The text of a manual · part 6 of 6

Local/Remote Interface, Class 8030 Types CRM-210, 211, 220, 222: Appendices, pages 29 to 38

Pages 29 to 38 of 38, from Local/Remote Interface, Class 8030 Types CRM-210, 211, 220, 222

The original document is the PDF (1.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Square D 8030-CRM-210, Square D 8030-CRM-220, Square D 8030-CRM-222, Schneider 8030-CRM-210, Square D 8030-CRM-211, Schneider 8030-CRM-220 and Schneider 8030-CRM-222

Page 29 read from a scan by OCR; it may hold reading errors

Page 29 30598-247-01

APPENDIX C

C.0 CHANNEL EXPANSION

C.1 General Information

This appendix provides information to expand an LI/RI system. Expansion may be accomplished in two ways. The first consists of adding to an existing drop. while the second is to add an additional drop.

Regardless of what type of expansion method is used. the user must develop and enter the ladder logic program for the newly added [/O points. For the specific programming procedures, refer to the CRT Programmer Instruction Bulletin.

C.2 V0 Expansion Considerations

1. The additional [/O must fit within the processor (CPU) addressing capability.

2. The additional 1/O must be able to be supported by the existing LI, if not, an additional LI module(s) will be required.

Note: Mode) 300 can support | LI only.

3. Expansion of a physical drop requires that external registers are available for use at that location by cither a result of:

A. Previously allocated address assignments. B. A reallocation of addresses.

4. The addition of more registers on a channel will increase the LI/RI update time. However. if the register(s) were previously on that channel. the L1/R1 update time should not be significantly increased by additional drops.

The following is a brief description of the two basic expansion alternatives, drop expansion and drop addition.

C.3 Drop Expansion

Drop expansion by a mere addition of hardware alone can be accomplished if, and only if, the previously entered rack addressing allows for it. Therefore, the current system configuration and the defined rack addressing has to be reviewed when contemplating expansion of an existing PC system.

Expansion can be accomplished in one of two ways: i. Replace the existing rack with a larger assembly.

2. With a four function digital lO rack assembly, an expander module (class 8030 Type CRM-115/116) may be used to add a second Digital I/O rack to the drop.

C.4 Drop Addition

Adding a drop can be performed at any time within the limitations of the CPU and LI{s) being used.

The mere addition of the hardware to support a drop to an existing LE channel alone wilt not make a drop operational. °

Alteration of the existing rack addressing assignments and associated ladder program most likely wil! be required.

WARNING: Care must be taken when altering existing rack addressing. Automatic shifting of addresses will occur from the point of alteration. Registers may be changed to locations which were not intended by the designer to be used as I/O points, thus possibly causing unexpected contral action to occur.

Once hardware and software modifications are started, com-piete and verify that they are correct before putting the system into Run or Disable Outputs.

For information on how to alter rack addressing assignments, refer to the CRT Programmer Instruction Bulletin.

When adding a drop or changing rack addressing for a specif-i he LI/R1] update time may be altered. Refer to Appendix AJLI/RI Update Time for more detailed informa- Ton. ;

Page 30 read from a scan by OCR; it may hold reading errors

Page 30 30598-247-01

APPENDIX D

D.O0 LI CONTROL/STATUS REGISTERS

D.1 General information

Control registers 8001 through 8163 (contained in the processor) are used to monitor, and in some cases, control the Local/ Remote Interface (LI) system. Not only is the condition of the LI system reflected in these control registers, but information pertaining to register modules and I/O modules is also tocated in these registers.

The CRM-210 and CRM-211 are two channel LI modules in which three registers are used to communicate directly with the processor (CPU). The first register is an error code control register. The second is a control register for channel | and the third is a control register for channel 2.

The number of contro] registers used to monitor a particular LI system is based on the number of local interfaces used in the system and the number of channels included in each local interface. Each register consists of two parts known as the Status field and data field. The data field can be programmed by the user for contro] functions. The status field, as the name impties, is used just to monitor status of specific system conditions.

D.2 Register Allocation

For the first LI Module in a system, the error code control register is S8163. The channel control registers are $8162 for channel | and $8161 for channel 2.

The following is a listing of the error contro] and channel registers for systems using both channels on each LI up to 7 LI modules.

