS-DP. The following table contains all normal DP identifiers for the motor starters, that are used as expansion modules on the ET 200X distributed I/O device. Motor starter
Order number
Identifiers (hexadecimal) Byte 0
EM 300 DS
3RK1 300- . .S00-0AA .
30
EM 300 RS
3RK1 300- . .S00-1AA .
30
EM 300 EDS
3RK1 300- . .S10-0AA .
30
EM 300 ERS
3RK1 300- . .S10-1AA .
30
SIMATIC - EM 300 Motor Starters GWA-4NEB 640070302-05
C-1
Page 66
Configuration Frame
Byte assignment The diagram below shows the byte for the input and output signals. Bits X.4 to X.7 have no meaning. X.3
X.0
Bit no.
Byte X Input signal DI0 or output signal DO0 Input signal DI1 or output signal DO1 Input signal DI2 or output signal DO2 Input signal DI3 or output signal DO3
Evaluation The following is an extract from an application for interrogating signals. The address of the motor starter is 4 in the example. STL
Label: Ende: On:
Description . . UN SPB U SPBN . . S U L U SPB . . BE UN SPBN SPA
Manual: . . SPA Error: . . SPA
Custom application E 4.3 Error E 4.0
Has circuit-breaker tripped (E4)? If so, branch to error handling Interrogate operating mode (E1) Branch if manual Program section for driving clockwise rotation output A 4.0 Activate clockwise rotation output(A1) A 4.0 Generate positive edge for timer 0 S5T#60ms Load delay time until contactor ”safely on” T0 If timer 0 expires On Continue here if time not elapsed Remainder of Program E 4.1 Error Label
Interrogate feedback from contactor (E2) Branch if error
Program section for manual mode End Program section for error handling End
SIMATIC - EM 300 Motor Starters
C-2
GWA-4NEB 640070302-05
Page 67
D
Selection Help Application examples
The table below contains various applications together with the type and number of motor starters EM 300 that you need for each application. You can actuate both pole-changing motors and motors with separate windings.
Without brake
Application
Direct starter EM 300 DS, EM 300 EDS
One dir. of rotation One speed
1 starter
Two dir. of rotation One speed One dir. of rotation Two speeds
Direct starter with braking contact
2 st.1) 2 st. 1)
One dir. of rotation One speed
1 st.
Two dir. of rotation One speed One dir. of rotation Two speeds Two dir. of rotation Two speeds
Reversing starter with braking contact
1 st.
Two dir. of rotation Two speeds With brake
Reversing starter EM 300 RS, EM 300 ERS
1 st. 1 st.2)
1 st. 2) 2 st. 3) 1 st. 2)
1 st. 2) 2 st. 3)
Notes 1) The two speeds must be mutually interlocked in the user program with the feedback contactor of the other starter. 2) see 1), but in addition the output brake of one starter must remain set during switchover and activation of the other starter. 3) This version is suitable if you want to loop the 24 V DC braking voltage through to the next drive. The 24 V DC braking voltage cannot be looped through via a motor starter without braking contact.
SIMATIC - EM 300 Motor Starters GWA-4NEB 640070302-05
D-1
Page 68
Selection Help
Motor list The following tables contain the operating values of squirrel-cage motors of basic design. Source: Siemens Three-Phase AC Low-Voltage Motors Catalog 1996“. Speed 3000 rpm two-pole 50 Hz 400 V
Speed 1500 rpm four-pole 50 Hz 400 V
Rated power kW
Rated speed min-1
Efficiency %
Power factor cos ϕ
Rated current A
0.18
2680
60
0.83
0.52
0.25
2725
64
0.82
0.69
0.37
2750
67
0.80
1.00
0.55
2790
71
0.81
1.38
0.75
2850
74
0.83
1.76
1.1
2835
76
0.84
2.45
1.5
2860
78
0.82
3.40
2.2
2850
80
0.85
4.65
3
2895
83
0.86
6.10
4
2895
85
0.87
7.80
5.5
2910
84
0.84
11.30
0.18
1315
59
0.76
0.58
0.25
1325
61
0.73
0.81
0.35
1375
66
0.77
1.05
0.55
1395
71
0.79
1.42
0.75
1395
74
0.79
1.86
1.1
1410
74
0.81
2.65
1.5
1410
74
0.81
3.60
2.2
1420
78
0.78
5.20
3
1430
80
0.80
6.80
4
1435
83
0.79
9.00
5.5
1450
86
0.81
11.40
SIMATIC - EM 300 Motor Starters
D-2
GWA-4NEB 640070302-05
Page 69
Selection Help
Speed 1000 rpm six-pole 50 Hz 400 V
Speed 750 rpm eight-pole 50 Hz 400 V
Rated power kW
Rated speed min-1
Efficiency %
Power factor cos ϕ
Rated current A
0.18
830
53
0.71
0.69
0.25
825
59
0.74
0.83
0.35
910
62
0.72
1.19
0.55
900
65
0.73
1.67
0.75
895
67
0.77
2.10
1.1
900
71
0.75
3.00
1.5
930
72
0.75
4.00
2.2
945
76
0.72
5.80
3
945
70
0.75
7.30
4
940
79
0.75
9.70
0.12
655
51
0.59
0.58
0.18
675
51
0.66
0.78
0.25
670
52
0.62
1.12
0.35
655
61
0.76
1.16
0.55
650
65
0.76
1.62
0.75
665
65
0.77
2.15
1.1
675
72
0.76
2.90
1.5
710
72
0.71
4.25
2.2
695
76
0.71
5.90
3
700
79
0.69
7.90
4
715
77
0.72
10.40
SIMATIC - EM 300 Motor Starters GWA-4NEB 640070302-05
D-3
Page 70
Selection Help
SIMATIC - EM 300 Motor Starters
D-4
GWA-4NEB 640070302-05