For the SMC EX120-SDN1
Page 1
Doc.No. EX## -OME0015
OPERATION MANUAL
SI unit EX120-SDN1 EX121-SDN1 EX122-SDN1 EX124D/U-SDN1
SMC Corporation
Page 2
SMC CORPORATION Doc.No.EX##-OME0015
Contents 1.Safety instructions
------------------------------------------------------ P3
2.Specifications 2-1.General specifications
------------------------------------------------------ P4
2-2.Electrical and network specifications ------------------------------------------------------ P4 2-3.Applicable solenoid valve series
------------------------------------------------------ P5
3.Wiring and setting 3-1.Connection type
------------------------------------------------------ P5
3-2.Address setting
------------------------------------------------------ P8
4.LED indicator and Physical dimensions 4-1.LED indication
------------------------------------------------------ P9
4-2.Physical dimensions
------------------------------------------------------ P9
5.EDS(Electronic Data Sheet) File
------------------------------------------------------ P12
6.Trouble Shooting
------------------------------------------------------ P13
-2-
Page 3
SMC CORPORATION
1.Safety instructions
Doc.No.EX##-OME0015
These safety instructions are intended to prevent a hazardous situation and/or equipment damage. These instructions indicate the level of potential hazard by label of "CAUTION" , "WARNING". To ensure safety, be sure to observe ISO, JIS and other safety practices.
CAUTION: Operator error could result in injury or equipment damage. WARNING: Operator error could result in serious injury or loss of life.
CAUTION Thoroughly read this manual and operate the product within the specified range. Follow the instructions. Do not drop or impart any impact to the product. Use within specified voltage range. Use outside of specified voltage will cause malfunction, damage of unit, electric shock, and fire. Do not touch the terminal or internal circuit board while they are energized. It may cause malfunction, damage to unit, and electric shock. Use within operating ambient temperature. Do not use where temperature can rapidly change even thought it is within the specifications. Foreign objects should be prevented from entering the product. Contamination by foreign objects, such as wire chips will cause fire, breakage, and malfunction. Use within the operating environment of the protection structure. In case of IP20, avoid use in the place where water and oil scatter. To realize IP65, install manifold properly and give some prevention against splash of liguid to electrical entry. Carry out periodical checks to confirm correct operation. Safety may not be maintained by unintentional malfunction or incorrect operation. Design must consider the space necessary for maintenance. As the contents of this manual is sometimes changed without the previous announcement, understand them beforehand, please. SI unit is not explosion proof. Operation in explosive enviromment may cause explosion accident.
WARNING The product specified here is designed to be used in standard factory automation equipment. Do not use in machinery and/or equipment where operators may be injured, and malfunction or failure may cause loss of life. Do not disassemble to repair or modify the product.
Connection CAUTION Power of the product and all other equipments should be turned off while wiring. Tighten the wiring with connector and tarminal screw completely. Short circuit, fire, and malfunction will be caused if connector and tarminal screw are not tightened enough. Avoid incorrect wiring. It may damage the product and/or other equipments. Ensure that the FG terminal is correctly grounded. Power with correct capacity should be prepared by considering the in-rush current when starting. Influence of noise should be avoided for the wiring. Wiring should be separated from power cables and high voltage cables. Ensure that the power is within the specified voltage range. Ensure that the cable is capable of supporting the solenoid valve and SI unit in terms of rating.
Applicable solenoid valves CAUTION SMC offers no guarantee against malfunction and damage of unit when valves not described to “2-3.Applicable solenoid valve series” and loads which is not valve are connected.
-3-
Page 4
SMC CORPORATION
2. Specifications 2-1. General specifications Item Model Operating ambient temp. Operating ambient humidity Storage ambient temp. Vibration proof Impact proof Noise immunity
Withstand voltage Insulation resistance Operating environment Weight Protection class
Doc.No.EX##-OME0015
Specifications EX120 EX121 EX122 EX124D EX124U -SDN1 -SDN1 -SDN1 -SDN1 -SDN1 0 to +55(with 8 points of valve ON) 0 to +50℃(with 16 points of valve ON) 35 to 85%RH(No dew condensation) -20 to +60℃ 50m/s2 (comply with JIS C 0911) 100m/s2 (comply with JIS C 0912) Normal mode ±1500 V Pulse 1µs Common mode ±1500 V Pulse 1µs Radiation 1000 V ±Pulse 1µs AC1000V for 1 min. between FG and external terminal package. DC500V, 2MΩ between FG and external terminal package. No corrosive gas and no dust 110g 140g 130g 240g or less or less or less or less IP20 IP65
2-2. Electrical and network specifications Item Applicable system Power supply voltage for communication Power supply voltage for solenoid valve Consumption Communication and current Internal power supply Power supply for Solenoid valve Solenoid valve Output style Connection Connected load spec.
