Manual · SMC
Operation Manual, SI unit EX120-SDN1, EX121-SDN1, EX122-SDN1, EX124D/U-SDN1
Manual13 pagesPDF 296 KB
Operation manual for SMC EX120, EX121, EX122 and EX124D/U-SDN1 DeviceNet serial interface (SI) units for valve manifolds.
What this file really is
The old site listed this file as “Oper Manual” for the SMC EX120-SDN1 and EX240-IE1. The file is named as an operation manual for the EX240-IE1, but it covers the EX120, EX121, EX122 and EX124D/U-SDN1 DeviceNet SI units and does not mention the EX240-IE1.
Names · 1 model
The models it names
Filed with · 1 model
Also filed with these models on the old site
Summary
What is in it
SMC operation manual for the EX120-SDN1, EX121-SDN1, EX122-SDN1 and EX124D/U-SDN1 serial interface (SI) units, which connect SMC solenoid valve manifolds to a DeviceNet network. It covers safety instructions, general, electrical and network specifications, the applicable valve series, connection types and cable lengths, wiring, node address and baud rate setting by DIP switch, LED indications, physical dimensions, the EDS file and troubleshooting.
Its parts
- Safety instructions
- Specifications
- Wiring and setting
- LED indicator and Physical dimensions
- EDS (Electronic Data Sheet) File
- Trouble Shooting
From the manual · read page by page
Key facts from this manual
Each line names its page in the PDF.
SMC operation manual for the DeviceNet SI units EX120-SDN1, EX121-SDN1, EX122-SDN1 and EX124D/U-SDN1, which drive solenoid valve manifolds. It does not cover the EX240-IE1. It gives the specifications, compatible valve series, cable wiring, DIP switch address and speed settings, LED meanings, dimensions, the EDS file and troubleshooting.
- Device
- DeviceNet serial interface (SI) unit for SMC solenoid valve manifolds p. 12
- Network
- DeviceNet Release 2.0, Group 2 only server; polled I/O and explicit messages p. 4
- Power
- Communication DC11V to DC25V from the DeviceNet connector; valves DC24V +10% -5% p. 4
- Valve outputs
- 16 NPN open collector outputs (2 bytes) for 24 VDC SMC valves of 2.1W or less with surge protection p. 4, 5
- Address, speed
- MAC ID 0 to 63; 500, 250 or 125 kbps; both set by DIP switch p. 4, 8
- Factory setting
- Node address 63, 125 kbps p. 8
- Valve series
- EX120: VQ1000, VQ2000; EX121: VQ1000, VQ2000, SX3000, SX5000; EX122: SY3000, SY5000; EX124U/D: VQ2000, VQ4000, VQ5000 p. 5
- EDS identity
- EX120-SDN1: vendor code 7, product type 16, product code 288 p. 12
- DeviceNet connector
- V- black, CANL blue, FG shield, CANH white, V+ red; separate 24V/0V valve power connector p. 7
- Connector screws
- M3, tightened to 0.5 to 0.6 N·m p. 7
- Terminators
- 121 ohm (1/2W) DeviceNet terminal resistor at both ends of the trunk p. 5, 6
- Operating temperature
- 0 to +55 with 8 valves on, 0 to +50℃ with 16 valves on; 35 to 85%RH p. 4
- Indicators
- PWR (green) and MOD/NET (green or red, steady or flashing) LEDs p. 9
What this manual walks you through
- Mapping output bits to solenoid valve numbers p. 5
- Choosing a DeviceNet connection type, cable and lengths p. 5, 6
- Wiring the communication and valve power connectors p. 7
- Setting the node address and speed with the DIP switch p. 8
- Reading the PWR and MOD/NET LEDs p. 9
- Physical dimensions of each SI unit p. 9, 10, 11
- Using the EDS file when the scanner does not recognize the unit p. 12
- Troubleshooting by MOD/NET LED state p. 13
Good to know
- The manual states the SI unit is not explosion proof and must not be used in an explosive environment. p. 3
- The SI unit does not monitor the solenoid valve power supply. p. 7
- Outputs are cleared when a communication error occurs. p. 8
- After a red MOD/NET error the unit does not recover by itself; cycle its communication and internal power. p. 13
- Switch off the communication power before changing the DIP switch settings. p. 8
Questions this manual answers
What is the default node address of the SMC EX120-SDN1?
It ships set to node address 63 at 125 kbps. p. 8
Which valve series work with the EX120-SDN1?
The VQ1000 and VQ2000 series. p. 5
What does a solid red MOD/NET LED mean on the EX120-SDN1?
A node address duplication or BUS OFF error; check addresses, noise and the 121 ohm terminators, then cycle the power, since the unit does not recover by itself. p. 9, 13
What power does the EX120-SDN1 need?
11 to 25 VDC through the DeviceNet connector for communication, plus 24 VDC (+10% -5%) for the valves. p. 4
What DeviceNet IDs does the EX120-SDN1 EDS file give?
Vendor code 7, product type 16 and product code 288. p. 12
The whole text · 2 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.