The text of a manual · part 5 of 6

Local/Remote Interface, Class 8030 Types CRM-210, 211, 220, 222: Appendices, pages 19 to 28

Pages 19 to 28 of 38, from Local/Remote Interface, Class 8030 Types CRM-210, 211, 220, 222

The original document is the PDF (1.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Square D 8030-CRM-210, Square D 8030-CRM-220, Square D 8030-CRM-222, Schneider 8030-CRM-210, Square D 8030-CRM-211, Schneider 8030-CRM-220 and Schneider 8030-CRM-222

Page 19 read from a scan by OCR; it may hold reading errors

Page 19 30598-247-01

APPENDIX A

A.O0 LI/RI UPDATE TIME

A.1 General Information

This appendix provides equations for calculation of the LVRI update time.

Update time refers to the time required to pass information in cither direction between the LI image tuble and the RI image table.

Update time should not be confused with throughput ame. Throughput time is the time required from the actuation of an input until an output action occurs. Throughput time also includes I/O module response time as well as CPU processing time. Further information regarding throughput joverall system response) is covered in the Planning and Installation Guide Instruction Bulletin, 30598-1775.

A.2 Channel Update Time

Channel update time 1s dependent on the update Gime of the drop with the greatest number of repisters assigned to it und the total number of registers on the channel. Therelore. by calculating the update time of that particular drop, the worst case channel update time may be deternuned.

A.3 Drop Update Time

One of two equations are used to calculate drop update time. For the purpose of these equations, drops will be pul into two categories, digital and register, The digital drop is a pure digital drop (8 or Jess registers*) with no register modules. While the register drop will contain register modules or a combination of register and digital modules.

* For 9 or more registers, use register drop equations.

A.4 Update Time Equation Variables

D, Total digital drops on the channel. (0-8)

R Total register drops (or digital/register drops) on the channel, (1-8)

DR = Total register addresses assigned to alt digital drops. (0-64)

RR = Total register addresses assigned to all register drops. (1-255)

X = Register addresses assigned to the drop being evaluated. (1-8) If more than 8 registers arc assigned, use X = 8.

Note that actual performance times may be better than calculations for channels with many registers.

A.5 Drop Update Time Equations Use this equation for a channel with only digital drops.

Digital Channel Drop Update Time (ms} =2.31D + DR + X + 0.79

Use this equation tor all other remote I/O channels.

Register Channel Drop Update Time (ms) =3.31D + DR + 3.15R + 1.24(RR + X) + 1-52

A.6 Example #1

This example works out the drop update time for a purely digitat channel. This exumple has the following relevant attri-butes.

SLOT 3} @ 3 4 5 & F7 8B 9 start aporess [ - | si | - | 957 | 561 | $85 sei|$37| - ceulLt|, avon/aBepiecofecdjoso FERS mse (CRM RIMROMRIMIRIMROMIDLM poe, 218 121 124141/141)141/11@ “ ENO pcorness | - |sse| - | s6e see | sea ses |si12| - CHANNEL 1 | 2 4 OROP #1 - SL

RI |e¢ orertma to

ICRXM| 4 REGISTERS eee) 51-1

THAY $4-16

Figure A.1 - Digital) Channel

CHANNEL | Consists of ene drop and 4 registers. DROP #1] Consists of 4 registers used for digital 'O CHANNEL 2 Not used.

Channel! | Digital Drop Update Time

=2731D + DR + X +079 =2.3l(1) + (4) + (4) +0.79 =]) Ims

A.7 Example #2

This example works out the drop update lime equution for a combinational (register) channel,

SLOT 1 2 3 4 §& stort sooress = [ 61 ] - [ses =Pu / ut MODEL |CRH LUCA ¢C°U) sep |21a RACK © ORES ssa - |sea CntewaeL 1 CHROEL 2 DROP #) DROF #1 24 123 4 5 6 7 @ 9 - Se - [8493 }s4ar | 96a1 |9517/o535 AL |:2@ otgrvm 170 RI JA/B/O/ AIBC OSC OECD RM| a necterone HRHIRTM|ROKIRTHI2 T MIROM 22|s63-1 PPPS 1141] b4) saris = _]$56]ssam] 5516/8532] 9S48 - + FUTYRE 2 1 DROP #2 CUP *O DROP #6) £47? S08

BCO| FI |iem orcivm xo 4LMICKM| @ MECISTERs 141)222|sse1-1

THs sane | ee oxte-i6

Figure A.2 - Register Channel

Page 20 read from a scan by OCR; it may hold reading errors

Page 20 30598-247-01

CHANNEL | Consists of two drops and 32 registers.

