Class 8030 Type CRM-210, 211, 220, 222 Local/Remote Interface Modules: SY/MAX Troubleshooting Guide
Pages 1 to 6 of 21, from Class 8030 Type CRM-210, 211, 220, 222 Local/Remote Interface Modules
The original document is the PDF (1.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Square D 8030-CRM-210, Square D 8030-CRM-220, Square D 8030-CRM-222, Schneider 8030-CRM-210, Square D 8030-CRM-211, Schneider 8030-CRM-220 and Schneider 8030-CRM-222
Page 1
3.12 Class 8030 Type CRM-210, 211, 220, 222 Local/Remote Interface Modules
The SY/MAX Class 8030 Type CRM-210,211 Local Interface and CRM-220, 222 Remote Interface modules provide a method to remotely locate both digital and register I/O racks from a SY/MAX Model 300, 400, 500 or 700 Processor and to communicate in a serial fashion.
To establish a remote I/O system a Local Interface (LI) module is mounted in the rack containing the SY/MAX Processor and the Remote Interface (RI) module is mounted in the remote digital or register rack, referred to as a drop.
3.12.1 SPECIFICATIONS
ELECTRICAL The CRM-210, 211, 220 and 222 are UL listed.
Current Draw on
SY/MAX
Power Supply ....... CRM-210, 211 = 1600 mA. CRM-220, 222= 1000 mA.
CAPABILITIES
Local Interface
Registers ........... CRM-210 contains 512 registers (255 for forcible external I/O, 257 for internal data storage*). CRM-211 contains 4096 registers (255 for forcible external I/O, 3841 for internal data storage*).
Local Interface
Channels ........... 2 Channels per Local Interface, 255 registers for digital 1/O per module. 8 drops per channel, max
Remote Drops ....... 127 registers per drop max.
Communications .... Continuous, full duplex, serial differential (RS-422)
at 31.25K baud.
Drop Configuration .. Daisy Chain
*Unused external registers may also be used for internal data storage. All registers used for interna! data storage are retentive.
Recommended Communication Cable Specifications
BELDEN 8723 | BELDEN 9463
Conductor-Conductor 35 pF/ft. 19.7 pF/ft. Capacitance Wire Size 22 gauge 20 gauge Conductors/Cable 4 2 (2Cables
Required) Recommended 7500 ft. 10,000 ft. Maximum Distance (2250 m.) (3048 m.)
Compatibility
With Processors The LI/RI system is compatible with all Model 400, 500 and 700 processors. Models 500 and 700 support up to seven LIs while Model 300 can support one. The Model 300 processors in the following table are compatible.
PROCESSOR PROCESSOR SERIE$* |
Without C ! With Con
Type Function Function SCP-311 EtoF Gor later SCP-312 EtoF Gor later SCP-313 DtoF Gor later SCP-321 DtoF Gor later SCP-322 DtoF Gor later SCP-323 CtoF Gor later SCP-332 DtoF Gor later SCP-333 DtoF Gor later SCP-344 CtoF Gor later
Processors with series designations earlier than these selected in Table 3.1 have local /O capability only and can force only the first 16 registers while these listed processors can force the first 32 registers.
** Control Functions Consist of:
1. Programmed Halting of Drops 2. Failure Override 3. Auto Restart upon Communications Loss 4. Freeze or Reset Outputs on Communications Loss TABLE 3.1 - Model 300 Li Compatibility Compatibility WithlV/O ....... All 32, 16 and 8 function I/O, all 4 function input modules. Series B or later 4 point output modules. Register Modules: All compatible. Class 8030 Type CRM-115/ 116, Bus Driver/ Terminator Series =D. Compatibility With Racks ..... The CRM-210/211 is compatible with all racks except the CRK- 100 and 200. The CRM-220 is compatible with all four function digital racks. ENVIRONMENTAL Ambient Temp. .......... Operational: 0°C-60°C (32°-140°F) Storage: -40°C-80°C (-40°- 176°F) Humidity ...... 5% to 95% non-condensing
Page 2
3.12.2
LI/RI LED INDICATORS
Each LI and RI has several diagnostic LEDs to simplify system troubleshooting. The LEDs indicate diagnostic information such as the status of the communication link, individual drop operation, and module operation.