The contents of the error ontrol registers are discussed in greater detail in Appendix BJ Error Codes. The format for the control data and status Tollow.

REGISTER L.i LOCATION FUNCTION

$8163 First (Right of Error Code

$8162 First CPU) Channel | Control Data and Status $816] First* Channe) 2 Control Data and Status $8160 Second* (Right of Error Code

$8159 Second* first LI Channel | Control] Data and Status 88158 Second* module} Channel 2 Control Data and Status $8157 Third* (Right of Error Code

88156 Third* second LI Channel 1 Control Data and Status $8155 Third* module) Channel 2 Control Data and Status $8154 Fourth* (Right of Error Code

$8153 Fourth* third LI Channel | Control Data and Status $8152 Fourth* module) Channel 2 Control Data and Status $8151 Fifth* (Right of Error Code

$8150 Fifth* fourth Channel | Control Data and Status $8149 Fifth* LI module) Channel 2 Control Data and Status $8148 Sixth* (Right of Error Code

$847 Sixth* fifth LI Channet | Control] Data and Status $8146 Sixth* module) Channel 2 Control] Data and Status $8145 Seventh* (Right of Error Code

$8144 Seventh* sixth LI Channel | Control! Data and Status $8143 Seventh* module) Channel 2 Control] Data and Status

* Indicated LI] register assignments may vary, dependent upon LI position and rack addressing assignments. Control registers are dynamically assigned in accordance with rack addressing and not solely based upon LI! count. For more information, refer to Section

4.3.3, LI Control Register Allocation.

Figure 0.1 - LI Control/Status Register Assignments

Page 31 read from a scan by OCR; it may hold reading errors

Page 31 30598-247-01

D.3 Local Interface Module Control Data Register fiolistisf rst iztnjuolosfselrzte6fs]4]3 [2]. ] UNDEFINED HALT DROP #1 AUTO RESTART HALT DROP #2 UNDEFINED, - - - - - - - - - - - - HALT DROP #3 FAILURE OVERRIDE, - - - - - - ~ HALT DROP #4 UNDEFINED HALT DROP #5 UNDEFINED HALT DROP #6 TXFT HALT DROP #7 FREEZE HALT DROP #8 Channel Control Register Bit Name Description

I KALT DROP #1 When OFF (0) the drop will

2 HALT DROP #2 operate as the ladder logic

3 HALT DROP #3 indictates.

4 HALT DROP #4 When ON (1) the drop will ba HALT DROP #5 be shutdown.

6 HALT DROP #6 |. Input status still valid

7 HALT DROP #7 2. Outputs turn OFF

8 HALT DROP #8 3. Register I/O clear (depending upon module type) 9 FREEZE When ON (1) and a loss of transmission or trans-

Mission error or local rack error occurs, all outputs are maintained in their last state. 10 TXFT Transmission Fault Tolerance determines whether 3 or 10 consecutive transmission errors occur before a channel} error is acknowledged.

OFF(0) = 3 errors

ON(1) = 10 errors i Undefined

2 Undefined t3 FAILURE OVERRIDE When ON (1) allows the channel to continue operating if a drop error on the channel occurs. When OFF (0) and drop error is present, channel will shutdown and processor will halt.

14 Undefined

15 AUTO RESTART When ON (1) allows the channel to attempt to re-establish valid communications with any drop shutdown due to transmission errors, (Bit 13 must be set to enable bit 15 to be recognized.) This control bit accomplishes a similar function as the restart button on the LI module.

16 Undefined

Figure D.2 - LI Control Data Register

Page 32 read from a scan by OCR; it may hold reading errors

Page 32 30598-247-01

D.4 Local Interface Module Control Status Register {Read Only)

[32 | 31 | 30 | 29 ' 28 [ 27 | 26 | 25 | 24 | 23 | 22 | 21 | 20] 19 | 18 | 17 |

LI INTERNAL CHANNEI. USAGE DIAGNOSTICS COMPLETE LI INTERNAL ' - - - CHANNEL USAGE INITIALIZATION COMPLETE LI CHANNEL ID CHANNEL ADDRESSING COMPLETE UNDEFINED, - - - - _ - _ - _ - ~, - - - - - - - - - UNDEFINED DROP #8 ERROR SHUTDOWN, - DROP #1 ERROR SHUTDOWN DROP #7 ERROR SHUTDOWN, - - - DROP #2 ERROR SHUTDOWN DROP #6 ERROR SHUTDOWN, - - - - - ~ DROP #3 ERROR SHUTDOWN DROP #5 ERROR SHUTDOWN DROP #4