DROP #1 Consists of 8 registers used for digital [/O. DROP #2 Consists of 24 registers, some used for data storage. CHANNEL 2 Consists of one drop and 56 registers DROP #1 Consists of 56 registers used for data storage.

Note that only the register drop update time equations can be used since neither channel has only digital drops.

Channel | Drop Update Time

=2.31D + DR + 3.1SR + 1.24(RR + X} + 1.52 =2.511) + (8) + 3.1501) + 1.24024 + 8) + 1.52 =54.7ms.

Channel 2 Drop Update Time =2.31D + DR + 3.15R + 1.24(RR + X) + 1.52 =2.31(0) + (0) + 3.15(1) + 1.24(56 + 8) + 1.52

=84.0ms.

A.8 Register Optimization

By allocating only the number of registers which will be used by a register module, channel update time can be minimized. For example, if only five of the 16 registers of a RIM 141 BCD Output Module are actually needed, assign only five. This register reduction of 16 to 5 will result in a 15ms channel update time savings.

Page 21 read from a scan by OCR; it may hold reading errors

Page 21 30598-247-01

APPENDIX B - - ERROR CODES

B.1 introduction And Description

B.1.1 GENERAL INFORMATION

Errors detected by the processor and error codes annunciat-ed on the CRT provide the operator with information useful in isolating problems.

Some errors are indicated as messages on the screen display while other error indications involve error code numbers. Since the messages are self explanatory, this appendix deals directly with the numbered error codes.

These error code numbers can be broken into (wo general categories and are indicated in different locations on the CRT screen.

In the first category are the peripheral to PC system interaction errors of which 3 classifications of error codes exist. These errors are indicated at the bottom of the screen display or for some special cases, in the status register of a communications rung.

In the second category are the PC system operational errors which are errors detected within the processor or any one of the modules contained in a programmable controller system. These errors are indicated in the STATUS Mode display next to the label) ERROR NUMBER, The number displayed is also the number contained in the error code control register 8175 or possibly in a Local Interface Module error code control register (when using remote 1/0).

B.1.2 PERIPHERAL TO PC SYSTEM INTERACTION ERRORS

These types of errors are associated with attempts to per-form illegal operations with the processor or the communication hardware is not functioning properly. This category of error will only be generated when using the keyboard !o command processor operations or when the processor is attempting communication with other responding devices.

The three classifications of peripheral to PC system interaction error codes are: Processor, Transmission, and Tape. When an error occurs while a programmer is connected to the processor, one of these messages will be shown on the display along with a number. Should an error occur during the execution of a processor communication rung a Processor Error will be used to indicate the fault. The number code will be shown when the status register of the communication rung is displayed.

Processor Errors

These errors indicate that the operation attempted was not successfully completed. The crror code numbers range from Ol thru 99. To resolve the error situation, check the error code description in the following table. use the CLEAR key to clear the error indication if the error has been displayed on a programmer, and take the appropriate recourse action. Error codes indicated by an asterisk (*) in the following Error Code Table. may also be displayed in the status regis-ler of a communications rung.

PROCESSOR ERROR CODE TABLE

Error Code No

Error Description ol* legal protocol opcode, the device does not recognize the instruction. Reenter the desired operation.

02

Iilegal intermediate code format. Reenter the desired operation.

03*

An illegal address has been attempted.

04

INegal rack addressing has been attempted.

05*

An instruction has been attempted which is not allowed in the processor. (Example: Square root in Model 300 processor.)

06

Item being searched for cannot be found.

o7*

An attempt has been made to alter data in a protected register. Check Control Register 8176.

08

An attempt has been made to access protected memory. Check Control Register 8176.

09*

An attempt has been made to alter data in a READ only register or a register containing external inputs.

An attempt has been made to exceed memory limitations.

Communications error {receiver overflow). Reenter the desired operation.

legal CPU rack addressing: Register assignments must be divisible by four.

13"

Communications error (link error). This error is generated by the processor, Check Control Register 8175 or the status register of the communication rung. Check cable connections between devices.

14

The operation that has been atternpted is not allowed in RUN.

1 5*

Communication overflow. Check the baud rate for compatibility between communicating devices. Reenter the desired operation.

The register count in a communication rung is 100 large for the processor.