LOCAL INTERFACE
All lights OFF indicates loss of 5VDC power.
ON-
OFF-
FLASHING-
RUN (green)
Indicates L] is operational and CPU is accessing image table information.
Indicates LI is in self-diagnostics or has failed.
Indicates L] is running but one or more drops on its channels have been programmed to halt. (Controlled by bits 1-8 of the LI channel contro! register.)
ON-
OFF-
FLASHING-
HALT (red)
Indicates LI is in self-diagnostics and/or has halted operation.
Indicates L] is fully operational and CPU is accessing image table information.
Indicates LI is running but one or more drops on its channels have been programmed to halt. (Bits 1- 8 of the LI channel control register.)
ON-
OFF- FLASHING-
CHANNEL ERROR (red)
Indicates LI cannot communicate with one or more of its drops which are shutdown.
Indicates all drops operational.
Indicates a module failure ona drop has caused a drop to shutdown on this channel.
ON-
OFF-
FLASHING-
MODULE ERROR (red)
Indicates a self diagnostic error or internal timeout error has been recognized and halted the CPU.
Indicates LI is operational even though a channel HALT or CHANNEL ERROR LED may be ON.
Not valid
Table 3.2 -L! LED Explanation
REMOTE INTERFACE
All lights OF
F indicates loss of 5VDC power.
ON- OFF-
FLASHING-
RUN (green) Indicates remote drop is operational.
Indicates RI is shutdown or has not been initialized. Outputs will de- energize unless the shutdown is the result of a communication error and the Freeze function is also selected. Indicates CPU is in Disable Outputs mode. (50% ON, 50% OFF alter- nately with HALT LED.)
ON-
OFF-
FLASHING-
BLINKING-
HALT (red)
Indicates RI is shutdown. Ifthe only LED ON, it indicates rack was shut down due to program control or has not been initialized .
Indicates Remote drop is operational.
Indicates CPU is in Disable Outputs mode. (50% ON, 50%OFF alter- nately with RUN LED.)
Indicates LI HALT bit for the drop is set. (95% ON, 5% OFF, alternately with RUN LED.)
CHANNEL ERROR (red)
ON-
OFF-
Indicates invalid or loss of communications between RI and LI, HALT LED wil! also be ON.
Indicates valid communication be- tween RI and LI.
ON-
OFF-
FLASHING-
VO ERROR (red)
(HALT LED will also be on.)
This condition indicates either:
> Read after write error to an output. » Error caused by a malfunctioning register module.
>RI malfunction.
Indicates RI is properly communi- cating with modules in same rack.
Indicates outputs and inputs are frozen (ON or OFF).
ON-
OFF-
FLASHING-
MODULE ERROR (red) Indicates a self diagnostic error or internal timeout error has occurred.
Indicates RI is operational although drop may be shutdown due to system shutdown or program control.
Not valid
Ta ble 3.3 - Rt LED Explanation
Page 3
MODEL 500 arrangement
SLOT 1 2 3 4 5
CPU MODEL 500 ul
SLOT
CHANNEL 1 CHANNEL 2
LIIN REGISTER RACK WITH MODEL 500
CHANNEL 1
MODEL 300 and 400 arrangement
2 $1 SLOT 1 2 3 4 5 300 300 or or 400 400
Ll vO ul
\
CHANNEL 2 CHANNEL 4 CHANNEL 2
LLIN DIGITAL RACK WITH MODEL 300 or 400
LHIN REGISTER RACK WITH MODEL 300 or 400
Figure 3.3 - Local Interface Location
3.12.3 MODULE LOCATION
3.12.3.1 Local Interface
The Local Interface module (LI) must be placed in the same rack assembly as the processor (CPU). When a register rack is used to house the CPU, we recom-mend the LI module be placed in the next closest slot. If more than one LI module is required, place additional modules in adjacent slots.
3.12.3.2 Remote Interface
The Remote Interface module (RI) must be placed in the CPU slot (slot #1) of any rack which is to be a drop. Only one RI is allowed for each drop.
