3.13 Class 8030 Type CRM-230,232 Local and Remote Transfer Interface Modules

The SY/MAX Transfer Interface System enables redundant SY/MAX Model 400, 500=M or 7002C Processors to control a common I/O system. The system will transfer control of the I/O system to a backup processor should the primary shut down for any reason. I/O communication occurs in serial fashion.

A SY/MAX Transfer Interface System consist of two or more Class 8030 Type CRM-230 Local Transfer Interface (LTI) Modules and one or more Class 8030 Type CRM-232 Remote Transfer Interface (RTI) Modules.

3.13.1 TRANSFER INTERFACE SYSTEM

SPECIFICATIONS ELECTRICAL

Rated Current Draw On SY/MAX Power Supply CRM-230: 1600 mA

CRM-232: 1000 mA

CAPABILITIES Registers (CRM-230) 4096 (255 for external drop addressing, 3841 for internal data storage)

1 1/O Channel per LTI 255 Registers maximum 1024 Digital I/O max. (2048 if 24VDC)

8 Drops maximum

I/O Channel

128 Digital 1/O maximum (256 if 24VDC)

127 Registers per drop maximum

Register Transfer

Channel .............. 1 Register Transfer Channel per LTI. 32 Registers transferable perscan. Upto 4096 Registers transferable upon system startup

Communication

Method ............... Continuous full duplex serial (RS422A)

Transmission Rate

VOChannel .......... 62.5K baud

Transmission Rate

Register Transfer

Channel .............. 375K baud

Transmission Distance

VYOChannel .......... 2500 feet (762 meters)

Transmission Distance Register Transfer Channel

Compatibility With Racks ...........

Compatibility With Processors

25 feet (7.62 meters)

All racks

The Transfer Interface System is compatible with the Model 400, the Model 500 (Series M or later) and the Model 700 (Series C or later) processors. The Transfer Interface System is not compatible with Model 300 processors. ENVIRONMENTAL Ambient Temp. ...... 0 to 60°C Storage Temp. ........ -40 to 80°C Humidity ............ 5 to 95% non-condensing 3.13.2 LTI/RTI LED INDICATORS

The Local and Remote Interface Modules have the following LED indicators:

LOCAL TRANSFER INTERFACE

RUN (green)

HALT (red)

CHANNEL ERROR (red) PRIMARY (green) BACKUP (green) RTCERROR (red) MODULE ERROR (red)

REMOTE TRANSFER INTERFACE

RUN (green)

HALT (red)

CHANNEL ERROR (req) PRIMARY (green) MODULE ERROR (red) CPUA (green)

CPUB (green)

Note that when the Transfer Interface System is powered up and operating with a backup in RUN synchronized with the Primary (bumpless transfer mode), the LED indicators will be displayed as follows:

LTl- RUN and either PRIMARY or BACKUP steady ON.

RTl- RUN and either CPU A or CPU B steady ON, with complement (CPU A or CPU B) flashing ON and OFF.

The LED functions for both the Local and Remote Transfer Interfaces are shown on the following page in Tabled 3.5]and 3.6 respectively.

Page 8 read from a scan by OCR; it may hold reading errors

Table 3.5 - Local Transfer interface LED Functions

Name

Color Function

RUN

HALT

CHANNEL ERROR

PRIMARY

BACKUP

RTC ERROR

MODULE

GREEN _ | When ON indicates the I/O channel is fully operational and the CPU is accessing the image table (note CPU need not be in RUN). When OFF indicates the module is either in self-diagnostics or has failed. When flashing (50% duty cycle) indicates that one or more drops have been programmed to halt (bits 1 through 8 of the LTI I/O channel control register).

RED The complement of the RUN LED.

RED When ON indicates one or more drops are shut down due to a communication problem. When OFF indicates all drop are operational. When flashing indicates that a drop has shut down due to a failure on the drop (typically a remote bus error).