Network connection spec.
Insulation type Residual voltage Applicable DeviceNet MAC ID setting range Baud Rate (Transmission speed) Slave (branch station) type Connection type Device type Product code Revision Vendor ID Corresponding message
Specifications DeviceNet Release 2.0 DC11V to DC25V (supplied by communication connector) DC24V +10% -5% 90mA or less (DC24V) 1.5A or less (DC24V) NPN output (Open collector) DC24V, Solenoid valve with lamp-surge voltage protection circuit of 2.1W or less. (made by SMC) Opt-coupler insulation type 0.4V DC or less VolumeⅠ- Release 1.2 VolumeⅡ- Release 1.1 0 to 63 (Set by Dip switch) 500kbps, 250kbps, 125kbps (Set by Dip switch) Group 2 only server T branch type, Multi drop type 16 288 Referred to EDS file. 7 Polled command (I/O message ), Explicit message
-4-
Page 5
SMC CORPORATION Doc.No.EX##-OME0015
SI unit I/O data (Receiving and sending data of polled command) Item Output(Poll request) Input(Poll response) Occupied byte 2 byte 2 byte (Solenoid valve output) Sending/ Address +0 Output No. 0 to 7 receiving data Address +1 Output No. 8 to 15 *) Mapping method of sending / receiving data is different by PLC. For further information, refer to the manual for PLC master (scanner) Offset 0 1
Bit of each output data and corresponding solenoid valve no. MSB LSB No.7 No.6 No.5 No.4 No.3 No.2 No.1 No.0 No.15 No.14 No.13 No.12 No.11 No.10 No.9 No.8
2-3. Applicable solenoid valve series SI unit Valve series EX120 VQ1000, VQ2000 EX121 VQ1000, VQ2000, SX3000, SX5000 EX122 SY3000, SY5000 EX124U/D VQ2000, VQ4000, VQ5000
3. Wiring and Setting 3-1.Connection type DeviceNet can be connected by T branch, Multi branch, Branch line branch and Multi drop. Total extension length of trunk and Branch line is different for different Baud rate and thickness of communication cable. Main line Terminal resistance
Terminal resistance Node
Multi branch Branch line
Node
Node Branch line
T branch
Branch line branch Node
Node Node
Node
Node Branch line
Node
Length of cable
Communication distance Thick cable Thin cable Terminal resistance
Baud rate 500 kbps 250 kbps 125 kbps Common
Total length of Length of Total length of trunk branch line branch line 100m or less 39m or less 6m or less 250m or less 78m or less 500m or less 156m or less 100m or less ―――――― 121 ohm (1/2W) -5-
Page 6
SMC CORPORATION Doc.No.EX##-OME0015
Cable specification Item Conductor cross section Colors
Thick cable Com m unication Power upply Signal
Thin cable Com m unication Power supply Signal
0.82 m m 2
1.65 m m 2
0.20 m m 2
0.33 m m 2
Blue, W hite 120Ω ± 10% (1MHz)
Red, Black
Blue, W hite 120Ω ± 10% (1MHz)
Red, B lack
Propagation delay
1.36ns / ft(m ax)
――
1.36ns / ft(m ax)
――
Attenuation rate
500k:0.25dB / ft 125k:0.13dB / ft 1.00M :0.40dB / ft
――
500k:0.50dB / ft 125k:0.29dB / ft 1.00M :0.70dB / ft
――
Conductor resistance
6.9Ω / 1000ft(m ax)
3.6Ω / 1000ft (m ax)
28Ω / 1000ft(m ax)
17.5Ω / 1000ft(m ax)
Im pedance
――
――
CAUTION For Multi drop connection, prepare plug connector for T branch separately. (Example, TMSTBP 2.5...- STF -5.08 made by Phoenix Contact Corp.) Use DeviceNet special cable for communication cable. Be sure to connect DeviceNet special terminal resistor with both ends of trunk.
-6-
Page 7
SMC CORPORATION Doc.No.EX##-OME0015
Wiring of cable for solenoid valve power supply and communication
Communication connector for DeviceNet Terminal Wire color Connected to VBlack (-) side of power supply cable CANL Blue Low side of communication cable FG Ground / Shield CANH White High side of communication cable V+ Red (+) side of power supply cable Power supply connector for solenoid valve Terminal Wire color Connected to 24V (+) side of solenoid valve source supply 0V (-) side of Solenoid valve source supply
CAUTION • Before wiring, be sure to turn power supply off. • Screw for connectors is M3. Tighten them properly by torque of 0.5 to 0.6 [N·m]. • SI unit isn’t available for monitoring of power supply for solenoid valve. • Do not put cable specified by DeviceNet with/near high voltage line or strong electric line such as driving line.
-7-