Class 8030 Type CRM-210, 211, 220, 222 Local/Remote Interface Modules: 3.14 LI/LTI Control Registers

Pages 13 to 21 of 21, from Class 8030 Type CRM-210, 211, 220, 222 Local/Remote Interface Modules

The original document is the PDF (1.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Square D 8030-CRM-210, Square D 8030-CRM-220, Square D 8030-CRM-222, Schneider 8030-CRM-210, Square D 8030-CRM-211, Schneider 8030-CRM-220 and Schneider 8030-CRM-222

Page 13 read from a scan by OCR; it may hold reading errors

3.14 LI/LTI CONTROL REGISTERS

Control Registers 8001-8163 (contained in the processor) are used to monitor and in some cases, control the Local/Remote Interface (LI/RI) system and/or Local/Remote (LTI/RTI) Transfer Interface System. These registers reflect the condition of the LY/RI and LTI/RTI system and contain information about registers and I /O modules.

Each control register consists of two parts, a DATA field and a STATUS field. The DATA field can be programmed by the user for control functions. The STATUS field, as the name implies, is used just to monitor the status of specific system conditions.

The Local Interface (LI) and Local Transfer Interface (LTI) control registers are dynamically assigned on the basis of physical position in the CPU rack and rack addressing assignments.

3.14.1 REGISTER ALLOCATION OF THE LOCAL INTERFACE SYSTEM (LI)

The Class 8030 Type CRM-210 and CRM-211 Local Interface modules (LI) are two- channel modules in which up to three control registers are used to communicate directly with the processor (CPU). The first register is an error code control register. The second is a control register for Channel 1 and the third is a control register for Channel 2, if used.

1. Local Interface Control registers are assigned in descending order starting with S8163 for the Local Interface module closest to the processor.

2. Local Interface Control register are further defined by the number of channels used.

For example, the local interface module closest to the processor would use control register 8163 as an error code register and use control register 8162 for Channel 1 and control register 8161 for Channel 2.

In the case where only one channel is assigned to the first LI, there will be no control registers assigned to Channel 2. $8163 is the error code control] register. $8162 is the channel control register for Channel 1 and $8161 is left unassigned. If an additional LI is placed in a higher numbered CPU slot, it would be assigned the next available control register, for example, S8161 becomes the second LI’s error code register, 58160 is the control register for Channel 1 of the second LI. S8159 is unassigned and available for Channel 2 or for the third LI’s error code register. If only Channel 2 is defined, the system automatically assigns a control register to Channel 1 whether Channel 1 is used or not.

| Figure 3.16jon the following page lists the error code and channel contro! registers for systems using both channels on each local interface module. This includes up to the maximum of seven local interface modules that can be used with a Model 500 or Model 700 processor system.

3.14.2 REGISTER ALLOCATION OF THE TRANSFER INTERFACE SYSTEM (TIS)

The 8030 CRM-230 Local Transfer Interface (LTI) isa two channel module which utilizes three registers to communicate directly with the processor (CPU). The first register is an error code register. The second isa control register for Channel 1 (I/O Channel). The third is a control register for Channel 2 (Register Transfer Channel-RTC). The number of control registers used to monitor a particular TIS is based on the number of LTI modules used in the system. Each matched pair of LTI modules uses three control registers.

LTI contro! registers are automatically assigned in descending order starting with S8163 for the LTI nearest the CPU with the lowest numbered CPU rack slot number. The first matched pair of LTI modules in a Transfer Interface System have register S8163 designated as their error code register. The I/O Channel (Channel 1) control register is S8162. The RTC (Channel 2) control register is $8161. Following the above sequence, S8160 would be the Error Code Register of the second LTI in the rack. See Figure 3.17jon the following page for LTI Control Register assignment.