ERROR SHUTDOWN

Channel Control

Register Bit Name Description \7 Channel Diagnostics Complete When ON (1) Ll channe!] completed its diagnostics. 18 Channel Initialization Complete When ON (1) |. Ris have completed their diagnostics 2. Valid LIVR1 communication 3. Image table updating sequence complete 19 Channel Addressing Complete When ON (1), indicates the CPU has loaded valid rack addressing infurrration into the LI. 20 Undefined 21 DROP #1 ERROR SHUTDOWN f drop has been rack addressed: 22 DROP #2 ERROR SHUTDOWN When OFF (0) drop is operating 23 DROP #3 ERROR SIIUTDOWN When ON (1) drop is shutdown duc to cror. 24 DROP #4 ERROR SHUTDOWN 25 DROP #4 ERROR SHUTDOWN lf drop has NOT been rack addressed: 26 DROP #6 ERROR SHUTDOWN 27 DROP #7 ERROR SHUTDOWN When OFF (U} no drop exists 28 _ | DROP #8 ERROR SHUTDOWN When ON (t) drop exists without addressing 29 Undefined 30 LI Channel [D When OFF (0), indicates a | channel Li. All LI internal Usage 32 LI internal Usage Figure D3 - LI Control Status Register D.5 Detailed Description of Control CAUTION: All inputs assigned to a drop that has halted Data/Status Bits because of the DROP HALT bit function momentarily show an OFF (0) status in the proc- The LI channel control register, bits 1-16, are initially reset essor. Within 5 seconds. all inputs are again OFF (0) when the LI is installed. Once altered by program- updated and valid input data is contained within ming equipment, data entry, or by the ladder program, these the processor.

bits will retain their state until altered again. A drop programmed to halt will have valid updated input Malt Bit(s) (1-8) Status contained within the LI! image table.

CAUTION: Do not use the DROP HALT bit function of the CRM-210/211 Local Interface Modules until you Freeze Bit (9) understand the following operational character-istic and the CAUTION below. The status of When the FREEZE BIT ibit 9} is set ON (1) by the user, all inputs reported in the ladder program for a drop the outputs on all the drops of a particular channel will retain shut down with the DROP HALT bit function, is their last state. ON or OFF when any of the following exist: not as described in the Instruction Builetin. ; |. A communication error at a drop (ie. cut cable) Any drop on a channel may be programmed to HALT, that is, tuming OFF ai] its associated outputs. This is done by setting 2. The CPU HALT BIT (S8176-1) is set ON (1). (ic. CPU its respective LI channel DROP HALT bit to ON (1). error or programmed Halt).

Page 33 read from a scan by OCR; it may hold reading errors

3. Power Joss at the local (CPU) rack.

Note: Although the freeze bit may be set on (1), the operation of the freeze function depends upon the detected error.

In the following cases, the drops will not be frozen, but set OFF (0).

1. Drop with internal error (ie. power loss, faulty RI, read after write error) will have it outputs reset OFF (0).

2. CPU turned into HALT via keyswitch or $8176-3 will cause all drops to reset OFF (0).

CAUTION: Do not use the FREEZE BIT function of the CRM-210/211 Local Interface Modules until you have read and understand the following series related operational differences. The status of inputs and outputs for a failed drop, as reported in the ladder program, will be different depending on the scrics module being used.

General Information

When using the CRM-2t0/211 Local Interface Modules, series L through N1, the freeze bit function operates in a manner different from other series modules. This errata sheet details those operational differences.

The operation of the freeze function is as follows:

Pre Series L

The freeze bit function operates as described previously in

Section D.5Jand as shown in the LI/RI fault status table in Section 5.7.

Series L through Nt

If a loss of communication occurs to a remote drop, the operation of the CRM-210/211 Module with Failure Override ON and the freeze bit set on is as follows:

1, All outputs in the remote rack will hold their last state.

