Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a spec sheet · part 1 of 2

SIMATIC ET 200S distributed I/O Power module PM-E DC24V (6ES7138-4CA01-0AA0) Manual, pages 1 to 9

Pages 1 to 9 of 18

The original document is the PDF (352 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Siemens PM-E / 6ES7138-4CA01-0AA0

Page 1

Power module PM-E DC24V (6ES7138-

___________________ Preface

4CA01-0AA0)

1 ___________________ Properties

SIMATIC ET 200S distributed I/O Power module PM-E DC24V (6ES7138-4CA01-0AA0) Manual

04/2007

A5E01119952-02

2 ___________________ Parameters 3 ___________________ Diagnostics 4 ___________________ Configuring

Page 2

Legal information Warning notice system This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger. DANGER indicates that death or severe personal injury will result if proper precautions are not taken. WARNING indicates that death or severe personal injury may result if proper precautions are not taken. CAUTION indicates that minor personal injury can result if proper precautions are not taken. NOTICE indicates that property damage can result if proper precautions are not taken. If more than one degree of danger is present, the warning notice representing the highest degree of danger will be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property damage.

Qualified Personnel The product/system described in this documentation may be operated only by personnel qualified for the specific task in accordance with the relevant documentation, in particular its warning notices and safety instructions. Qualified personnel are those who, based on their training and experience, are capable of identifying risks and avoiding potential hazards when working with these products/systems.

Proper use of Siemens products Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems. The permissible ambient conditions must be complied with. The information in the relevant documentation must be observed.

Trademarks All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.

Disclaimer of Liability

We have reviewed the contents of this publication to ensure consistency with the hardware and software described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this publication is reviewed regularly and any necessary corrections are included in subsequent editions.

Siemens AG Industry Sector Postfach 48 48 90026 NÜRNBERG GERMANY

A5E01119952-02 Ⓟ 04/2014 Subject to change

Copyright © Siemens AG 2007. All rights reserved

Page 3

Preface Purpose of the manual This manual supplements the ET 200S Distributed I/O System Operating Instructions. General functions for the ET 200S are described in the ET 200S Distributed I/O System Operating Instructions (http://support.automation.siemens.com/WW/view/en/1144348). The information in this document along with the operating instructions enables you to commission the ET 200S.

Basic knowledge requirements To understand these operating instructions you should have general knowledge of automation engineering.

Scope of the manual This manual applies to this ET 200S module. It describes the components that are valid at the time of publication.

Recycling and disposal Thanks to the fact that it is low in contaminants, this ET 200S module is recyclable. For environmentally compliant recycling and disposal of your electronic waste, please contact a company certified for the disposal of electronic waste.

Additional support If you have any questions relating to the products described in this manual and do not find the answers in this document, please contact your local Siemens representative (http://www.siemens.com/automation/partners). A guide to the technical documentation for the various SIMATIC products and systems is available on the Internet. (http://www.siemens.com/simatic-docu). The online catalog and ordering systems are available on the Internet (http://www.siemens.com/automation/mall).

Training center We offer courses to help you get started with the ET 200S and the SIMATIC S7 automation system. Please contact your regional training center or the central training center in D -90327, Nuremberg, Germany (http://www.siemens.com/sitrain).

Power module PM-E DC24V (6ES7138-4CA01-0AA0) Manual, 04/2007, A5E01119952-02

3

Page 4

Preface

Technical Support You can contact Technical Support for all Industry Automation products by means of the Internet Web form for the Support Request (http://www.siemens.com/automation/csi_en_WW/support_request). Additional information about Siemens Technical Support is available on the Internet (http://www.siemens.com/automation/csi_en_WW/service).

Service & Support on the Internet In addition to our documentation, we offer a comprehensive knowledge base on the Internet (http://www.siemens.com/automation/csi_en_WW/support). There you will find: ● Our Newsletter, which constantly provides you with the latest information about your products. ● The right documentation for you using our Service & Support search engine. ● The bulletin board, a worldwide knowledge exchange for users and experts. ● Your local contact for Automation & Drives in our contact database. ● Information about on-site services, repairs, spare parts, and lots more.