17*

The remote device is inactive. This error code is generated by the Network Interface Module. Check cable connections between devices.

The rung number used is not allowed.

An illegat READ parameter has been assigned.

An illegal channel number, or no channel number has been assigned.

Trying to change a forced bit or WRITE to an external output while the processor is in HALT.

The forcing function is inhibited from the processor COMM port.

An attempt has been made to alter data in a fenced register.

An attempt has been made to force a nonforceabie register.

Page 22 read from a scan by OCR; it may hold reading errors

Page 22 30598-247-01 25« CPU error, check Control Register 8175. Refer 58 Unused to the following section on CPU/LI errors. 59 Unused 27 Memory error, A CLEAR ALL operation is 60 numbers above 8189 not allowed. required. 61 MARK ST. SUB rung cannot be inserted- 28 An illegal baud rate was selected. append only allowed. 298 An attempt has been made to send a message 62 RTN (return) rungs are not allowed in ladder with an illegal route. area. An attempt has been made to alter PROM MARK number previously used in the 30 memory after the PROM inhibit coil was 63 program. Each MARK instruction must have a entered in memory. unique number assigned. 31* | See Tape Errors Operation is not allowed while the processor is oe : 64 in RUN. Cannot delete a RTN if any GOSUB Operation is not allowed in PROM memory : 32 (such as inserting, deleting, or replacing a rung). contains the same MARK number. . Operation is not allowed. Cannot delete 33 See Tape Errors 65 MARK ST. SUB rung unless all subroutines For UVPROM processors only: Read after are deleted. White error, panty error, or security jumper, 34 | was removed and no UVPROM inhibit coil 66 | Operation is not allowed, cannot delete was programmed into memory. MARK having an associated RTN (return). * Operation is not allowed, RTN rungs must 35 =, Errors 5 ‘lowed on thi 67 have an associated MARK number. 36 eplace rung operations are not allowed on this Operation is not allowed, onl RT y one N per =, - - - and insert operations only. 68 MARK number is allowed. = mare ars Operation is not allowed while the processor is 38 Unused 69 in RUN, GOSUB cannot invoke a 39* | Alarm already set within the D-LOG Module. subroutine having no RTN. 40 Unused Operation is not allowed while the processor is : , 70 in RUN, GOTO rung cannot jump to a An illegal register WRITE. The D-LOG module : * 41* | does not accept a register WRITE into certain MARK having an associated RIN. - registers. Operation is not allowed while the processor is 7) U d 1 in RUN, cannot delete MARK until all nuse GOSUBs or GOTOs with the same number are 43* An illegal operation has been attempted. D- deleted. LOG Module protected. Operation is not allowed while the processor is 44 Unused in RUN, rung cannot have unused MARK ne ” number. A GOTO or GOSUB with an 45* oeration ee eroprea D-LOG Module tape 72 | undefined MARK is not allowed. The MARK - must be programmed before the GOTO or 46 | Unused GOSUB is programmed. 47* | Operation is not allowed due to keyswitch 73 Unused position. 74 Unused Programming of an MCR in subroutine area is 48 not allowed. 75 Unused 1/O, Register or Channel is safeguarded; used 76__| Unused 49 in Type SCP-544 RAM/PROM Processor, 77 Unused 50 Rack Addressing is not alterable when forcing 39 | Operation is not allowed when the processor is IS ACLIVE. in RUN while the Timed Interrupt is enabled. A module is not seated properly or missing, or 51* | no rack address assigned to the module, or the address exceeds the capability of the processor. 52 Unused 53* | See Tape Errors 54 HWegal MARK number. 55 See Tape Errors 56 Unused 57 Unused

Page 23 read from a scan by OCR; it may hold reading errors

Tape Errors

These errors are generated when performing tape operations. When the processor is operating with a Loader/Recorder through the use of communications rungs, the status register of that rung can be checked for the presence of an error condition.

Error Code Error Description No. 31" The end of the tape was encountered before the operation could be completed.

Tape Data Error detected, the block of data 33* | involved in the Read or Write operation was faulty.

The tape cartridge is not seated properly or is

35* | missing, or the “Record” tab on the cartridge has been set to the Write Inhibit position.

An attempt to Skip or Read a file was made when already past the last file on the tape.

53* | illegal Tape Format, Erase Track Required.

Tape operation has been aborted. Retry the operation.

37*

55*

Transmission Errors

Communication errors due to hardware problems are an-nunciated on the CRT screen by the message “Transmission Error” followed by a number.