2. While communication with the remote rack is interrupted, the ladder diagram program will show all Input/Output puints assuciated with the frozen drops 1-4 as being off. The LO puints in the ladder program associated with the frozen drops 5-8 will reflect their last state.

3. Once communication is reestablished with the remute rack, the ladder diagram program will again accurately reflect the state of ali I/O in the remote rack.

Serles NZ and later

The freeze bit function operates as described in Section D.5 and as shown in the LI/RI fault status table in Section 5.7.

Turning Off Frozen Drops

1. Power cycling a drop with frozen outputs will reset, turn OFF all the outputs, regardless of the processor state

2. When valid communications exist. setting a particular LI halt bit ON (1) will result in turning off frazen oulputs.

Note that if the CPU is halted due to an error, turning the key switch to halt wilf not reset frozen drops.

Page 33 30598-247-01

Restarting Frozen Drops

1. Placing the CPU in either Run or Disable Outputs. by either turning the CPL’ keyswitch or setting the appropriate control register bits ($8176). will atlaw all draps with valid communications to restart in accordance with the user program.

2. Power cycling the CPU when st is in either Run or Disable Outputs.

3. To automatically restart all drops. the CPU must be running. Also, the Failure Override Bit (bit 13) and the Aute Restart Bit (bit 15} must be previously set ON (1). This will function provided valid communications cxist between the operational CPU and dropts).

4, Pushing the RESTART (RESET) button on the LI. if and only if, the CPU and communications are fully operativun-al. (Failure Override must be set ON (1).

Transmission Fault Tolerance Bit (10)

In harsh electromagnetically noisy environments, the possi-bility of nuisance system shutdowns could occur, If communications are disrupted, the LI/RI system is designed to establish a valid data transmission 3 times before acknowledging these errors to the processor.

Transmission Error Detection

Two types of data transmission error detection methods are used in the 1.U/RE communications link.

The first detection method counts the number of times a specific block of data is determined to be invalid. The second detection method counts the number of consecutive blocks of data which are determined to be invalid

The accumulative values for each type of transmission error on each of the independent channels is kept internally by the LI and RI module. When any one good transmission occurs on a channel, the respective transmission error counters for that channel are reset to zero.

The user has the option of increasing the transmission fault tolcrance Ievcl from 3 to 10 transmission errors. This is done by setting the Transmission Fault Tolerance Bit ON (1). Be aware that by sctting the number of transmission errors to 10 will require additional time for the system to recognize a transmission error and cause a shutdown.

Note that the transmission fault tolerance unly affects the operation of the system when invalid data is detected. In the event thal data is Jast due to cable damage, hardware malfunctions transmission acknowledgements will not be present in the LI/RI full dupléx communication link. the system wall shutdown immediately.

When the LI acknowledges excessive transmission errors, the entire system will shutdown unless the Failure Override Bit, (Bit 13) is set ON (1).

Fallure Override Bit (13) The LI is designed so thal upon recognizing any drop error, it will signal the CPU to terminate ladder program processing and shuidown.,

Each channel has a Failure Override Bit. The Failure Override Bit provides a means of preventing the drop error signal

Page 34 read from a scan by OCR; it may hold reading errors

Page 34 30598-247-01 from affecting the CPU. With the Failure Override Bit set ON (1), a detected drop error will shutdown that drop, but will allow the rest of the channei to operate.

CAUTION: |. Care must be taken whenever the Failure Override Bit is set ON (1), because the sys- tem will continue 10 operate when drop errors occur. However, it is still possible to halt drops thru ladder programming by setting ON (1) selected Drop Halt Bits.

hm

. If Failure Override Bit has been set ON (1) and a drop error shutdown occurs, foliowed by the Failure Override Bit being turned OFF (0), the channel will shutdown, The channel shutdown will in turn cause the system to shuldewi,

This bit allows for more system flexibility, therefore improv-ing troubleshooting and start-up capabilities.

Auto Restart Bit (15}

Ifa drop has been strulduwn due to transmission error, seating bit [5 ON (1) wiil allow the LI to automatically atternpt to re-establish valid communication to that drop. It stuuld be noted, however, that the processor must be operating in Run or Disable Outputs. In order to keep the processor running under error conditions, the Failure Override Bit (Bit 13) must be ON (1).

