Page 1 of Local/Remote Interface, Class 8030 Types CRM-210, 211, 220, 222

Manual · Square D

Local/Remote Interface, Class 8030 Types CRM-210, 211, 220, 222

Manual38 pagesPDF 1.2 MB

Instruction bulletin for the Square D SY/MAX Class 8030 CRM-210, 211, 220 and 222 local and remote I/O interface modules.

Download the PDF1.2 MB

Covers · 7 models

The models it covers

Summary

What is in it

Square D instruction bulletin for the SY/MAX local/remote interface system: the CRM-210 and CRM-211 local interface (LI) modules that mount beside the processor, and the CRM-220 and CRM-222 remote interface (RI) modules that sit in remote racks (drops). It gives specifications and compatibility with processors, racks and I/O, explains installation, keying, field wiring and RI switch settings, local interface registers and rack addressing, and troubleshooting. Appendices cover update times, error codes, channel expansion, control/status registers and the power-up sequence.

Its parts

  1. Introduction
  2. Specifications
  3. Installation
  4. Operation
  5. Troubleshooting

From the manual

Key facts from this manual

Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.

Square D instruction bulletin 30598-247-01D2 (October 1990) for the Class 8030 Types CRM-210, 211, 220 and 222 local and remote interface modules of the SY/MAX programmable controller family. The CRM-210 and CRM-211 local interfaces sit in the processor rack and link over twisted shielded pair cable to CRM-220 or CRM-222 remote interfaces in distant racks. It covers specifications, installation, wiring, LED meanings, error codes and troubleshooting.

Read for this summary: pages 1, 5 to 8, 14 to 17 and 21 of 38.

What it is
Local (LI) and remote (RI) interface modules that let SY/MAX digital and register racks sit away from the processor p. 5
Module types
CRM-210 and CRM-211: local interface; CRM-220 and CRM-222: remote interface p. 6
Channels and drops
2 channels per local interface, each with up to eight drops p. 6, 8
Registers
CRM-210: 512 registers; CRM-211: 4096 registers p. 6
Processors
All Model 400, 500, 600 and 700 SY/MAX processors; Model 300 supports one LI p. 6
Link cable
Dual twisted shielded pair cable, wired in daisy chain p. 8
Cable types
Belden 8723 up to 7,500 feet; Belden 9463 (dual cables) up to 10,000 feet p. 8
Current draw
CRM-210 and CRM-211: 1600 mA; CRM-220: 1000 mA, from the SY/MAX power supply p. 6
Rack slots
LI in a register slot of the CPU rack; RI in the CPU slot of the remote rack p. 6
Terminal strips
CRM-210, 211: part number 25410-02529; CRM-220: 30605-255-02; CRM-222: 25410-02526 p. 7
Keying kit
Optional Class 8030 Type CBP 104 keying pin kit p. 7
Operating temperature
0°C to 60°C (32° to 140°F); storage -40°C to 80°C p. 7
Size and weight
CRM-210, 211, 222: 3.81 x 32.5 x 16.76 cm, 3.0 lb; CRM-220: 1.0 lb p. 7
LI error codes
901: LI storage registers corrupt (normal on a new Series L or later LI); 902: recovery from undervoltage lockout p. 7, 16

What this manual walks you through

  • Planning a remote I/O system with LI and RI modules p. 5
  • Keying rack slots for the interface modules p. 7
  • Placing the LI and RI modules in their racks p. 8
  • Wiring the LI/RI communication cable p. 8
  • Setting the RI drop switches p. 8
  • Reading the LI and RI status LEDs p. 15
  • Isolating faults with the error and control registers p. 14, 16
  • Replacing a module p. 16
  • Restarting LI/RI communication with the restart button p. 17
  • Looking up processor error codes p. 21

Good to know

  • Remove power from all local and remote racks before inserting or removing any module or the communication cables. p. 7
  • Wire the modules in daisy chain only; any other layout may cause erratic operation. p. 8
  • Pressing the RESTART button on the LI may turn outputs on or off. p. 17
  • Series O and later LIs halt when the rack DC voltage falls below 4.6 volts. p. 16
  • Where lightning or induced transients are likely, signal line protection devices are recommended. p. 8

Questions this manual answers

How long can the CRM-210 remote I/O cable be?

Each channel allows 7,500 ft of Belden 8723 cable; Belden 9463 dual cables allow 10,000 feet. p. 8

How many remote drops can a CRM-210 local interface run?

It has two channels, and each channel can have up to eight drops. p. 6, 8

What does error 901 mean on a SY/MAX local interface?

On Series L or later LIs it means the storage registers hold corrupt data; it is normal on a new LI and clears after keyswitching the processor again. p. 7

Which SY/MAX processors work with the CRM-210?

All Model 400, 500, 600 and 700 processors, which can use several LIs; a Model 300 supports one LI. p. 6

What does a flashing I/O ERROR LED on the remote interface mean?

It means the drop's outputs and inputs are frozen. p. 15

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. 30598-247-01D21
  2. Class 80301
  3. Types CRM-210, 211, 220, 2221
  4. Local/Remote Interface Modules1
  5. Warnings and Cautions2
  6. List of Figures4
  7. 1: Introduction5
    1. 1.1 General Information5
    2. 1.2 Summary of Operation5
  8. 2: Specifications6
    1. 2.1 General Information6
    2. 2.2 Electrical6
    3. 2.3 Environmental7
    4. 2.4 Physical7
  9. 3: Installation7
    1. 3.1 General Information7
    2. 3.2 Inspection7
    3. 3.3 Module Keying7
    4. 3.4 Module Location8
    5. 3.5 Field Wiring8
    6. 3.6 RI Switch Settings8
  10. 4: Operation9
    1. 4.1 General Description9
    2. 4.2 Local Interface Registers9
    3. 4.3 Rack Addressing10
    4. 4.4 Summary13
  11. 5: Troubleshooting14
    1. 5.1 General Information14
    2. 5.2 General Procedures14
    3. 5.3 LI/RI LED Explanation14
    4. 5.4 Fault Isolation Procedures14
    5. 5.5 Undervoltage Lockout Circuit Operation16
    6. 5.6 Module Replacement Procedure16
    7. 5.7 LI/RI Communication Restart16
    8. 5.8 CPU and LI/RI Response to Faults17
    9. 5.9 Obtaining Additional Assistance18
  12. Appendices19
    1. A: LI/RI Update Time19
    2. B: Error Codes21
5 more lines, from page 29 on
  1. C: Channel Expansion29
    1. D: LI Control/Status Registers30
    2. E: LI/RI Power-Up Sequence34
    3. F: LI/RI Addressing with Model 30035
    4. G: Additional Data Line Protection38

From the PDF’s own bookmarks.

The whole text · 6 parts

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 31-3
  2. Pages 4 to 64-6
  3. Pages 7 to 137-13
  4. 5: Troubleshooting14-18
  5. Appendices, pages 19 to 2819-28
  6. Appendices, pages 29 to 3829-38

The file

Revision and size

RevisionBulletin 30598-247-01D2, October 1990
PublisherSquare D Company
Pages38
PDF1.2 MB
TextThe pages are scans; their text was read by OCR, which may hold reading errors.