The error code numbers that appear are the numbers 1, 72, and 74. When an error such as this occurs, check all] cable connections and BAUD rates (Register 8169), then use the CLEAR key to clear the error indication. When all connections are secure, retry the operation.

B.1.3 PC SYSTEM OPERATIONAL ERRORS

These error codes indicate PC system operational errors and consist of a five digit decimal value. These error codes or (ERROR NUMBERS) are the contents of the Control Register 8175 data field (bits 1-16). Seven possible ctassifica-tions of operational error codes exist and they are:

ERROR

NUMBER TYPE OF ERROR 30000-32700 CPU/LI ERROR 29000-29999 MISCELLANEOUS ERROR 20000-28192 SLOT REGISTER ERROR 19000-19016 SLOT ERROR 10000-18192 READ AFTER WRITE ERROR 01000-09999 PROCESSOR COMMUNICATION

PORT ERROR

00001-00999 GENERAL ERROR

Page 23 30598-247-01

The same operational errors are used by the Local/Remote Interface systems to indicate errors in devices under its control. In this case, Register 8175 or the ERROR NUMBER in the CRT Status display will indicate the slot of the Local Interface having the problem. Once located, inspection of the error control register inside the Local Interface will reveal which of the remote devices contains the error. Refer to or greater detai] on using the error codes to Isolate System faults.

CPU/LI Error (30000-32700)

This error indicates a problem with either the processor (CPU) or Local Interface Module.

L3|t}tie]o} 4 4 b ..- Drop Number Drop #0 indicates CPU or LI! error. Drop # > 0 indicates Remote interface Error

Channel Number

Channel 0 indicates CPU or LI error. : Channel # > 0 indicates Remote Interface Error

Type Error: 00, 27

TT ERROR DESCRIPTION

00 | Status Register Read/Write Parity Error Ol | Image RAM Read/Write-Parity Error 02 | Internal Register Data Error

03 | Nilegal PROM Format

04 | Illegal Opcode Encountered in RUN

0S | Bus Error Signal Error

06 | Software Watchdog Error

07 | Not Used

08 | Not Used

09 | User Memory Read/Write-Parity Error 10 | Iltegal Data in User Memory

11 | PROM Memory Corrupted

12 | Illegal Addressing Map Code

13 | Transmission Error Exceeds Tolerance 14 | Loss of Transmission

15 | More External I/O Registers Assigned Than Module Can Handle

16 | Too Many Registers Assigned to the Drop 17 |.Addressing More than 8 Drops per Channei 18 | Addressing Number of Channels Exceeded Module Capabilities

19 | Addressing Map Checksum Enror

20 | Bus Error, Watchdog Time Out

21 | BPU Diagnostic Error

22 | Parity Circuit non-functional

23 =| Clear Line Error

24 | Executive Scratch RAM Error

25 | Watchdog Tolerance Error

26 | Hardware Diagnostic Error

27 | Module Inactive

When an error condition occurs, the appropriate error code is loaded into Control Register 8175 only if the register contains zero of ir it presently contains an error code of lower priority (a smaller number). The previous error code is then lost (if a Model 300) or moved to Register 8183 (if a Model 500 or 700).

Page 24 read from a scan by OCR; it may hold reading errors

Page 24 30598-247-01

L2]s]ejele |

FY t t Error Code

EEE Error Description

000 Subroutine Nesting Error.®

100 Time to Process the Timed Interrupt Subroutine has Exceeded the Time Base.¢

101 Timed [nterrupt Routine Missing.

192 Time to Solve a Rung has Exceeded the Tolerance Set Within a Timed Interrupt.®

201 MCU Software Mismatch with LCU.

202 LCU Software Mismatch with MCU.

300 Mixed Primary. Backup LTIs in CPU Rack.*

301 LT! Timeout on EOS Transfer. @

302 1.71 Timeout on Start-Up Transfer.@

50 Number of Assigned Loca! Transfer Interface Registers must he at least 8 for 1 defined channel, 12 for 2 defined channels.

S01 Insufficient Local Transfer Interface Control.

510 RTI Wired Improperly - Channels A and B are mixed.

Si LTlIs in CPU racks A and B have equal states of operation and no primary determination can be made in HALT.

$i2 Backup Transfer System cannot be in RUN when Primary Transfer System is in DISABLE OUTPUTS.