This bit acts in the same manner as does the RESTART (RESET) button on the front of the respective LI module. The AUTO RESTART BIT has the advantage of attempting to bring a drop back on line as soon as possible without requiring personnel to push the L] RESTART buttop_korm information on the RESTART button, refer tof Section 5 6 LI/RI Communication Restart (Pushbutton).

Drop Error Shutdown Bit(s) (21-28)

Drop Error Shutdown bits are used tor diagnostic purposes. They are also used to initiate contro] functions when the Failure Override Bit is set ON (Ef).

The Drop Error Shutdown bit of a non-existent or an undefined drop will be displayed as ON (1 }*, because the LI is not communicating with the drop. The drop error bit of an undefined drop being ON (1}* will not affect the shutdown operation of the system.

Note that these bits will be extremely useful when imple-menting applications which use ladder control programs to affect conditional failure overriding and programmed shutdowns,

* Some programmers are capable of displaying information which is relevant only to the present system configuration. For additional information, refer to a programming instruction bulletin.

APPENDIX E

E.0 LI/RI POWER-UP SEQUENCE

E.1 General Information

This appendix will describe the power-up sequence for the LIURI VO system.

E.2 Li Light Sequence

The foltowing sequence of events occurs when the LI is energized, or the processor keyswitch goes from HALT to RUN or DISABLE OUTPUTS:

1. The MODULE ERROR LED blinks ON, OFF, ON, OFF, and remains OFF if no detected error*® exists within the LI.

2. The CHANNEL ERROR and I[ALT LED's are ON and turn OFF when all the self-diagnostic routines are completed.

3. The green channel RUN LED will turn ON when the LI is cammunicating.

*The MODULE ERROR LED will turn ON if this module has initiated a rack error condition, thus halting the system when:

1. A self-diagnostic error is detected.

2. Missing defined racks (unless the Failure Override Bit is ON (1).

3. An illega! rack addressing map is detected

E.3 Ri Light Sequence

The following sequence of events occurs when the RI is energized:

1. Allred LED’s turn ON and then OFF,

2. The red HALT LED will turn OFF when the grecn RUN LED turns ON.

3. The green RUN LED turns ON when the RI is communicating to its rack assembly and the CPU is in Run or Disabled Outputs.

When the processor keyswitch goes from HALT to RUN or DISABLE OUTPUTS, only steps 2 and 3 occur.

The MODULE ERROR LED will remain ON only when a self-diagnostic error is detected.

E.4 LI/AI Initialization

1. When power is applied, self-diagnostic routines are initiated and verified within the LI, RI, CPU, and other regis-ler modules. Completion of the self-diagnostics insures that these modules are operational.

2. The LI then verifies cammunicatians with all of its drops.

3. The CPU will initiate the toading of the user defined rack addressing map into the LI.

Hf valid LI/RI communications cannot be established, an error will be generated by the LI module. This error will halt the processor unless the failure override bit of that LI channel contro] register has been set ON (1).

Page 35 read from a scan by OCR; it may hold reading errors

Page 35 30598-247-01

APPENDIX F

F.0 LAI ADDRESSING WITH MODEL 300

F.1 General Information

The following two examples ate used to illustrate the concept of the Model 300 local and remote address assignments. The first utilizes a Model 300 housed in a digital YO rack. The second has the Model 300 in a register rack. In both examples, there are 256 digital /O and 6 register modules.

When examining these Model 300 examples, observe the following points:

1. Since the Mode] 300 can support only one LI and address a maximum of | 1? registers, adding an E.I does not increase the number of useable registers, but does permit the use of remote I/O.

2. Assign as many registers as possible to the LI. This type of register assignment allows for flexible remote /O configurations.

3. The register assignments are distributed in an equitable manner between the two channels of the LI. This method allows for a uniform LI/RI update time.

4. The digital I/O are assigned to the first 16 registers because these are the forcible registers within the Model 300°s 112 useable registers.

F.2 Local (Model 300 CPU) Digital Rack Assignments

This first example demonstrates the use of a Model 300 being housed in a digital rack tu support local I/O while also supporting remote VO. The local (CPU) rack is supporting 64 digital I/O points and a 2 channel LI module with remote drops. 192 digital 1/0 points and 6 register modules are assigned to the drops among the two channels.

