Operation Manual, SI unit EX120-SDN1, EX121-SDN1, EX122-SDN1, EX124D/U-SDN1, pages 8 to 13

Pages 8 to 13 of 13

The original document is the PDF (296 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the SMC EX120-SDN1

Page 8

SMC CORPORATION Doc.No.EX##-OME0015

3-2. Address setting Before setting of address by DIP switch, turn power supply for communication cable in SI unit “OFF”. Setting (binary) of following items is available by DIP switch installed to cover. 1) Node address (00 to 63) 2) Communication speed (125kbps, 250kbps, 500kbps)

ON

<Setting of node address> Node SW1 SW2 address 1 2 #0 0 0 #1 1 0 #2 0 1 : : : #62 0 1 #63 1 1

SW3 4 0 0 0

SW4 8 0 0 0

SW5 16 0 0 0

SW6 32 0 0 0

1 1

1 1

1 1

1 1

<Setting of communication speed> Setting Max. transmission distance (m) Communication Length of trunk Length SW7 SW8 speed (kbps) of Total length Thick Think branch of cable cable line branch line 0 0 125 500 156 100 6 1 0 250 250 78 0 1 500 125 39 1 1 Not used Not used

CAUTION • When shipped, node address of 63 and communication speed of 125kbps are set in advance. • When communication error occurs, output condition is cleared.

-8-

Page 9

SMC CORPORATION

4.LED indicator and Physical dimensions

Doc.No.EX##-OME0015

4-1 LED indication EX120-SDN1

EX124D-SDN1

EX121-SDN1 EX122-SDN1

EX124U-SDN1

Indication PWR

Contents Green Lights up when power for DeviceNet line is supplied. Lights off SI unit isn’t on line or power supply for communication line isn’t turned on. Green Waiting for connection (ON line) flashing Green Connection completed (ON line) lights up Red Connection time out (Minor communication error) flashing Red MAC ID duplication error or BUS OFF error lights up (Major communication error)

MOD / NET

4-2 Physical dimensions SI unit (EX120-SDN1)

SMC

SERIAL UNIT

SWITCH SETTINGS

STATION ADDRESS

TRANSMIT SPEED

1 ON 0 1 2 3 4 5 6 7 8 0 1 2 62 63 125K 250K 500K

1 2 4 8 16 32 0 0 0 0 0 0 1 0 0 0 0 0 0 1 0 0 0 0 0 1 1 1 1 1 1 1 1 1 1 1 0 0 1 0 0 1 1 1

10.2

28.8

-9-

Page 10

SMC CORPORATION Doc.No.EX##-OME0015

SI unit (EX121-SDN1)

Flat cable length about 70mm

SMC

5.4

SERIAL UNIT

SWITCH SETTINGS

1 ON 0 1 2 3 4 5 6 7 8 0 1 2

60.8

66.1

STATION ADDRESS

TRANSMIT SPEED

62 63 125K 250K 500K

64

1 2 4 8 16 32 0 0 0 0 0 0 1 0 0 0 0 0 0 1 0 0 0 0 0 1 1 1 1 1 1 1 1 1 1 1 0 0 1 0 0 1 1 1

10.2

28.8

2

SI unit (EX122-SDN1)

- 10 -

Page 11

SMC CORPORATION Doc.No.EX##-OME0015

SI unit (EX124D-SDN1) SI unit (EX124U-SDN1)

19

11.6

53.8

114

5.5

19.8

67 (72.5)

4-G(PF)1/2

- 11 -

Page 12

SMC CORPORATION

5.EDS (Electronic Data Sheet) File

Doc.No.EX##-OME0015

The EDS File is a file which described ID information on SI unit and important information in the operation. The DeviceNet controller or scanner automatically recognizes the SI unit by referring to the EDS File. * Please refer to the undermentioned list when DeviceNet controller or the scanner dose not automatically recognize the EDS File. $ Electronic Data Sheet File for $ SMC EX120-SDN1 Serial Interface Unit [File] DescText = "SMC EX120-SDN1 EDS File"; CreateDate = 05-20-1999; CreateTime = 10:30:00;

$ created

Revision = 1.1;

$ Revision of EDS

[Device] VendCode = 7; VendName = "SMC Corp."; ProdType = 16; ProdTypeStr = "General Motion Controller"; ProdCode = 288; MajRev = 2; MinRev = 7;

$ Device Major Revision $ Device Minor Revision

ProdName = "Valve Manifold SIU"; Catalog = "EX120-SDN1"; [IO_Info] Default = 0x0001;

$ Poll(Bit 0)

PollInfo = 0x0001 , 1 , 1;

$ Prod. Cnxn=1 $ Cons. Cnxn=1

Input1 = 2,

$ 2 byte

0, 0x0001,

$ All bits are significant $ Poll Only Connection

"Solenoid Status",

$ Name String

6, "20 04 24 05 30 03",

$ Path Size $ Assy Obj Inst 5 Attr 3

"";

$ Help String

Output1 = 2, 0,

$ 2 byte $ All bits are significant

0x0001,

$ Poll Only Connection

"Solenoid Output", 6,

$ Name String $ Path Size

"20 04 24 23 30 03",

$ Assy Obj Inst 23 Attr 3

"";

$ Help String

- 12 -

Page 13

SMC CORPORATION Doc.No.EX##-OME0015

6. Trouble Shooting MOD/NET LED Lights off

Green flashing

Red flashing

Red lights up

Cause & Countermeasure PWR LED lights off <Countermeasure> Confirm that power for SI unit circuit is supplied. Confirm correct wiring. If above countermeasures do not improve status, please exchange SI unit. PWR LED lights up <Countermeasure> Confirm that baud rate is set correctly. If MOD/NET LED lights off in spite of baud rate is set correctly, change SI unit. Connection waiting Shows communication waiting status between SI unit and master. <Countermeasure> Confirm master operate correctly. If using scan list, ensure slave is recorded to scan list correctly. Communication wire disconnected error <Countermeasure> Confirm communication wire is not disconnected. <Remark> Red flashing if master power source is turned off during communication. Node address overlapping error <Countermeasure> Confirm there is no overlapping on the node address. BUS OFF error Detects communication error. <Countermeasure> Case 1 Communication error due to noise. Confirm there is no component or high voltage cable that generate noise around communication wire. Make some distances between communication wire and noise source. Case2 Communication cable problem. Confirm terminal resistance (121ohm) connects to the both ends of communication wire that is main wire of communication wire. If red MOD/NET LED is still lights up in spite of above countermeasures, change SI unit.

CAUTION When red MOD/NET LED is lit, even if cause is solved, SI unit do not do auto-recovery. In this case, please reset the power to SI unit circuit (Communication/Internal power supply). SI unit isn’t available for monitoring of power supply for solved valve.