Page 14 read from a scan by OCR; it may hold reading errors

REGISTER | L.I. LOCATION FUNCTION

$8163 First (Right of Error Code

$8162 First CPU) Channel 1 Control Data and Status

S8161 First* J Channel 2 Control Data and Status

$8160 Second* (Right of first LI | Error Code

$8159 Second* module) Channel 1 Contro!i Data and Status

$8158 Second* Channel 2 Control Data and Status

$8157 Third* (Right of second | Error Code

S8156 Third* LI module) Channel 1 Control Data and Status

$8155 Third* J Channel 2 Control Data and Status

$8154 Fourth* (Right of third | Error Code

$8153 Fourth* LI module) Channel 1 Control Data and Status

$8152 Fourth* 1 Channel 2 Control Data and Status

$8151 Fifth* (Right of fourth | Error Code

$8150 Fifth* LI module) Channel 1 Control Data and Status

$8149 Fifth* J Channel 2 Contro! Data and Status

$8148 Sixth* (Right of fifth LI | Error Code

$8147 Sixth* module) Channel 1 Control Data and Status

$8146 Sixth* Channel 2 Control Data and Status

$8145 Seventh* (Right of sixth | Error Code

$8144 Seventh* LI module) Channel 1 Control Data and Status | $8143 Seventh* { Channel 2 Contro! Data and Status

* Indicated LI register assignments may vary, dependent upon rack addressing assignments. Control registers are dynamically assigned in accordance with rack addressing and further defined by the number of channels used. They are not assigned solely based upon LI count.

Figure 3.16 - Lt Control Register Assignments

REGISTER |{LTI LOCATION FUNCTION

58163 First (Right of Error Code

$8162 First CPU) I/O Channel 1 Control Data and Status $8161 First J RTC Channel 2 Control Data and Status $8160 Second (Right of first | Error Code

$8159 Second LTI module) 1/O Channel 1 Control Data and Status $8158 Second 1 RTC Channel 2 Contro! Data and Status $8157 Third (Right of second | Error Code

$8156 Third LTI module) I/O Channel 1 Control Data and Status $8155 Third ‘ RTC Channel 2 Control Data and Status S8154 Fourth (Right of third | Error Code

$8153 Fourth LTI module) I/O Channel 1 Control Data and Status $8152 Fourth J RTC Channel 2 Control Data and Status $8151 Fifth (Right of fourth | Error Code

$8150 Fifth LTI module) 1/O Channel 1 Control Data and Status $8149 Fifth J RTC Channel 2 Control Data and Status S8148 Sixth (Right of fifth | Error Code

$8147 Sixth LTI module) I/O Channel 1 Control Data and Status $8146 Sixth J RTC Channel 2 Control Data and Status $8145 Seventh (Right of sixth | Error Code

$8144 Seventh LTI module) 1/O Channel 1 Control Data and Status $8143 Seventh J RTC Channel 2 Control Data and Status

Figure 3.17 - LT! Contro! Register Assignments

Page 15 read from a scan by OCR; it may hold reading errors

3.14.3 REGISTER INFORMATION

3.14.3.1. Error Code Control Register

The LI/LTI error code register is the first of the group of registers allocated to an LI/LTI. It is this register which provides diagnostic information in the event an LI/LTI, RI/RTI register card, or I/O module experience a failure. Ifa device in the serial interface system causes the PC system to shutdown, control register 8175 will indicate which LI/LTI is responsible (by register address number) for the control of that device. The particular LI error code control register can then be examined to further diagnose the error. In general, errors indicated in 58175 refer to CPU and LI/LTI module problems or local register module problems, while errors indicated in the LI/LTI error code control registers refer to problems between the LI/LT] module and RI/RTI module, remote register module or I/O module. Error codes which are displayed in the LI/LTI error code register as decimal numbers can be separated into three basic groups ag follows

ERROR CODE

NUMBER* TYPE OF ERROR

. Master Module Error 30,000 - 32,700 (LI/LTI or RI/RTt internal error.)

. Slot Error 20,000 - 28.192 (Gives the first register address of the CPU rack register module that malfunctioned.)

. Read after Write Error 10,000 - 18,192 (Remote outputs or registers do not have the same state as commanded by the CPU.)

*All specific error codes are listed in Section 7.0|

Note: Ifthe failure override bit is set in the channel control register (see| Section 3.14.4]}0n the following page), S8175 will only indicate 30,000 and above errors. 10,000 to 28,192 errors will go unnoticed by 8175 but will be indicated by the LI/LTI error control register.

3.14.3.2. Channel Control Register

Associated with each channel contained in a local interface module is a 32 bit control register. The first 16 bits provide several LI/LTI control options which can be programmed by the user. Bits 17-32 comprise the status field and provide to the CPU operational information about the RI/RTI or LI/LTI system. A number of these bits can be used as inputs to affect the control of the options previously mentioned. A break-down and description of Channel Control Registers is given on the following pages.