The maximum update time for any drop on channel I is 54.7ms. The maximum update time for the drop on channel 2 is 84.0ms. For more information, refer to Appendix A, LI/RI Update Time.

F.2.1 LOCAL (CPU) RACK

SLOT e 1 START ADDRESS | S5 | si

LI |CPUle4 vrezTeaL Ivo

LOCAL CRM|s3@e; 4 REGISTERS 218 S1-1 CCPU) THRU RACK

S4-16

ENO ADDRESS $112] S4

Figure F.1 - Local (Model 300 CPU) Digital Rack Address Assignments

Slot 1- Four registers have been assigned to the Model 300 for the 64 local digital [/O. (SE-1 thru S4-16)

Note hal in a digital rack, addresses for digital 1/O are always assigned to slow 1.

Slot 2- The remaining [08 registers are assigned io the LI module (CRM-210} so the CPU may access and use them as either external or internals. (SS thru S112)

F.2.2 CHANNEL 1, DROP #1 RACK ADDRESS ASSIGNMENTS SLOT e2 1

START ADDRESS ss | SL

LI |CPUle4 orerten ro. CRM|sew| + recrsters 9 LOCAL

218 Stat Ree EMD AoORESsS [S112] 54 54-16 Ck ] CHANNEL 1 2 1 OROP #1 - |

RI |e4 prerma 170 CRM) « necrsters 228) ss-:

ifm | Pen

L___/

Figure F.2 - Channel 1, Drop #1 Rack Address Assignments

A total of 64 digital I/O points are assigned to this remote drop. Note that this drop uses a low profile RI (Class 8030 Type CRM-220) which is designed to fit into four function LO rack assemblies only. This same addressing scheme can be used if a Type CRM-222 were used.

Slot 1- The RI module (CRM-220) has been assigned four registers for the 64 remote digital lO. (S5-1 thru S8-16)

Slot 2- No address assignments required.

F.2.2 CHANNEL 1, DROP #2 RACK ADDRESS ASSIGNMENTS stor 2 1 START PODRESS §={ 395 | SI

LI |CPU\s¢ orsrtan 1/0 LoceL CRM) 38) 4 REGLSTERS (CPUS

218 si-1 Aare END ADORESS § [S112] s4 se-16 Cc

T CHANNEL 1 |

DROP #1

1 - | RI jes oretr™ 1/0 CRM] 4 REGISTERS e228) ss~) THR - | sa $0-16 ea: DROP #2 | 817 33 BCO RT hize overt, 170 RI ci @ RECISTERS 141/222! ¢9-1 THRU $16-16

S32 | Sis

Figure F.3 - Channel t, Drop #2 Rack Address Assignments

Page 36 read from a scan by OCR; it may hold reading errors

Page 36 30598-247-01

The second drop is similar to the first in that it has digital 1/0. However, this drop has double the digital 1/O points and is also using a BCD input module.

Siot 1- The RI module (CRM-222) has been assigned 8 registers for the 128 remote digital I/O. (S9-1 thru St6-16)

Slot 2- 16 registers have been assigned for the BCD input module. ($17 thru $32)

F.2.4 CHANNEL 2, DAOP #1 RACK ADDRESS ASSIGNMENTS goat 2 1 ‘ATORT ROONESS «| 95 | 1

LT CPU m4 orstra. 10! 1 orca el ai-1 ccPu) Bad erg | RACK

DROP #1

_|e 16 F, + FUTURE 2. OROP #2 CUF TO CROP #8)

Figure F.4 - Channal 2, Drop #1 Rack Address Assignments

For this next drop, a 9 slot registcr rack is connected to channel] 2. Note that the addrcesscs for channel 2 start at one greater than the ending address for channel 1. In other words, when channel | ends, channel 2 begins.

Requirements for register modules vary. As an example, a 4 channel analog module requires 4 registers for complete addressing. A BCD VO module requircs 16 registers.

Slot 1- No address registers arc required since there are no digital {/O points.

Slot 2- Four registers are assigned to a 4 channel analog input module. ($33 thru $36}

Slot 3- Four registers are assigned to a 4 channel analog output module. ($37 thru 540)

Slot 4- 16 registers are assigned to a 16 (4 digit) BCD input module. (S41 thru $56)

Slot 5- 16 registers are assigned to a 16 (4 digit) BCD input module, (S57 thru $72)

Slot 6- 16 registers are assigned to a 16 (4 digit) BCD output module. ($73 thru 588)

Slot 7-9*- No address assignments required.

