SY/MAX guide pages for the Class 8030 CRM-210, 211, 220 and 222 local/remote interface and CRM-230/232 transfer modules.
What this file really is
The old site listed this file as a spec sheet for the Square D 8030 CRM-510, 8030-CRM-210 and 7 more models. This is not a spec sheet but chapter 3, sections 12 to 14 of a SY/MAX troubleshooting guide covering the CRM-210, 211, 220, 222, 230 and 232 modules; it does not mention the CRM-510.
Names · 7 models
The models it names
Filed with · 2 models
Also filed with these models on the old site
Summary
What is in it
Pages from a SY/MAX troubleshooting guide (chapter 3, sections 12 to 14) on the Class 8030 interface modules. The CRM-210 and 211 Local Interface and CRM-220 and 222 Remote Interface modules let SY/MAX Model 300, 400, 500 or 700 processors run remote digital and register I/O racks over a serial link. The pages give specifications, LED meanings, module location, rack installation, field wiring and cable, RI DIP switch settings and the power-up sequence, then the same for the CRM-230/232 transfer interface modules and the LI/LTI control registers.
Its parts
- Type CRM-210/11/20/21 LI/RI Modules
- Type CRM-230/32 LTI/RTI Modules
- LI/LTI Control Registers
From the sheet
Key facts from this sheet
Much of this sheet is scanned with little readable text, so this says only what its text supports. Each line names its page in the PDF.
Section 3.12 to 3.14 of the Square D SY/MAX Troubleshooting Guide, covering the Class 8030 Type CRM-210 and 211 Local Interface (LI) and CRM-220 and 222 Remote Interface (RI) modules, plus the CRM-230 and 232 transfer interface modules. It gives the LI/RI specifications, LED meanings, where each module goes, wiring the serial link, setting the RI drop switches, the power-up sequence and the control registers. The pages are scans read by OCR; the CRM-510 the site also files here is not named.
- What it is
- Local (LI) and Remote (RI) interface pair for running SY/MAX digital and register I/O racks remotely over a serial link p. 1
- Communications
- Continuous, full duplex, serial differential RS-422 at 31.25K baud, daisy chain p. 1
- Cable and distance
- Belden 8723, 7,500 feet; or Belden 9463 (two cables), 10,000 feet p. 4
- Drops
- Up to 8 drops per LI channel, 127 registers per drop max p. 1, 4
- Processors
- SY/MAX Model 300, 400, 500 or 700; up to seven LIs with Model 500 and 700, one with Model 300 p. 1
- Operating temperature
- 0°C-60°C (32°-140°F); humidity 5% to 95% non-condensing p. 1
- Power draw
- CRM-210, 211: 1600 mA; CRM-220, 222: 1000 mA, from the SY/MAX supply p. 1
- LI registers
- CRM-210: 512 registers; CRM-211: 4096 registers; 255 of each for forcible external I/O p. 1
- LI channels
- CRM-210, 211: 2 channels per Local Interface p. 1
- Rack compatibility
- CRM-210/211: all racks except CRK-100 and 200; CRM-220: all four function digital racks p. 1
- Module location
- LI in the processor's rack; RI in slot 1 (CPU slot) of each drop rack, one per drop p. 3
- Indicators
- RUN, HALT, CHANNEL ERROR and MODULE ERROR LEDs on both LI and RI p. 2
- Power wiring
- None external; LI and RI are powered through the rack edge connector p. 3
What this sheet walks you through
- Reading the LI and RI LED indicators p. 2
- Placing the LI and RI modules in their racks p. 3
- Installing and removing a module in a rack p. 3
- Routing and connecting the communication cable and shield p. 4
- Setting the RI drop number and terminator DIP switches p. 4, 5
- Following the LI and RI power-up light sequence p. 6
- How LI control registers are assigned p. 13
- Reading the LI error code register p. 15
Good to know
- Set the RI switches before inserting the module, and set switch 1 ON only on the drop farthest from the LI. p. 5
- Do not connect the cable shield to an external ground point; the shield terminals are capacitively coupled to ground. p. 4
- A new LI shows MODULE ERROR and error code 901 on first keyswitching; switching again clears it. p. 6
- Remove power from the rack before installing or removing an LI or RI module. p. 3
- The manual states the CRM-210, 211, 220 and 222 are UL listed. p. 1
Questions this sheet answers
What does error code 901 on a CRM-210 mean?
On a new LI it is normal: its storage registers hold random data, and keyswitching HALT to RUN or DISABLE OUTPUTS again clears it. p. 6
What is the difference between the CRM-210 and CRM-211?
Both are Local Interface modules; the CRM-210 has 512 registers and the CRM-211 has 4096. p. 1
How far can a SY/MAX remote I/O drop be?
Up to 7,500 feet with Belden 8723 cable, or 10,000 feet with dual Belden 9463 cables. p. 4
Where does the CRM-220 Remote Interface go?
In the CPU slot (slot 1) of the remote rack, one RI per drop. p. 3
Contents
Chapters and sections
Each line opens the PDF at its page.
- SY/MAX Troubleshooting Guide1
- Chap 3, Secs 12, 13, 141
- 3.12 Type CRM-210/11/20/21 LI/RI Modules1
- 3.13 Type CRM-230/32 LTI/RTI Modules7
- 3.14 LI/LTI Control Registers13
- 3.14.1 LI Register Allocation13
- 3.14.2 TIS Register Allocation13
- LI Control Register Assignments14
- LTI Control Register Assignments14
- 3.14.3 Register Information15
- 3.14.4 LI Control Data Register16
- 3.14.5 LI Control Data Register (Read-Only)17
- 3.14.6 LTI Control Register (I/O Channel)18
- 3.14.7 LTI Control Register (Transfer Channel)20
The whole text · 3 parts
Read the sheet here as text