Page 16 read from a scan by OCR; it may hold reading errors

3.14.4 LOCAL INTERFACE MODULE CONTROL DATA REGISTER

16]15)}14}13}12)11

Undefined ¢-' : “-® Halt Drop #1

Auto Restart < - - - ~ : > - - - - p Halt Drop #2 Unused .--------.-! : Leceeeseeeeeeee > Halt Drop #3

Failure Override ¢ : : t________-» Halt Drop #4 Unused 9.0.0... : Lees eeee nese et eee teee eee ee ees » Halt Drop #5

Unused < : : > Halt Drop #6

TET qe ee eect eee eens 3 Mec eecceeteeeecceeeensetesesstnsteeeeeeenes > Halt Drop #7

Freeze -» Halt Drop #8

CHANNEL CON L REGISTER BI NAME DESCRIPTION

1 Halt Drop #1 When OFF (0) - the drop will operate as the ladder logic

2 Halt Drop #2 indicates.

3 Halt Drop #3

4 Halt Drop #4 When ON (1) - the drop will be shutdown.

5 Halt Drop #5

6 Halt Drop #6 1. Input status still valid

7 Halt Drop #7 2. Outputs turn OFF

8 Halt Drop #8 3. Register I/O clear (depending upon module type)

9 Freeze When ON (1) and a loss of transmission or transmission error or local rack error occurs, all outputs are maintained in their last state.

10 TXFT Transmission Fault Tolerance determines whether 3 or 20 consecutive transmission errors occur before a channel error is acknowledged.

OFF (0) = 3 errors ON (1) = 20 errors

11 Unused

12 Unused

13 Failure Override | When ON (1) allows the channel to continue operating if a drop error on a channel occurs.

When OFF (0) and drop error is present, channel will shutdown and processor will halt.

14 Unused

15 Auto Restart When ON (1) allows the channel to attempt to reestablish valid communications with any drop shutdown due to transmission errors. (Bit 13 must be set to enable bit 15 to be recognized.) This control bit accomplishes a similar function as the restart button on the LI module.

Note: When the LI/LTI failure override bit (13) and auto restart bit (15) are set and a channel error occurs, the drop will restart automatically. When bus errors occur operator intervention is necessary. Toggle the keyswitch or press the restart button for the drop to restart.

16 Unused

* Only in certain series of Model 306 processors. Seq Table 3.ifin Section 3 - page 20.

Figure 3.18 - LI Control Data Register

Page 17 read from a scan by OCR; it may hold reading errors

3.14.5 LOCAL INTERFACE MODULE CONTROL DATA REGISTER (Read Only) 32 | 31 | 30 | 29 | 28 | 27 | 26 | 25 | 24 | 23 | 22 | 21 | 20/19 | 18] 17 Li Internal Usage ¢: ‘> Channel : Diagnostics Li Internal Usage q - - 3 Complete LI Channel {1D 400-0 : > Channel Unused <« - - - - - Initialization Drop #8 Error : : : : Complete Shutdown @...--...-...- eee t : : Lee eeeeeecaees > Channel Drop #7 Error Addressing Shutdown ¢ Complete Drop #6 Error i» Unused Shutdown <4 nee eee eee eee ence eat tet e been eeeteene ’ bebe beeen. > Drop #1 Error Drop #5 Error Shutdown Shutdown ¢ > Drop #2 Error : Shutdown weccecevecectetecseuaaceveceeaueneeneecs » Drop #3 Error Shutdown > Drop #4 Error Shutdown CHANNEL CONTROL REGISTER BIT NAME DESCRIPTION 17 Channel Diagnostics Complete | When ON (1) - LI channel completed its diagnostics. 18 Channel Initialization Complete | When ON (1) 1. Ris have completed their diagnostics. 2. Valid LI/RI communication. 3. Image table updating sequence complete. 19 Channel Addressing Complete When ON (1), indicates the CPU has loaded valid rack addressing information into the LI. 20 Unused 21 Drop #1 Error Shutdown If drop has been rack addressed: 22 Drop #2 Error Shutdown When OFF (0) drop is operating. 23 Drop #3 Error Shutdown When ON (1) drop is shutdown due to error. 24 Drop #4 Error Shutdown 25 Drop #5 Error Shutdown If drop has NOT been rack addressed: 26 Drop #6 Error Shutdown When OFF (0) no drop exists. 27 Drop #7 Error Shutdown When ON (1) drop exists without addressing. 28 Drop #8 Error Shutdown 29 Unused 30 LI Channel ID When OFF (0), indicates a one channel LI. 31 Ll internal Usage 32 LI Internal Usage

* Only in certain series of Model 300 processors. See Table 3.1 in Section 3 - page 20.