GREEN {| When ON indicates the LT] is in Primary status. When flashing (50% duty cycle) indicates a Backup which is not able to become Primary. When blinking (10% duty cycle) indicates a Backup in “bump transfer” mode.

GREEN The complement of the primary LED with the exception of a 90% duty cycle to indicate a backup in “bump transfer” mode.

RED When ON indicates the RTC is not receiving communication. When OFF the RTC is fully operational. When flashing, indicates the RTC is receiving data but the other RTC is not.

RED When ON indicates the LTI has recognized a bus error and has halted the CPU. Note this does not necessarily mean the LTI itself is bad. When OFF indicates the LT] itself is operational, despite the possibility that other LTI error LEDs may be ON.

Table 3.6 - Remote Transfer Interface LED Functions

Name

Color Function

RUN

HALT

CHANNEL ERROR

1/0 ERROR

MODULE

CPUA

CPUB

GREEN _ | When ON indicates the drop has been initialized and is operating normally. When flashing (50% duty cycle) indicates the CPU is in DISABLE OUTPUTS. When blinking (10% duty cycle) indicates that the LT! halt bit has been set for that drop.

RED When ON indicates that the drop either has not initialized or has been shut down due to program control. When flashing (50% duty cycle) indicates the CPU is in DISABLE OUTPUTS. When blinking (90% duty cycle) indicates that the LTI halt bit has been set for that drop.

RED When ON indicates a communication problem with the LTI. When flashing indicates a Primary is present but that no communication has been established with the Backup.

RED When ON indicates a problem has been detected on the remote rack (not necessarily an RTI failure). When flashing indicates outputs on the drop have been FROZEN.

RED When ON indicates a self-diagnostic error. If error is transient, power-cycling the drop will allow recovery.

GREEN _ | When ON indicates CPU A is Primary. When flashing (50% duty cycle) indicates CPU A is in ready Backup status. When OFF indicates CPU A is neither Primary nor a ready Backup.

GREEN _ | Same conditions as CPU A LED except applied to CPU B.

Page 9 read from a scan by OCR; it may hold reading errors

3.13.3 MODULE LOCATION

3.13.3.1 Local Transfer Interface

The Local Transfer Interface (LTI) module must be placed in the same rack as the Model 400, 500 or 700 processor. The first LTI in a Transfer Interface system should be placed in the third slot of the register rack, though any slot is acceptable. Additional LTIs are placed in adjacent register slots.

3.13.3.2. Remote Transfer Interface

The Remote Transfer Interface (RTI) module must be placed into the CPU slot (slot #1) of any rack which is to be adrop. Only one RTI is allowed for each drop.

3.13.4 INSTALLATION IN RACK ASSEMBLY Power must be removed from the rack assembly before installing or removing the Local or Remote Transfer Interface Modules.

After the removal of power, release the latching clamp and insert the module into the appropriate register slot until firmly seated and aligned on the stud located above the socket for the slot. Close the latching clamp and be sure to tighten the captive screw to insure the module is secured and properly grounded. To remove the module, release the latching clamp, loosen the captive screw at the bottom and pull the module out of the slot using the finger tab located on the top of the module.

Note: Refer to|Section 8.0/for proper grounding procedures. 3.13.5 FIELD WIRING 3.13.5.1 1/0 Channel Configuration

The LTIs I/O Channel must be wired in a daisy chain configuration to the RTI modules. | Figure 3.9 illustrates this typical configuration. A “star” wiring configuration is not allowed anywhere along the I/O channel.

Note that all LTIs in the CPU rack selected as ‘CPU A’ must be connected to the ‘CPU A’ channel of the RTIs. Likewise, LTIs in ‘CPU B’ rack must be connected to the ‘CPU B’ channel of the RTIs. There can be no intermixing: wiring from ‘CPU A’ RTIs must not be connected to any of the ‘CPU B’ RTI terminals and vice versa.

Note: ‘CPU A’ and ‘CPU B’ terminals must be wired consistently for each drop (A to A and B to B). Otherwise the RTI will generate error code 29510 and not go to RUN, regardless of the state of the I/O Failure Override bit.

