Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact
Page 1 of Signet 8550 Spec Sheet

Spec sheet · Signet

Signet 8550 Spec Sheet

Spec sheet4 pagesPDF 420 KB

All 4 pages are below, each with its text.

Download the PDF420 KB

Covers · 1 model

The models it covers

From the sheet · read page by page

Key facts from this sheet

Each line names its page in the PDF.

This is a four-page data sheet for the Signet 8550 ProcessPro flow transmitter. It describes the features, specifications, dimensions and mounting options, and lists the order numbers of the dual-channel field and panel mount packages and their accessories.

Device type
Converts the signal from frequency and digital (S3L) flow sensors into a 4 to 20 mA signal p. 1
Features
2 or 4 wire power; dual input and output; two optional relays; permanent and resettable totalizers; output simulation p. 1
Order numbers
3-8550-3 field mount package; 3-8550-3P panel mount package; both two inputs, two 4 to 20 mA outputs, two open collectors p. 4
Power
12 to 24 VDC ±10%, regulated p. 2
Current output
4 to 20 mA, isolated, passive, fully adjustable and reversible p. 2
Display
Alphanumeric 2 x 16 LCD p. 2
Keypad
Sealed 4-key silicon rubber p. 2
Enclosure
PBT resin; NEMA 4X/IP65 front face only on panel mount, field mount 100% NEMA 4X/IP65 p. 2
Operating temperature
-10 °C to 70 °C p. 2
Shipping weight
0.325 kg (0.7 lb) p. 2
Integral mount kits
3-8051 NPT, Valox; 3-8051-1 NPT, PP; 3-8051-2 NPT, PVDF p. 4
Mounting accessories
3-8050 universal mounting kit; 3-0000.596 heavy duty wall mount bracket and 3-5000.598 surface mount bracket (panel mount only) p. 4
Connectors, filter
3-9000.392 kit for rear cover (3 connectors); 3-9000.392-1 NPT; 3-9000.392-2 PG 13.5; 3-8050.396 RC filter kit for relay use p. 4
Integral mount sensors
With the 3-8051-X kit: Signet integral mount sensors 3-8510-XX and 3-8512-XX p. 3

What this sheet walks you through

  • Choosing panel, field (pipe, tank, wall) or integral mounting p. 3
  • Dimensions of the panel and field versions p. 3
  • Sizing the panel cutout p. 3
  • Ordering the transmitter packages, mounting kits and connector kits p. 4
  • Typical applications such as flow control, filtration regeneration and leak detection p. 1

Good to know

  • On the panel mount version only the front face is NEMA 4X/IP65. p. 2
  • The splashproof rear cover for the panel mount version is ordered separately. p. 3
  • The sensors and fittings in the system overview are sold separately. p. 3

Questions this sheet answers

What does the Signet 8550 flow transmitter do?

It converts the signal from frequency and digital (S3L) flow sensors into a 4 to 20 mA signal for long distance transmission. p. 1

What is the difference between the 3-8550-3 and 3-8550-3P?

The 3-8550-3 is the field mount package and the 3-8550-3P the panel mount package; both have two inputs and two 4 to 20 mA outputs. p. 4

What size panel cutout does the 8550 need?

92 mm X 92 mm (3.62 in X 3.62 in.). p. 3

Which kit mounts the 8550 on a pipe, tank or wall?

The field mount version uses the 3-8050 Universal Mount Kit. p. 3

Is the 8550 panel mount watertight at the back?

No: the panel mount is NEMA 4X/IP65 at the front face only; an optional splashproof rear cover can be ordered separately. p. 2, 3

The file

Size and text

Pages4
PDF420 KB
TextText from the PDF itself.

Every page · 4

Read it here

Each page as it is printed, and its words beside it, so a phone can search and copy them.

Page 1 of Signet 8550 Spec Sheet

The text of page 1, from the PDF itself

Signet 8550 Flow Transmitters Check out the 9900 Transmitter for your single channel needs

Features Member of the ProcessPro Family of Instruments ®

  • 2 or 4 wire power
  • Available with dual input & output
  • 4 to 20 mA scaleable outputs
  • Permanent & resettable totalizers
  • Relay options available
  • NEMA 4X enclosure with self-healing window

Panel Mount

Pipe, Wall, Tank and Integral Mount

  • Output simulation for complete system testing

MEASURING EQUIPMENT 77CJ

Signet 8550 Flow Transmitters are advanced instruments that convert the signal from frequency and digital (S3L) flow sensors into a 4 to 20 mA signal for long distance transmission. Configuration flexibility is maximized with dual input/output, two optional relays for process control, two packaging options for integral/ pipe mount or panel installation, and scalability for virtually any flow range or engineering unit. State-ofthe-art electronic design ensures long-term reliability, signal stability, and simple user setup and operation.