313 Rack Addressing between LTIs in racks A and B (Primary and Backup) are not the same.

514 Backup cannot be in run with Test bit set when Primary goes to HALT. Backup must also go to

HALT. 515 Backup cannot become Primary until synchronization has occurred and Primary goes to HALT. $16 Backup unable to become Primary because remote bus error exists. Also error generated by Primary to allow transfer to Backup when Primary keyswitched to HALT.

51? Backup has lost synchronization and does not have RTC FAILURE OVERRIDE bit set.

518 Two Primary processars were found in RUN; this processor was halted with a bus error.

* Control Register 8184 will contain the rung number where the error took place. It 8184 equals zero, check Kack Addressing.

* The data field of Controt Register 8184 contains the bit table of primary or back-up status (bit set indicates primary} while the status field of Control Register 8175 identifies the slots which contain LTJs (bit sct mdicates LT] present).

® The data field of Contro) Register 8184 identifies the first register assigned to the LTI that caused the error while the status field of Control Register 8175 contains the elapsed time (in msec.) that the scan was held.

Slot Register Error (20000-28192)

In the event of a Slot Register Error, the ERROR NUM- BER (last four digits} will point out the first register number assigned to the slot containing a faulty register module. Further inspection of that register’s status field will provide additional diagnostics.

[2]r}rin[R]

Starting Register Number Slot Error (19000-19016)

In the event of a Slot Error, the ERROR NUMBER will point out the slot number experiencing the error.

Lijelojsi{s| & 6&4

Slot Number containing the Error

NOTE: ERROR [9000 same as ERROR 32000.

Register Read After Write Error (16000-16192)

A read after write error indicates a particular bit in a register has not maintained the condition written to it by the processor. The error number (last four digits) will point out which register encountered the problem.

Litriraltayr

Register Number

By displaying the status field (bits 17-32) of the control register containing the error code, the bit or bits causing the malfunction will be indicated (by a 1}. Since each register contains both a status field and a data field, control register 8184 is used to indicate which set of bits contains the problem.

Register 8184

Seham

Q, Data Field 1, Status Field

If the faulty register is used to control outputs and control register 8184 indicates the bad bits are contained in the data field, most likely, an output module has caused the problem. Foliowing is a diagram which can be used to isolate the output module having the problem.

In addition, note that a parity error can also be detected in a register and is indicated by a zero in all bil positions.

Status Field ot Control Register 8175 or of Local Interface Error Code Control Register

32 31 30 29 28 27 2 25 24 29 22 21 20 19 18 17

EB ES EXEREO ES AES ES EAEREDEAEA EES ry 4 4 4 i 4} 4 4,

Org. “ Func. Dig. ‘4 Fure. Dig. 4 "Func. Dig. 4 Func. Module #4 Module #3 Module #2 Module #1 Dw. 8 Function Dig. 8 Function Module #2 Module #+

Checks: a. If X=0, Bit was read correctly. b. lf X=1, Bit was read incorrectly. c. If all X°s - O, Parity crror was detected.

Page 25 read from a scan by OCR; it may hold reading errors

Processor Communication Port Error (01000-09999)

To clear a communication port error. toggle the processor keyswitch from HALT to RUN, or Clear $8175. If this does not clear the error, cycle power 10 the processor. These errors can be seen in the STATUS Mode Display by the ERROR NUMBER. Also check remote device and cable connections.

ERROR NUMBER | 0 | P| T | T | O |

4 4 i Type of error

Port Number

TT ERROR DESCRIPTION

11 Communications overflow.

12 | Buffer overflow.

13 [legal data.

14 Wrong reply (odd/even).

15 Checksum error.

16 Framing error.

17 Parity error.

18 Inability to communicate thru Port #P.

19 Reiry timeout.

General Errors (00001-00999)

The ERROR NUMBER in the Status Display indicates the problem.

ERROR NUMBER | 0 [o| 747 { T | t + +

Error Code

TTT

Error Error Description

900 Control registers corrupted.”

901 Data registers corrupted.*

902 Undervoltage lockout is engaged.

960 | HALT or HALT/RUN bit set.

92 | Tolerance equal to or greater than the rate.

963 | Timed Interrupt time base is less than 3.