LT) ! 8

0 6) 0 EV RIC | EV RTC, - - - - - - vO

Au vo

Figure 3.9 - /O Channel Wiring Configuration

3.13.5.2 Communication Cable

The communication between modules of a Transfer Interface System takes place via a two pair, twisted, shielded cable. In order to minimize the potential of electrical interference:

1. Route communication cable in separate, enclosed, metal wire ducts, away from power wiring and electro-magnetic devices.

2. Connect each end of the communication cable shield to the SHD terminal on each device. Do not connect this shield to an external ground point since the SHD terminals are capacitively coupled to ground.

Follow all applicable electrical codes for wiring and communication cable routing.

Communication cable should be equivalent to Belden 8723. Using a cable with different specifications may cause unreliable operation.

Page 10 read from a scan by OCR; it may hold reading errors

The maximum communication distance for the Belden 8723 or equivalent cable is as follows:

Communication Maximum Channel Length I/O Channel 2500 feet (762 m.) Register Transfer Channel | 25 feet (7.6 m.)

Because the Transfer Interface System uses redundant LTI-to-RTI communication cables, it is possible (and desirable ) to route the two cables separately or in different wire ducts. This practice will minimize the chances of both communication cables being broken or damaged simultaneously.

NOTE: (ADDITIONAL DATA LINE PROTECTION)

In environments where lightning or induced transients over communication lines are likely to cause communication failures, signal line protection devices are recommended. Even though transient protection is designed into SY/MAX communication circuits, additional specialized protection devices are suggested for communication lines that_are exposed to the outside environment. Refer to [Section 8| for recommended wiring scheme and protection devices.

Authoritative reference material which discusses the art and science of noise reduction and data line protection includes the ANSI/IEEE Std. 518 as well as a book entitled Noise Reduction Techniques in Electronic Systems by Henry Ott (Wiley-Interscience 1976).

3.13.5.3 LTI/RTI Connections

There are five terminals on the LTI and RTI modules for each communication link connection. These terminals are labeled 1, 2, 3, 4, and SHD.

The twisted-pair continuity of the communication cables must be maintained in the communication links (for example, Black with Red and Green with White for Belden 8723 cable). The RTC communication link for each pair of LTI modules are connected together as in|Figure 3.10] This distance is restricted to a maximum of 25 feet.

*Note: For the RTC communication link the wiring crisscrosses; terminals 1 and 2 of one LTI connect to terminals 3 and 4 of its matched LTI, and vice versa.

one twisted pair 1D van ni T ( } T Cc 2+ C2 30 p03 Cc Cc H H N 4B ws 44 N t 4 *See note t 2 SHD, £] SHD 2 one twisted pair

Figure 3.10 - RTC Channel: LTI-to-LTI Connections

The I/O communication link between the LTIs and RTIs is wired as shown if Figure 3.11] A maximum of two communication wires should be connected to each RTI terminal since each RTI in the daisy chain should be wired to the next RTI “straight through.”

Note that for the I/O communication link, the wiring is straight through; there is no crisscrossing.

one twisted j pair (Up to eight drops total) LTI RTI RTI 1 ) 1e - +fA Cy ~ O11 5 (] 2 20 wy £}-, {] 2 Cc 3 H 3G £} van, O 3 N ~ | L 407 jane ws, - { 4 1 SHO Cb _ x Csup one twisted pair

Figure 3.11 - !/O Channel: LTi-to-RTI Connections

3.13.6 RTI DIP SWITCHES

The RTI module has six dip switches on the rear of near the edge of the circuit board. See Figure 3.12) Each RTI module must be assigned as one of the eight drops on the LTI I/O Channel. The switches must be set correctly for the system to operate properly. See the following section on RTI DIP switch settings. Also, terminator switches must be set (ON) for the farthest drop of the channel. A label on the side of the module describes the switch settings. Sed Figure 3.13

Page 11 read from a scan by OCR; it may hold reading errors

L-~<@ $5802

Figure 3.12 - RTI DIP Switches

3.13.6.1 Setting the RTI DIP Switches

Before putting an RTI into a rack assembly, set the DIP switches for correct operation. The bank of six switches is accessible from the rear of the module. The switches are ON when they are set towards the PC board.