* Slot 9 and above cannot be addressed by the Model 300. (These slots may be uscd to power any register module which require only power and does not require registers such as a D-LOG or SY/NET module).

F.3 Local (Model 300 CPU) Register Rack Address Assignments

This second exampie demonstrates the use of a Mode] 300 in a register rack. The local (CPU) rack will house the processor, LI and 5 additional register modules.

Note how the addresses are assigned in very much the same manner as the previous example and specifically the digital VO and register modules.

The first 16 of the 112 total addressable registers of the Model 300 are used for digital /O since they may be forced.

The Model 300 Processor can support one L] module. The addition of a LI module does not increase the number of additional regisiers, however, it does permit the use of remote 1/0.

In order to maximize the number of registers available to the LI, and facilitate for easier future expansion, the ending addresses are calculated for the slots by subtracting the num-her of registers required for each modute in the CPU rack from the available registers. (i.e. The ending address for the last addressed slot. in this case slot 8. is 112 and the preced-ing slot’s ending address should be |12 minus the number of registers required for this module.)

The maximum update time for any drop on channe] | is 17.4ms. The maximum update time for the drop on channel 2 is 44.4ms. For more information on how to calculate LI/RI update times, refer tof Appendix A.JLU/RI Update Time.

F.3.1 LOCAL CPU RACK

SLOT 1 2 35 4 § 6 7 8 9”™

STRAT RODRESS - $1 $S7 | S61 | S65 | S81) S97) - cPsjLt|, javolpzalecplecojecplosse| LOCAL see |CRM|, |RIMIROMIRTMIRIMIROMIDLM| Goat

210 121/121]1413141/141/118 END ROORESS - | $56

56@ | S64 | Sag | S86 S112) -

™ SLOT 9 CANNOT BE ROORESSED BY THE MODEL 308. CTHIS SLOT MAY GE USED TO POWER A O-LOG OR SY/NET ROOULEJ

Figure F.5 - Local (Model 300 CPU} Ragister Rack Address Assignments

Slot 1- No address registers are required since there are no digital VO points.

Slot 2- 56 registers are assipned to the LI (CRM-210) for the 2 remote 1/O channets and future expansion. (S1 thru $56)

Slot 3- No register assignments required. (Spare slot for future expansion.)

Slot 4 4 registers are assigned to a 4 point analog input module. ($57 thru $60}

Slot 5- 4 registers are assigned to a 4 point analog output module. (S61 ihru $64)

Slot 6- 16 registers are assigned to a BCD input module. (S65 thru $80)

Slot 7- 16 registers are assigned to a 16 (4 digit) BCD input module. ($81 thru $96)

Page 37 read from a scan by OCR; it may hold reading errors

Slot 8- 16 registers are assigned to a 16 (4 digit) BCD output module. ($97 thru $112)

Slot 9- This slot is not addressable by the Modei 300. (This slot can be used to support a module which only requires power. For example, a D-LOG (DLM-1 10) or SY/NET (CRM-510).)

F.3.2 CHANNEL 1, DROP #1 RACK ADDRESS ASSIGNMENTS suoT 1 2 53 4 5 6 7 8 9 START AOOMESS | - | Si 957 | 961 | 965 | sur | S87} - cPulLI| jAzOlD/AIBCO|BCOlecDjoxe| ec 5 5 rsws|CRM| IRIMIROMRIM|RIMIROMIOLM| pac, 21a) |1eifierji41iaajisiliia

See | Se¢ | SOB | S8G S112) -

OROP #1

RI jes prcrta 1/0 ICRM| 4 REGISTERS

220} si~1 THRU - S4 94-16

Figure F.6 - Channel 1, Drop #1 Rack Address Assignments

This drop will support 64 I/O. !t uses a Type CRM-220 RI module which means that the drop must use 4 function VO rack assemblies.

Slot 1- Four registers are required for the 64 digital I/O. (S1-1 thru S4-16)

Slot 2- No address assignments required.