Applications

  • Flow Control and Monitoring
  • Filtration or Softener Regeneration
  • Effluent Totalization
  • Pump Protection
  • Feed Pump Pulsing
  • Ratio Control
  • Water Distribution
  • Leak Detection
Page 2 of Signet 8550 Spec Sheet

The text of page 2, from the PDF itself

Specifications

General Compatibility

Signet Flow Sensors with frequency outputs

Accuracy Display

± 0.5% of reading Alphanumeric 2 x 16 LCD

Update Rate Contrast

1 second User selectable, 5 levels

Materials EnclosurePBT resinKeypad

Sealed 4-key silicon rubber

Panel and Case Gasket

Neoprene

Window Electrical Power

Polyurethane coated polycarbonate

Sensor Input Range Sensor Power

Current Output Max. Loop Impedance

Update Rate Accuracy Relay Output Mechanical SPDT contacts Maximum Voltage Rating Hysteresis Maximum 400 pulses/min Open-Collector Output

12 to 24 VDC ±10%, regulated 100 mA max. 0.5 to 1500 Hz 2-wire: 5 VDC ± 1% @ 1.5 mA 3 or 4 wire: 5 VDC ± 1% @ 20 mA Optically isolated from current loop short circuit protected 4 to 20 mA, isolated, passive, fully adjustable and reversible 50 Ω max. @ 12 V 325 Ω max. @ 18 V 600 Ω max. @ 24 V 100 ms ±0.03 mA High, Low, Pulse, Off 30 VDC @ 5 A , 250 VAC @ 5 A resistive load User selectable

High, Low, Pulse, Off Optically isolated, 50 mA max. sink, 30 VDC max. pull-up voltage. User selectable for exiting alarm condition

Hysteresis Maximum 400 pulses/min. Environmental Operating Temperature

-10 °C to 70 °C

Storage Temperature Relative Humidity Enclosure

-15 °C to 80 °C 5 °F to 176 °F 0 to 95%, non-condensing NEMA 4X/IP65 (front face only on panel mount); field mount is 100% NEMA 4X/IP65

14 °F to 158 °F

Shipping Weight 0.325 kg

0.7 lb

Standards and Approvals CE, FCC, UL, CUL RoHS compliant, China RoHS Manufactured under ISO 9001 for Quality and ISO 14001 for Environmental Management and OHSAS 18001 for Occupational Health and Safety

www.gfsignet.com

Page 3 of Signet 8550 Spec Sheet

The text of page 3, from the PDF itself

Dimensions 3-8550-XP 96 mm (3.8 in.)

Field version with universal mount

96 mm (3.8 in.)

82mm (3.23 in.)

Optional Splashproof Rear Cover

41mm (1.6 in.)

92 mm (3.6 in.)

64mm (2.5 in.) 106mm (4.2 in.)

56 mm (2.2 in.) 97mm (3.8 in.)

Panel Mount Signet 8550 Flow Transmitter (Includes mounting bracket and panel gasket)

System Overview

42mm (1.7 in.)

Field Mount - Pipe, Tank, Wall Signet 8550 Flow Transmitter with 3-8050 Universal Mount Kit

Integral Mount Signet 8550 Flow Transmitter with 3-8051-X Integral Mount Kit

+ Signet Sensor 515 525 2100 2507 2537 2540 2552

2000 2536 2551

Signet Sensor 515 2507 2540 525 2536 2537 2000 2551 2552 2100

+ Signet Integral Mount Sensor 3-8510-XX 3-8512-XX

Signet Fittings

All sold separately

Ordering Notes 1) Use the field mount version to directly mount the instrument to the Model 515 or 2536 integral mount sensor. See sensor data sheet for more information. 2) Field mount and sensor can be ordered in a package. See Integral Mount for more information.

3) Panel cutout should be 92 mm X 92 mm (3.62 in X 3.62 in.). 4) An optional splashproof rear cover for the panel mount version can be ordered separately if needed.

Please refer to Wiring, Installation, and Accessories sections for more information. www.gfsignet.com

Page 4 of Signet 8550 Spec Sheet

The text of page 4, from the PDF itself

Ordering Information Mfr. Part No.

CodeInputOutputPowerTwo

Two 4 to 20 mA outputs and two open collectors for Hi, Lo, Pulse or Frequency

2 or 4 wire

Two

Two 4 to 20 mA outputs and two open collectors for Hi, Lo, Pulse or Frequency

2 or 4 wire

ProcessPro Flow Transmitter Field mount package 3-8550-3

159 000 051

Panel mount package 3-8550-3P

159 000 052

Accessories and Replacement Parts Mfr. Part No.

Code

Description

Mounting Accessories 3-8050

159 000 184Universal mounting kit3-8051159 000 187

Flow Sensor integral mount kit, NPT, Valox

3-8051-1

159 001 755

Flow Sensor integral mount kit, NPT, PP

3-8051-2

159 001 756

Flow Sensor integral mount kit, NPT, PVDF

3-0000.596

159 000 641

Heavy duty wall mount bracket (panel mount only)

3-5000.598

198 840 225

Surface mount bracket (panel mount only)

3-8050.395 3-9900.396

159 000 186 159 001 701

Splashproof rear cover (panel mount only) Angle adjustment adapter kit

Liquid Tight Connectors and Other 3-9000.392

159 000 368

Liquid tight connector kit for rear cover (includes 3 connectors)

3-9000.392-1

159 000 839

Liquid tight connector kit, NPT (1 connector)

3-9000.392-2

159 000 841

Liquid tight connector kit, PG 13.5 (1 connector)

3-8050.396

159 000 617

RC filter kit (for relay use)

3-8550.099 Rev F (4/13) © Georg Fischer Signet LLC 3401 Aero Jet Avenue, El Monte, CA 91731-2882 U.S.A. • Tel. (626) 571-2770 • Fax (626) 573-2057 • www.gfsignet.com • e-mail: signet.ps@georgfischer.com Specifications subject to change without notice. All rights reserved. All corporate names and trademarks stated herein are the property of their respective companies.