Manual · Square D
Local/Remote Interface, Class 8030 Types CRM-210, 211, 220, 222
Manual38 pagesPDF 1.2 MB
Instruction bulletin for the Square D SY/MAX Class 8030 CRM-210, 211, 220 and 222 local and remote I/O interface modules.
Covers · 7 models
The models it covers
Summary
What is in it
Square D instruction bulletin for the SY/MAX local/remote interface system: the CRM-210 and CRM-211 local interface (LI) modules that mount beside the processor, and the CRM-220 and CRM-222 remote interface (RI) modules that sit in remote racks (drops). It gives specifications and compatibility with processors, racks and I/O, explains installation, keying, field wiring and RI switch settings, local interface registers and rack addressing, and troubleshooting. Appendices cover update times, error codes, channel expansion, control/status registers and the power-up sequence.
Its parts
- Introduction
- Specifications
- Installation
- Operation
- Troubleshooting
From the manual
Key facts from this manual
Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.
Square D instruction bulletin 30598-247-01D2 (October 1990) for the Class 8030 Types CRM-210, 211, 220 and 222 local and remote interface modules of the SY/MAX programmable controller family. The CRM-210 and CRM-211 local interfaces sit in the processor rack and link over twisted shielded pair cable to CRM-220 or CRM-222 remote interfaces in distant racks. It covers specifications, installation, wiring, LED meanings, error codes and troubleshooting.
- What it is
- Local (LI) and remote (RI) interface modules that let SY/MAX digital and register racks sit away from the processor p. 5
- Module types
- CRM-210 and CRM-211: local interface; CRM-220 and CRM-222: remote interface p. 6
- Channels and drops
- 2 channels per local interface, each with up to eight drops p. 6, 8
- Registers
- CRM-210: 512 registers; CRM-211: 4096 registers p. 6
- Processors
- All Model 400, 500, 600 and 700 SY/MAX processors; Model 300 supports one LI p. 6
- Link cable
- Dual twisted shielded pair cable, wired in daisy chain p. 8
- Cable types
- Belden 8723 up to 7,500 feet; Belden 9463 (dual cables) up to 10,000 feet p. 8
- Current draw
- CRM-210 and CRM-211: 1600 mA; CRM-220: 1000 mA, from the SY/MAX power supply p. 6
- Rack slots
- LI in a register slot of the CPU rack; RI in the CPU slot of the remote rack p. 6
- Terminal strips
- CRM-210, 211: part number 25410-02529; CRM-220: 30605-255-02; CRM-222: 25410-02526 p. 7
- Keying kit
- Optional Class 8030 Type CBP 104 keying pin kit p. 7
- Operating temperature
- 0°C to 60°C (32° to 140°F); storage -40°C to 80°C p. 7
- Size and weight
- CRM-210, 211, 222: 3.81 x 32.5 x 16.76 cm, 3.0 lb; CRM-220: 1.0 lb p. 7
- LI error codes
- 901: LI storage registers corrupt (normal on a new Series L or later LI); 902: recovery from undervoltage lockout p. 7, 16
What this manual walks you through
- Planning a remote I/O system with LI and RI modules p. 5
- Keying rack slots for the interface modules p. 7
- Placing the LI and RI modules in their racks p. 8
- Wiring the LI/RI communication cable p. 8
- Setting the RI drop switches p. 8
- Reading the LI and RI status LEDs p. 15
- Isolating faults with the error and control registers p. 14, 16
- Replacing a module p. 16
- Restarting LI/RI communication with the restart button p. 17
- Looking up processor error codes p. 21
Good to know
- Remove power from all local and remote racks before inserting or removing any module or the communication cables. p. 7
- Wire the modules in daisy chain only; any other layout may cause erratic operation. p. 8
- Pressing the RESTART button on the LI may turn outputs on or off. p. 17
- Series O and later LIs halt when the rack DC voltage falls below 4.6 volts. p. 16
- Where lightning or induced transients are likely, signal line protection devices are recommended. p. 8
Questions this manual answers
How long can the CRM-210 remote I/O cable be?
Each channel allows 7,500 ft of Belden 8723 cable; Belden 9463 dual cables allow 10,000 feet. p. 8
How many remote drops can a CRM-210 local interface run?
It has two channels, and each channel can have up to eight drops. p. 6, 8
What does error 901 mean on a SY/MAX local interface?
On Series L or later LIs it means the storage registers hold corrupt data; it is normal on a new LI and clears after keyswitching the processor again. p. 7
Which SY/MAX processors work with the CRM-210?
All Model 400, 500, 600 and 700 processors, which can use several LIs; a Model 300 supports one LI. p. 6
What does a flashing I/O ERROR LED on the remote interface mean?
It means the drop's outputs and inputs are frozen. p. 15
Contents
Chapters and sections
Each line opens the PDF at its page.
The whole text · 6 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.