Figure 3.19 - LI Control Status Register

Page 18 read from a scan by OCR; it may hold reading errors

3.14.6 LT!| CONTROL REGISTER - I/O CHANNEL

3.14.6.1 1/O Channel Data Field

16)15114]13}12}11;10] 9} 8] 7} 6) 5] 4] 3] 2] 1

Unused 4° -% Halt Drop #1

Auto Restart < - - - ~ : - - - ® Halt Drop #2

Unused .-...------ Vereeeesseeeeees >» Halt Drop #3

Failure Override ¢ : : : : > Halt Drop #4

Unused -.---e cere : : : Lecce cee cee ee cence te eee eens > Halt Drop #5

Unused <¢ : : > Halt Drop #6

TXET qi eee teeee ; osc eee tesa eee eeee sete een eecaeeneese ete eene > Halt Drop #7

Freeze « - - p Halt Drop #8 CONTROL

REGISTER BIT NAME DESCRIPTION

1 Halt Drop #1 When OFF (0) the drop will operate as the ladder program indicates.

2 Halt Drop #2 When ON (1) the drop will be shut down.

3 Halt Drop #3

4 Halt Drop #4 1. Input status still valid.

5 Halt Drop #5 2. Outputs turn OFF.

6 Halt Drop #6 3. Register I/O clear (depending upon module type).

7 Halt Drop #7 4. Adrop shutdown under Primary control will not cause a transfer

8 Halt Drop #8 from Primary to Backup.

9 Freeze When ON (1) and a loss of transmission, transmission error, or CPU rack error occurs, all outputs are maintained in their last state. This bit is ignored in a Primary LT! if a running Backup is able to take control.

10 TXFT Transmission Fault Tolerance determines whether three or twenty

(Transmission consecutive transmission errors are allowed to occur before a channel Fault Tolerance) | error is acknowledged and an attempt is made to transfer to Backup. OFF (0) = Three Errors ON (1) = Twenty Errors

11 Unused

12 Unused

13 /O Failure When OFF (0) and drop error occurs, I/O channel will shut down and

Override processor will HALT. When ON (1) - and Backup is ready - TIS will switch control to the Backup rather than run with the channel in error (thus ignoring the 1/O Failure Override Bit). When ON (1) - and Backup is not ready - The I/O channel will be allowed to continue operating if a drop error occurs.

14 Unused

15 Auto Restart When ON (1) allows the I/O Channel to attempt to reestablish valid communications with any drop shut down due to transmission errors (bit 13 must be set to enable bit 15 to be recognized). This control bit performs the same function as the RESET button on the primary LTI module. This bit is only active ina Primary system with no Backup; otherwise control will be switched to the ready Backup.

16 Unused

Figure 3.20 - LT! I/O ControlRegister Data Field

Page 19 read from a scan by OCR; it may hold reading errors

3.14.6.2 1/O Channel Status Field

32 | 31 | 30 | 29 | 28 | 27 | 26 | 25 | 24 | 23 | 22 | 21 | 20] 19 | 18 | 17

LI Internal Usage <¢: : : “> Channel age zl : : : : : : Diagnostics LI Internal Usage Complete ‘ sage ot LI Internal Usage : Channel Unused + : Initialization Drop #8 Error 40000 : Complete Shutdown : eeeeeeteeeeees p Channel Drop #7 Error « : Addressing Shutdown : : Complete Drop #6 Error. ese cee! : : » Unused Shutdown ae ® Drop #1 Error 7 < : Shutdown Drop #5 Error * : Shutdown > Drop #2 Error : Shutdown wevesceesneeceeeeeceeeeenseeeteneeeeenses » Drop #3 Error Shutdown, » Drop #4 Error Shutdown CONTROL REGISTER BIT NAME DESCRIPTION 7 Channel Diagnostics Complete When ON (1) - LTI channel completed its diagnostics. 18 Channel Initialization Complete When ON (1)

1. RTIs have completed their diagnostics. 2. Valid LTI/RT! communication. 3. Image table updating sequence complete.

19 Channel! Addressing Complete When ON (1), indicates the CPU has loaded valid rack addressing information into the LTI.