Power module PM-E DC24V (6ES7138-4CA01-0AA0)

4

Manual, 04/2007, A5E01119952-02

Page 5

Table of contents Preface ................................................................................................................................................... 3 1

Properties ............................................................................................................................................... 7 1.1

Power module PM-E DC24V (6ES7138-4CA01-0AA0) ................................................................. 7

2

Parameters ........................................................................................................................................... 11

3

Diagnostics ........................................................................................................................................... 13

4

3.1

Diagnostics using LED display .....................................................................................................13

3.2

Error types ....................................................................................................................................14

Configuring ........................................................................................................................................... 15 4.1

Configuring the address space ....................................................................................................15

Index..................................................................................................................................................... 17

Power module PM-E DC24V (6ES7138-4CA01-0AA0) Manual, 04/2007, A5E01119952-02

5

Page 6

Table of contents

Power module PM-E DC24V (6ES7138-4CA01-0AA0)

6

Manual, 04/2007, A5E01119952-02

Page 7

1

Properties 1.1

Power module PM-E DC24V (6ES7138-4CA01-0AA0)

Properties ● The PM-E DC24V power module monitors the supply voltage for all the electronic modules in the voltage group. The supply voltage is fed in by means of the TM-P terminal module. ● You can use all the electronic modules except the 2DI AC120V ST, 2DI AC230V ST, and 2DO AC24..230V/1A in the voltage group of the PM-E DC24V power module. ● The current status of the power module is stored in the status byte in the process input image (PII). This is updated irrespective of whether the "No Load Voltage" diagnosis has been enabled. ● The PM-E DC24V power module is suitable for fail-safe modules. ● Extended temperature range from 0 to 55°C with vertical installation. CAUTION Only connect the specified rated load voltage of 24 VDC to the TM-P terminal module of the power module. The connected rated load voltage must correspond to the supply voltage of the electronic modules in the voltage group.

Maximum configuration per voltage group The number of modules that can be connected depends on the total current of all modules in a voltage group. This total must not exceed the maximum current carrying capacity.

Address space of inputs/outputs Address space of inputs/outputs by selecting the following as an option: Options

Address space of the inputs

Address space of the outputs

Status byte (S)

1 byte

--

Option handling (O)

8 bytes

8 bytes

Status byte and option handling (SO)

9-byte inputs

9 bytes (9th byte not relevant)

Power module PM-E DC24V (6ES7138-4CA01-0AA0) Manual, 04/2007, A5E01119952-02

7

Page 8

Properties 1.1 Power module PM-E DC24V (6ES7138-4CA01-0AA0)

General terminal assignment Note Terminals A4 and A8 are only available at specified terminal modules.

Terminal assignment for PM-E DC24V (6ES7138-4CA01-0AA0) Terminal

Assignment Terminal

Assignment

2

L+

6

L+

Notes •

L+: Rated load voltage 24 VDC

3

M

7

M

•

A4

AUX1

A8

AUX1

M: Chassis ground

•

AUX1: Protective-conductor terminal or potential bus (freely usable up to 230 VAC)

Power module PM-E DC24V (6ES7138-4CA01-0AA0)

8

Manual, 04/2007, A5E01119952-02

Page 9

Properties 1.1 Power module PM-E DC24V (6ES7138-4CA01-0AA0)

Usable terminal modules Usable terminal modules for PM-E DC24V (6ES7138-4CA01-0AA0) TM-P15C23-A1 (6ES71934CC30-0AA0)

TM-P15C23-A0 TM-P15C22-01 (6ES7193-4CD30- (6ES7193-4CE100AA0) 0AA0)

Spring terminal

TM-P15S23-A1 (6ES71934CC20-0AA0)

TM-P15S23-A0 TM-P15S22-01 (6ES7193-4CD20- (6ES7193-4CE000AA0) 0AA0)

Screw-type terminal

TM-P15N23-A1 (6ES71934CC70-0AA0)

TM-P15N23-A0 TM-P15N22-01 (6ES7193-4CD70- (6ES7193-4CE600AA0) 0AA0)

Fast Connect

Block diagram

Figure 1-1

Block diagram of the PM-E DC24V power module

Power module PM-E DC24V (6ES7138-4CA01-0AA0) Manual, 04/2007, A5E01119952-02

9