Switches 3,4 and 5 should_be set according to the label on the RTI module (Figure 3.13) |to specify the drop number of the rack on the 1/O Channel.

Switches 1 and 2 are terminators which must be properly set to minimize the electrical interference on the communications link. For each LTI I/O Channel, the last RTI on the channel (the unit farthest along the link from the LTI) must have the terminator switch ON. Note that because the I/O Channel is redundantly controlled, it is possible to use different wire routing from processor A and from processor B. Therefore, there are two terminator switches on the RTI - one for processor A (switch 2) and one for processor B (switch 1). All other RTIs on the channel must have the terminator switches OFF.

Note: Switch 6 is not used.

NOTICE: FOR PROPER OPERATION SWITCHES MUST BE SET CORRECTLY BEFORE INSERTING MODULE

OFF , OFF ON ov Wee eed 123456 NO. |B] A| SELECT O-OFF-OPEN-UP 1 [AlATX EXT X [oe %# =NOT USED 2 lalalx|xlol* A TERMINATOR SWITCHES: 3 lalalxlolxl* 4 |alalx|]ololx A- CPU ACHNL. B - CPU BCHNL. 5 l|alalolx| xls 6 talalolx]o{#| SET SWITCH ON FOR DROP AT END OF EACH DAISY CHAIN. ALL 7 [4/4] 0/0] X13] otHER TERMINATOR SWITCHES OFF. 8 [Aj 4} 0/0) 01* 30608-406-01

Figure 3.13 - RT! DIP Switch Label

WARNING Before operating the Transfer Interface System, be sure that all RTI DIP switches are set properly. Improper switch settings will cause unpredictable system operation and personal injury or property damage may result from unanticipated output actuation.

3.13.7 POWER UP SEQUENCE

Once the processors have “rack addressing” and ladder programs loaded into them, the Power Up Sequence can be initiated. The user is advised to per-form the power up sequence as described below, to insure correct initialization of the Transfer Interface System (TIS). Along with insuring correct initialization this sequence will determine the Primary/ Backup status of the system.

In the following sequence the user will power up the processors separately and check them out by observing the status of the LED indicators, and then put both processors in operation for redundant control.

Special

Note: When initially keyswitching the processor from HALT to DISABLE OUTPUTS or RUN, a processor that has a new “out of the box” LTI installed will remain in HALT and the LTI will indicate a MODULE ERROR. The processor error register (8175) will identify the LTI in error, and the LTI error register will contain error code 901. This is a normal occurrence, reflecting the fact that the LTI storage registers are corrupt (contain random data). Keyswitching the processor from HALT to DISABLE OUTPUTS or RUN a second (or third) time will clear the error.

Proceed with the Power Up Sequence:

1. With both processors powered down, power up the processor that will be designated Backup, and keyswitch it to DISABLE OUTPUTS. Verify, by the status of the LED indicators shown in Figure that the unit is operating correctly. Note that when switching processors from one state to another the LED indicators will momentarily change states before stabilizing.

If an LED display other than that indicated in Figure] 3.14/occurs, refer to the Special Note above. ,lf trouble persists, refer to Troubleshooting Section 3.15.4

2. Once the unit is operating correctly in DISABLE OUTPUTS, the unit can be further verified to be operating correctly by keyswitching it to RUN. Be reminded that when the processor is in RUN, it controls external I/O via the ladder program.

Page 12 read from a scan by OCR; it may hold reading errors

The correct LED indication when the unit is in RUN is shown in Figure 3.15.