20 Unused

23 Drop yi ; Error shutdown If drop has been rack addressed:

2 Drop rror Shutdown h FF ; rating.

23 Drop a Error opurgown When ON (1) drove chvidewe ine to error. oa Drow ae prror cputgown If drop has NOT been rack addressed:

27 Drop #7 Error Shutdown When OFF (0) no drop exists. 28 Drop #8 Error Shutdown When ON (1) drop exists without addressing. 29 Unused

30 Internal Usage

31 Internal Usage

32 Internal Usage

Figure 3.21 - LTI /O Channel Control Status Field

Page 20 read from a scan by OCR; it may hold reading errors

3.14.7 LTI CONTROL REGISTER - REGISTER TRANSFER CHANNEL 3.14.7.1 RTC Data Field 16/15114/13/12/11110) 9} 8| 7), 6] 5} 4) 34 21] 1 EOS Transfer <¢---- --& Unused Re-syne < - - - - ’ : L - - » Unused Test qed : Leececeseeeaees p Unused RTC Failure + : -» Unused Override : ee sececeeeeeetettteeeeennes > Unused Unused DP eee eee : > Unused Unused +t : Deca cece eee tence eee sees e eee eeeeeene tees > Unused Unused <¢...--.. ecient eee eer eeeee <, > Unused Unused ¢ CONTROL REGISTER NAME DESCRIPTION 1 Unused 2 Unused 3 Unused 4 Unused 5 Unused 6 Unused 7 Unused 8 Unused 9 Unused 10 Unused 11 Unused 12 Unused 13 RTC Failure When set ON (1) ina Backup LTI, will allow Backup Override processor to continue to RUN despite losing synchronization with the Primary. This bit is active only in the Backup LTI. 14 Test When set ON (1) ina Backup LTI,the LTI (upon a HALT to RUN transition) will not request a Startup Transfer from the Primary processor. 15 Re-sync When set ON (1) ina Backup LTI that is in RUN, the Backup system will attempt a Startup Transfer to re-synchronize the TIS. To enable the RE-SYNC bit, the RTC FAILURE OVERRIDE bit must also be set ON (1) and the TEST bit must be reset OFF (0). 16 EOS Transfer When set ON (1) in a Backup LTI that is in RUN, the Backup LTI will request an End of Scan Transfer of 32 registers. The block of 32 registers to be transferred is determined by the value residing in the End of Scan Transfer Register (second register assigned to the RTC).

Figure 3.22 - RTC Control Register Data Field

Page 21 read from a scan by OCR; it may hold reading errors

3.14.7.2 RTC Status Field

29 | 28 | 27 | 26 } 25 | 24 | 23 | 22 |21)20}19/18] 17 Internal Usage aa Channel - Internal Usage Diagnostics Internal Usage Complete Unused _ - _ - -» Channel Unused qeecccccccccceeeeeeeeceeeeeet Initialization Unused Complete Unused wdc eee e eee cence eee tet neneeeeteteee : wee e cece wees > Channel Unused Addressing Complete, Primary Backup beeeceeeterteveneseetectiess > Transmit Loss, p» Receive Loss bee ceeeeeseceecneeeeseeetnseeeeeneneeees ~» Backup Loss > Startup Transfer CONTROL REGISTER BIT NAME DESCRIPTION

17 Channel Diagnostics Complete When ON (1) - LT channel completed diagnostics. Reset OFF (0) - Self-tests are in progress.

18 Channel Initialization Complete Set ON (1) when:

1. LTlisin RUN with a verified address map. 2. /Ochannel is initialized

19 Channel Addressing Complete Set ON (1) when address map has been loaded and verified

20 Primary/Backup Set ON (1) when LTI is Primary.

Set OFF (0) when LT! is Backup.

21 Transmit Loss Set ON (1) when matched LTI has its RECEIVE LOSS bit set.

22 Receive Loss Set ON (1) when LTI has not received communication from its matched pair.

23 Backup Loss Set ON (1) in Primary LTIs that do not have a Backup that can become Primary. Reset OFF (0) when a Backup in full RUN is present. Backup LTIs will also set their BACK UP LOSS bit when they are unable to become Primary.

24 Startup Transfer Set ON (1) one sean before a Primary does a Startup Transfer. Reset OFF (0) upon completion of the Startup Transfer.

25 Unused

26 Unused

27 Unused

28 Unused

29 Unused

30 Internal Usage

31 Internal Usage

32 Internal Usage

Figure 3.23 - RTC Control Register Status Field