SLOT 1 2 3 4 5 RI IN REGISTER RACK RI FROM LOCAL RACK (CHANNEL 1 OR 2) SLOT 2 1 RI IN DIGITAL RACK Ri vo
FROM LOCAL RACK (CHANNEL 1 OR 2)
Figure 3.4 - Remote Interface Location
3.13.4 INSTALLATION IN A RACK ASSEMBLY Power must be removed from the rack assembly before installing or removing the Local or Remote Interface Modules.
After the removal of power, release the latching clamp and insert the module into the appropriate register slot until firmly seated and aligned on the stud located above the socket for the slot. Close the latching clamp and be sure to tighten the captive screw to insure the module is secured and properly grounded. To remove the module, first remove power; then release the latching clamp, loosen the captive screw at the bottom and pull the module out of the slot using the finger tab located on the top of the module.
Note: Refer to] Section 8.0|/for proper grounding procedures. 3.12.5 FIELD WIRING 3.12.5.1 Power Connection
No external power wiring is required. The LI and RI modules receive their power through the edge connector socket of the rack assembly. Insert the LI module in the register slot until firmly seated and aligned on the stud (the middle post above the socket in that slot) and tighten the captive mounting screw at the bottom of the module. These two connections not only provide support for the module but also provide a ground.
Page 4
3.12.5.2 Communication Cable
The communication between the L] and RJ modules is achieved via a dual shielded twisted pair cable. In order to minimize the potential of electrical interference:
1. Route communication cable in different wire ducts (enclosed metal ducts) than the power wiring is routed.
2. Connect each end of the communications cable shield to the shield terminal! on each module. Do not connect this shield to an external ground point since the SHIELD terminals are capacitively coupled to ground.
Transmission cable should be electrically equivalent to:
CONDUCTOR- capLetype | MANMUM | CONDUCTOR CAPACITANCE Belden 8723 7,500 feet 35 pf/ft. 2250 meters Belden 9463* 10,000 feet 19.7 pf/ft. 3048 meters
*Dual cables required.
Table 3.4 - Recommended Cable Distance
Note: ADDITIONAL DATA LINE PROTECTION
In environments where lightning or induced transients over communication lines are likely to cause hardware failures, signal line protection devices are recommended. Even though transient protection is designed into SY/MAX communication circuits, additional specialized protection devices are suggested in areas where there is a high probability of secondary lightning strikes occurring. The specific environments which are of greatest concern are communication cable runs in the outside environment. Refer ta Section 8]on Installation, Additional Data Line Protection, for recommended wiring and protection devices.
3.13.5.3
The| wiring method from one module to the next must be in daisy chain configuration. A branch may contain up to 8 drops per LI channel. The total allowable cable distance for each channe sing Belden 8723 cabling is 7500 feet ee| tale 54h Always connect the shield wire to the shield terminals.
Local/Remote Interface Connections
LOCAL REMOTE INTERFACE INTERFACES
(1) 1X1 a) Rx O - -4 -O
RED (2) TX2 Q BLACK
(2) AX2 O - BLACK 3) EN a) 1x1 QSREE AX! GRE (4)_ AX2_ py WHITE A) Bx2 o
(4) 1x2 O - SHIELO @ - SHIELD Q SHIELD
REO
WHITE
= FMZ2Y~r50
SHIELD
DROP #1 a) RX® jn) Txt RED |
(2) AX2@ R (2) TX2 2 BLACK
(3) 11 @ (3) RX1 Q GREEN (4) ™2@ w (4) AX2 O WHITE SHIELD @
SHIELD
SHIELD LJ ~O-
' DROP #2 oO
S CMZZYPXIO
(1) 1X1 +- - _ - - -@ (2) TX2 - - - - -2
(3) AX1 po OD (4) AX2 pa RD SHIELD $2
OROP #8
Figure 3.5 - LI/RI Wiring Connections
3.12.6 Ri DIP SWITCH SETTINGS
The RI Module hag four dip switchesjon the rear of the module near the edge of the circuit board. A module must be assigned as one of the eight drops on a specific channel. The switches must be set for the system to operate properly.
Page 5
Set the switches for the appropriate drop as shown in Either one of thesq labels will be located on the side of Figure 3.6} RI switch settings. the RI module.