F.3.3 CHANNEL 1, DROP #2 RACK ADDRESS ASSIGNMENTS gloT 1 2 3 4 S$ 6 7 8 9 START ADORESS -~ | S31 957 | 061 | 905 | S81 | s87) - CPULLI{ [A/DID/AIBCDIBCOIBCO|>-6| cepy 5 see (CRM RIMROMIRIMRIMIROMIDLM pack 218 121]/121]141/141/141)112

LOCAL

END ADORESS - | 358 966 | 2a4 | S08 | S88 S112) - come. 1 | 2 1 DROP #1

- St

RI [es orerta 1/0 CRM 4 REGISTERS e228) 81-1 - 34 $4-16 Figure F.7 - Channel 1, Orop #2 a OROP #2 Rack Address Assignments - 738

RI [es oer, 1/0 CRM] 4 RECISTERS e2e2| se-1 - Et $8-16

Page 37 30598-247-01

This drop is identical to Drop #1 in that it has 64 digital /O and differs in only that a Type CRM-222 is used. The Type CRM-222 RI] can be used in any type of rack assembly, 4 or 8 function I/O rack as well as register rack assemblies.

Slot 1- 4 registers are required for the 64 digital [/O. (S5-1 thru S8-16)

Slot 2- No address assignments required.

F.3.4 CHANNEL 2, DROP #1 RACK ADDRESS ASSIGNMENTS

SLOT 1 2 3 S§ 6 7 8 9 START ADORESS | - | $1 o57 | sui | ses | soi | 97] - ceulLz|, |avoloAlecolecolecdlaux| LSEAL rase|CRM) |RIMIROMRIMIRIMIROMIOLM| Gory

218 121]121/141)141/141/118 eno nponess | - | 958 | sum | 264 | see | soe jsii2| - omer 1 | |cwveus. 2

2 1 OROP #1 21 - | $1 $17| 33

DROP #1

RI |ea oxerra 1/0 BCD) AT |1ee orerra 1/0 ICRM| « REGISTER RIMICRM| 2 REcrsTers 228) si-; 141}222| sey

- | ss $4-16 ese |$16 S16-16

2 t DROP #2 - oS

FUTURE

CUP TO DROP #8) RI |e4 orerva 170 CRM) « REGISTERS 222] g4-1

THRU ~- 39 90-16

|

Figure F.8 - Channel 2, Drop #1 Rack Address Assignments

This drop supports 128 digital [/O and a BCD input module.

Slot 1- 8 registers are assigned to support the 128 digital /O. (S9-1 thru $16-16)

Slot 2- 16 registers are assigned to the BDC input module.

(S17 thru $32}

Page 38 read from a scan by OCR; it may hold reading errors

Page 38 30598-247-01

APPENDIXG ADDITIONAL DATA LINE PROTECTION

For outdoor communication cable, or indoor cable that is subject to severe electrical disturbances, overvoltage transient protection is required. This protection is to guard both modules and cable from damage. To accomplish this, a device that suppresses transients caused by lightning, inductive switching and electrostatic discharge must be used. This device is called a data fine protector (DLP).

The recommended DLP is the Square D Class 8030 CBP-310.

IMPORTANT INSTALLATION CONSIDERATIONS

1.

Cable runs between the CRM-2XxX Interface Modules and panel DLPs should be kept as short as possible. The shield in the cable can be connected to the DLP’s “'N/C”’ screw; the portion of the unshielded cable must be kept as short as possible. The Interface Module wiring is standard.

. A pane! DLP should be solidly grounded, via its ground lead, directly to the panel.

. Building DLPs are suggested for outdoor runs of cable to provide primary level protection against lightning-induced transients. The DLPs should preferably be installed at the point of building entry to keep all transients outside the building, otherwise it may be necessary to electromagnetically shield the cable so that the high voltage transients aren't coupled into cables within the building. Shielding the cable can be done with a separate, properly grounded, steel conduit.

. Building OLPs must be solidly grounded, via their GND lead, directly to building steel or to the power ground.

. The load of each DLP is equal to 200 feet of cable.

. Each SY/MAX rack and power supply must be solidly grounded. Refer to the "Planning and Installation Guide,” Instruction Bulletin #30598-175-XX.

. See Instruction Bulletin #30598-518-01 for further details on the Data Line Protector.

. The CRM-210/211 Modules Series 0 and later have this isolation built into the module and they do not require a DLP.