PROCESSOR LTls RTIs RUN - RUN -ON RUN - flashing flashing PRIMARY - ON HALT - flashing RTC ERROR-ON | CHNL ERROR - flashing CPU AorB- ON

Figure 3.14 - DISABLE OUTPUTS LED Display

PROCESSOR LTis RTIs RUN - ON RUN-ON RUN - ON PRIMARY - ON HALT - OFF RTC ERROR-ON | CHNL ERROR - flashing CPU Aor B-ON

Figure 3.15 - RUN LED Display

Once the unit designated to be Backup is operating properly, power it down in preparation for the succeeding steps.

With the processor designated to be Backup powered down, apply power to the processor to be designated Primary, then keyswitch it to DISABLE OUTPUTS. As before, verify by the status of the LED indicators shown in Figure that the unit is operating correctly.

an LED display other than indicated in Figure |3.14]occurs, refer to the Special Note on the previous page. ouble persists, refer to the Troubleshooting Section 3.15.4

Once the unit is operating correctly in DISABLE OUTPUTS, keyswitch it to RUN and verify by he status of the LED indicators, shown in Figure hat the unit is operating correctly.

After the processor designated to be the Primary is operating correctly in RUN, leave it powered up and in RUN in preparation for the following steps.

With the Primary in RUN (for at least 10 seconds), apply power to the Backup and keyswitch it to RUN. If the Register Transfer Channel communication link is connected and operating correctly, the “RTC ERROR” LED on the Primary will turn OFF and the Backup will initialize and go into RUN. If the TIS is operating correctly there should be no ERROR indicators illuminated at this time; on the RTs, CPU A or B will be ON steady with the complement CPU A or B flashing.

Now that the Transfer Interface System is up and running, a more comprehensive ladder program can be entered and appropriate control bits set to adapt the TIS to the particular user application.

3.13.8

TROUBLESHOOTING

In the power-up sequence the user verifies correct operation of the TIS by observing the status of the LED indicators. If the LED indications are not as illustrated in the power-up sequence, the user may

[Section 3.13.2| (LED Indicators) and to

Error Codes) for help.

It should be noted that the illustrated LED indications for the power-up sequence assume “rack addressing” matches existing external I/O. Some typical causes for the LED indications to be different than as illustrated in the power-up sequence are described below:

1.

When initially keyswitching a processor that has a new “out of the box” LTI installed to DISABLE OUTPUTS or RUN, the processor will remain in HALT and the LTI will indicate a MODULE ERROR. The processor error register (8175) will identify the LTI in error, and the LTI error register (S8163 if the first LTI) will contain error code 901. This is a normal occurrence, reflecting the fact that the LTI storage registers are corrupt (contain random data). Keyswitching the processor from HALT to DISABLE OUTPUTS or RUN a second (or third) time will clear the error.

The I/O LED indicator on the processor will illuminate if “rack addressing” includes drops that don’t actually exist, are not wired, or are not communicating for some reason. Also, on the affected LTIs the HALT, CHNL ERROR, and MODULE ERROR indicatorg_will be ON. Interrogation of the error codes i | Section 7.0|will reveal the drop in error.

The RTI HALT and CHNL ERROR LED indi- cators will remain ON steady, regardless of the keyswitch position of the processor, if the RTI is not communicating with the LTI (RTI not wired).

The RTI HALT, CHNL ERROR, and CPU A (or B) LED indicators will remain ON steady - regardless of the keyswitch position of the processor - if the RTI drop number is incorrect (for example, RTI DIP switch setting does not match an existing drop in “rack addressing”).

Since these modules annunciate system errors that may actually originate in another module, error LEDs on the LTI or RTI themselves do not necessarily indicate a failure in these modules. If beset by erratic and seemingly contradictory indications, we suggest following a pattern which includes power-cycling all remote and CPU racks with the processor keyswitch in HALT. This should be followed by turning each of the processors to RUN, accompanied by the user rror code information as described in Section 7.0] Useful information is contained in egister 8175 as well as the appropriate LT] error code registers (S8163, S8160, etc.). Registers 8183 and 8184 may also contain relevant information, depending on the nature of the failure.