The text of a spec sheet · part 2 of 2
SIMATIC ET 200S distributed I/O Power module PM-E DC24V (6ES7138-4CA01-0AA0) Manual, pages 10 to 18
Pages 10 to 18 of 18
The original document is the PDF (352 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Page 10
Properties 1.1 Power module PM-E DC24V (6ES7138-4CA01-0AA0)
Technical data PM-E DC24V (6ES7138-4CA01-0AA0) Dimensions and weight Dimension B (mm)
15
Weight
Approx. 35 g Voltages, currents, potentials
Rated load voltage •
24 VDC No
Overvoltage protection
Protection with automatic circuit breakers
Yes, tripping characteristic B, C
Max. current-carrying capacity (up to 60°C)
10 A
•
No
Short-circuit protection
Electrical isolation •
Between rated load voltage and backplane bus
Yes
•
Between the power modules
Yes
Insulation test voltage
500 VDC
Current consumption •
From the load voltage L+ (no load)
Max. 4 mA
Power dissipation of the module
Typically 100 mW
Parameter length
3 bytes Status, interrupts, diagnostics
Diagnostic function
Yes
•
Group error
Red "SF" LED
•
Load voltage monitoring
Green "PWR" LED
•
Diagnostic information readable
Yes
Power module PM-E DC24V (6ES7138-4CA01-0AA0)
10
Manual, 04/2007, A5E01119952-02
Page 11
2
Parameters
Parameters The following table lists the power module parameters. Table 2- 1
Parameters for power modules PM-E DC24V
Diagnostics: No load voltage
Range of values Disable/enable
Default setting Disable
Applicability Power module
The parameters are explained below.
Diagnostics: No load voltage Use this parameter to enable a diagnostic message because there is no load voltage. If there is no load voltage, only the diagnostic message of the affected power module is sent to the DP master. The SF error LEDs of all modules in the relevant voltage group light up.
Power module PM-E DC24V (6ES7138-4CA01-0AA0) Manual, 04/2007, A5E01119952-02
11
Page 12
Parameters
Power module PM-E DC24V (6ES7138-4CA01-0AA0)
12
Manual, 04/2007, A5E01119952-02
Page 13
3
Diagnostics 3.1
Diagnostics using LED display
Power module LED displays on the power module:
① ②
Batch error (red) Load voltage (green)
Status and error displays by means of LEDs on power modules The table below shows the status and error displays on the power module. Event (LEDs) SF
Cause
Remedy
PWR
On
Off
No parameter assignment or incorrect module plugged in. A diagnostic message is pending.
Check the parameter assignment. Evaluate the diagnostics.
There is no load voltage at the power module.
Check the load voltage.
Power module PM-E DC24V (6ES7138-4CA01-0AA0) Manual, 04/2007, A5E01119952-02
13
Page 14
Diagnostics 3.2 Error types
3.2
Error types
Power module error types The diagnostic message is reported on channel 0 and applies to the entire module. The table below shows the types of errors affecting power modules Table 3- 1
Power module error types Error type
17D
10001: Encoder or load voltage missing
Meaning
Remedy
Supply voltage not present or too low.
Correct the process wiring. Check the supply voltage.
Power module PM-E DC24V (6ES7138-4CA01-0AA0)
14
Manual, 04/2007, A5E01119952-02
Page 15
4
Configuring 4.1
Configuring the address space
Address area for option handling and status byte You can control and monitor option handling, and evaluate the status byte of the power module using the control (PIO) and feedback interface (PII). The address range of the control (PIO) and feedback interface (PII) depends on how the corresponding entry in the configuration software is configured, or which entry has been selected. This table shows the PII feedback interface and the PIO control interface for different entries. Table 4- 1
PII feedback interface and PIO control interface
With STEP 7, HW Config or COM PROFIBUS or other configuration software Usual entry for the power module Ends in ...S
IBx
Ends in ...O
IBx :::
PII feedback interface
PIO control interface
---
---
Status byte
--QBx
Option handling
IBx+7 Ends in ...SO
QBx Option handling
IBx+7 IBx+8
Option handling
QBx+7
IBx :::
:::
:::
Option handling
QBx+7 Status byte
QBx+8
Not applicable
Power module PM-E DC24V (6ES7138-4CA01-0AA0) Manual, 04/2007, A5E01119952-02
15
Page 16
Configuring 4.1 Configuring the address space
Status byte for power modules
Figure 4-1
Assignment of status byte for power modules
Power module PM-E DC24V (6ES7138-4CA01-0AA0)
16
Manual, 04/2007, A5E01119952-02
Page 17
Index B Basic knowledge requirements, 3 Block diagram, 9
D Disposal, 3
I Internet Service & Support, 4
P Parameters For power modules, 11 Power modules Parameters, 11 Properties, 7
R Recycling, 3
S Scope Manual, 3 Service & Support, 4
T Technical data, 10 Technical Support, 4 Terminal assignment, 8 Training Center, 3
Power module PM-E DC24V (6ES7138-4CA01-0AA0) Manual, 04/2007, A5E01119952-02
17
Page 18
Index
Power module PM-E DC24V (6ES7138-4CA01-0AA0)
18
Manual, 04/2007, A5E01119952-02