CAUTION: SET SWITCHES BEFORE INSERTING MODULE 1234 Ion Circuit q HA ON Board prop sevect |*0P SWITCHES xix]xt 1 x{xfo| 2 REAR VIEW XJOIXx] 3 DROP 1 23 4 8030 CRM 220, 222 xlolol « n 0 with Switches Set O|xKIx] 5 #1 a ' For Drop #1 0}x{O} 6 olo|x] 7 0/0}O! 8 #2 = [* 1 iz ION 1 O-OFF (OPEN) L__ LINK TERMINATOR #3 * 11 SWITCH: ii 1 LAST DROP: SWITCH ON. ALL OTHERS: wa |e 0 SWITCH OFF. | | ' #5 * 0 1 #6 * 0 CAUTION: SET SWITCHES BEFORE INSERTING MODULE 1 SWITCH 1 2 3 4 SWITCH 1 2 3 4 * IF LAST DROP DROP 1/#/D/DjD DROP 5/#/U/D/D #7 * 0 OF CHANNEL. SET 2|#/0/0/U 6/#/UjO[U 1 SWITCH DOWN (D) 3{#]0/U|D 7\#|U/U1D OTHERWISE UP (U) 4(#)O}uUTU 8 Le] UjulU #8 * 0 1
Figure 3.7 - RI Module Labels
* For each channel, the drop (RI module) farthest from the LI must have switch 1 set ON, to a (1). Only one drop per channel requires this switch to be set. Failure to do so will result ina more noise susceptible communications link.
Figure 3.6 - RI Switch Settings
Label terminology may vary. The following equivalent terms are used:
0 O UP OPEN OFF Xx DOWN CLOSED ON
Page 6
3.12.7 Li/Ri POWER-UP SEQUENCE
The following describes the power-up sequence for the LI/RI system.
3.12.7.1 LI Light Sequence
The following sequence of events occurs when the LI is energized, or the processor keyswitch goes from HALT to RUN or DISABLE OUTPUTS:
1. The MODULE ERROR LED blinks ON, OFF, ON, OFF, and remains OFF if no detected error* exists within the LI.
2. The CHANNEL ERROR and HALT LEDs are ON and turn OFF when all the self-diagnostic routines are completed.
3. The green channel RUN LED will turn ON when the LI is communicating.
*The MODULE ERROR LED will turn ON if this module has initiated a rack error condition, thus halting the system when:
1. Aself-diagnostic error occurs.
2. Missing defined racks are detected (unless the Failure Override Bit is ON (=1).
3. An illegal rack addressing map is detected.
3.12.7.2 RI Light Sequence
The following sequence of events occurs when the RI is energized:
1. Allred LEDs turn ON and then OFF.
2. The red HALT LED will turn OFF when the green RUN LED turns ON.
3. The green RUN LED turns ON when the RI is communicating to its rack assembly and the CPU is in Run or Disabled Outputs.
When the processor keyswitch goes from HALT to RUN or DISABLE OUTPUTS, only steps 2 and 3 occur.
The MODULE ERROR LED will remain ON only when a self-diagnostic error is detected.
3.12.7.3 LIURI Initialization
1. When power is applied, self-diagnostic routines are initiated and verified within the LI, RI, CPU, and other register modules. Completion of the self-diagnostics insures that these modules are operational].
2. The LI then verifies communications with all of its drops.
3. The CPU will initiate the loading of the user defined rack addressing map into the LI.
If valid LI/RI communications cannot be established, an error is generated by the LI module. This error will halt the processor unless the failure override bit of that LI channel contro! register has been set ON
(1).
Special
Note: When initially keyswitching the processor from HALT to DISABLE OUTPUTS or RUN, a processor that has a new “out of the box” LI installed will remain in HALT and the LI will indicate a MODULE ERROR. The processor error register (8175) will identify the LI in error, and the LI error register will contain error code 901. This is a normal occurrence, reflecting the fact that the LI storage registers are corrupt (contain random data). Keyswitching the processor from HALT to DISABLE OUTPUTS or RUN a second (or third) time will clear the error.