Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact
Page 1 of SIMATIC ET 200S distributed I/O Power module PM-E DC24V (6ES7138-4CA01-0AA0) Manual

Spec sheet · Siemens

SIMATIC ET 200S distributed I/O Power module PM-E DC24V (6ES7138-4CA01-0AA0) Manual

Spec sheet18 pagesPDF 352 KB

Manual for the Siemens SIMATIC ET 200S PM-E DC24V power module (6ES7138-4CA01-0AA0): properties, parameters, diagnostics and configuration.

Download the PDF352 KB

Covers · 1 model

The models it covers

Summary

What is in it

The Siemens manual for the PM-E DC24V power module (6ES7138-4CA01-0AA0) of the SIMATIC ET 200S distributed I/O system, which monitors the supply voltage for the electronic modules in its voltage group. It lists the properties, terminal assignment, usable TM-P terminal modules, block diagram and technical data, the no load voltage diagnostic parameter, LED diagnostics and error types, and how to configure the address space. It supplements the ET 200S operating instructions.

Its parts

  1. Properties
  2. Parameters
  3. Diagnostics
  4. Configuring

From the sheet · read page by page

Key facts from this sheet

Each line names its page in the PDF.

Siemens SIMATIC ET 200S manual (edition 04/2007) for the PM-E DC24V power module 6ES7138-4CA01-0AA0. It describes the module's properties, terminal assignment, usable terminal modules, technical data, parameter, LED diagnostics, error type and address space. A reader can use it to wire, configure and troubleshoot the module.

Type
ET 200S power module that monitors the supply voltage of all electronic modules in its voltage group, fed through a TM-P terminal module p. 7
Rated load voltage
24 VDC p. 8, 10
Max. current
10 A (up to 60°C) p. 10
Terminals
2 and 6: L+; 3 and 7: M (chassis ground); A4 and A8: AUX1 (protective conductor or potential bus up to 230 VAC) p. 8
Terminal modules
TM-P15C23-A1, TM-P15C23-A0, TM-P15C22-01, TM-P15S23-A1, TM-P15S23-A0, TM-P15S22-01, TM-P15N23-A1, TM-P15N23-A0, TM-P15N22-01 p. 9
Usable modules
All electronic modules except 2DI AC120V ST, 2DI AC230V ST and 2DO AC24..230V/1A; the manual states it suits fail-safe modules p. 7
Address space
S: 1 input byte; O: 8 bytes in and out; SO: 9 bytes in and out (9th output byte not relevant) p. 7
LEDs
Red SF (group error) and green PWR (load voltage monitoring) p. 10
Isolation
Between rated load voltage and backplane bus, and between power modules; 500 VDC insulation test p. 10
Consumption
Max. 4 mA from L+ (no load); power dissipation typically 100 mW p. 10
Size and weight
Dimension B 15 mm; approx. 35 g p. 10
Temperature
Extended range 0 to 55°C with vertical installation p. 7
Parameter
Diagnostics: No load voltage, disable or enable (default disable); parameter length 3 bytes p. 10, 11
Error type
17D 10001: encoder or load voltage missing (supply voltage absent or too low) p. 14

What this sheet walks you through

  • Which electronic modules can share the power module's voltage group p. 7
  • Terminal assignment of the power module p. 8
  • Choosing a spring, screw-type or Fast Connect terminal module p. 9
  • Enabling the no load voltage diagnostic message p. 11
  • Reading the SF and PWR LEDs p. 13
  • Fixing a missing or low supply voltage error p. 14
  • Configuring the address space and status byte p. 15, 16

Good to know

  • Connect only the rated 24 VDC load voltage to the TM-P terminal module, matching the electronic modules' supply voltage. p. 7
  • The total current of all modules in a voltage group must not exceed the maximum current-carrying capacity. p. 7
  • Terminals A4 and A8 exist only on specified terminal modules. p. 8
  • With no load voltage, only the power module sends a diagnostic message, but the SF LEDs of all modules in the group light. p. 11

Questions this sheet answers

What does the Siemens PM-E DC24V 6ES7138-4CA01-0AA0 do?

It is an ET 200S power module that monitors the 24 VDC supply for all electronic modules in its voltage group. p. 7

How much current can a PM-E DC24V supply?

Its maximum current-carrying capacity is 10 A, up to 60°C. p. 10

Which terminal module does the 6ES7138-4CA01-0AA0 use?

A TM-P terminal module, such as the TM-P15C23-A1, TM-P15S23-A1 or TM-P15N23-A1 and their A0 and 22-01 variants. p. 9

Which modules cannot be used with the PM-E DC24V?

The 2DI AC120V ST, 2DI AC230V ST and 2DO AC24..230V/1A; all other electronic modules can be used. p. 7

What does error 10001 mean on a PM-E DC24V?

Encoder or load voltage missing: the supply voltage is absent or too low; correct the wiring and check the supply. p. 14

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. Power module PM-E DC24V (6ES7138-4CA01-0AA0)1
  2. Legal information2
  3. Preface3
  4. 1 Properties7
    1. 1.1 Power module PM-E DC24V (6ES7138-4CA01-0AA0)7
  5. 2 Parameters11
  6. 3 Diagnostics13
    1. 3.1 Diagnostics using LED display13
    2. 3.2 Error types14
  7. 4 Configuring15
    1. 4.1 Configuring the address space15
  8. Index17

From the PDF’s own bookmarks.

The whole text · 2 parts

Read the sheet here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 91-9
  2. Pages 10 to 1810-18

The file

Revision and size

Part no.A5E01119952-02
Revision04/2007
PublisherSiemens AG
Pages18
PDF352 KB
TextText from the PDF itself.
A5E01119952-02

The first pages · 4 of 18

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 18
Page 2
Page 2of 18
Page 3
Page 3of 18
Page 4
Page 4of 18