964 | GOTO and GOSUB to same MARK. ***

965 IMegal Internal Error Code.

966 | User Subroutine Stack Error.***

967 | A MARK rung with the same reference number is required.***

968 {| GOTO to MARK with RTN (return).***

969 GOSUB to MARK with no RTN (return).*** 970 | Scan Time of processor is greater than 1 second or scan limit in $8167 has been exceeded.**

971 | Scan Time limit of processor has been exceeded due to long LTI start-up transfer. (Check register 8184 for clapsed time in msec.)

979 | Rack Addressing missing.

980 | Keyswitch in RUN and no program in memory. 981 | PROM inhibit coil not in memory (PROM processor).

983 Safeguarding rung not in memory or programmed incorrectly.

984 | Undefined register programmed in user memory.**

* Cantrol registers are normalized and data registers are cleared. Toggling keyswitch will allow CPU to run.

** $8184 will contain the rung number being executed when the error occurs.

*** $8184 will contain the MARK number.

Page 25 30598-247-01

B.2 Using Error Codes To isolate P.C. System Faults

8.2.1 GENERAL CONCEPT

When a P.C. system. which was once operating correctly malfunctions, one of three situations can arise: either the whole P.C. system shuts down, one or more drops shut down, or arun time communication port error is detected. Once the malfunction is identified as existing in ane of these three categories, the PC. SYSTEM OPERATIONAL ERROR CODES can be used to isolate the fault. Recognition of the first culegory ts obvious however, the second calegory can exist only when the P.C. system incorporates remote I/O and the override bit is set in the Local Interface Module.

The third category of malfunction deals with communica-lions to external devices and requires that control register 8175 be monitored by the program for errors in the range 01000 to 09999, These types of errors are different from those described in the “Processor Errors” section in that they are generated by the processor itself and not by the external device.

8.2.2 WHEN THE SYSTEM SHUTS DOWN

When the processor halts, register 8175 should be the first point of interrogation. The error code indicated will be one in the following number ranges:

ERROR

CODE DESCRIPTION 30000-32700 CPU/LI Error 29000-29999 Miscetlanevus Error 20000-28 1 92 Slot Register Error 10000-18192 Read After Write Error 00001-00999 General Errors

In the case of the 20000-28192 Slot Register Errors two courses of action may be taken depending on the register number indicated by the last four digils. If the register is the first assigned to a register module, interrogating the slatus field of that register will indicate the error. (Refer to appropriate register module Instruction Bulletin.) If the register number is the first assigned to a Local Interface Module (when using remote I/O). then further interrogation of the LI error code register is required. (Refer to} determine the address of the LI error code register/s.) When the L] error code register is interrogated, the number will be in the following ranges:

Lt ERROR DESCRIPTION CODE 30000-32728 CPU/LI Error 20000-28192 Slot Register Error 10000-18192 Read Afier Write Enor

In the case of the 10000-18192 Read After Write Errors, the affected bit or bits are indicated in the status field of the LI error cade register.

Page 26 read from a scan by OCR; it may hold reading errors

Page 26 30598-247-01

Following is a flow chart which illustrates the previously described procedure.

P.C. SYSTEM SHUTS DOWN

STEP 1: INTERROGATE $6175 IF 30000-32700, Refer toe“CPU/LI Error” IF 29000-29999; Refer el p - - - I F 20000-28192; Refer to STEP 2, following IF 19000-19016; Ensure module{s) are seated properly in rack.

IF 10000-18192; Look at sta eld of S8175 for an indication of the affected bits and refer to “Read

1F 0001-9999, Refer tof “General Error” and interrogate control register $8184 when indicated ¥

STEP 2: USING THE REGISTER NUMBER INDICATED BY THE LAST FOUR DIGITS DETERMINE THE SLOT TO WHICH THE REGISTER IS ASSIGNED

IF assigned to a register module; Look at status field of the register number indicated by the error code then refer to appropriate register module [nstruction Builetin for the meaning of the error number

IF assigned to a local interface; Interrogate the LI error code register then refer to STEP 3

STEP 3: INTERROGATE THE LI ERROR CODE REGISTER

IF 30000-32728; Refer to]“CPU/LI Error”

IF 20000-28192; Using the register number from error code (last four digits), determine slot to which register is assigned. The register module in that slot, generated the error. Look at status field of that register then refer to appropriate register module Instruction Bulletin for the meaning of the error number.

IF 10000-18192; Look a le register for an indication of the affected bits and refer toe]*Read After Write Error”

Page 27 read from a scan by OCR; it may hold reading errors

EXAMPLES:

Shown is an arbitrary P.C. system configuration with four different fictitious malfunctions (which are not the only ones possible) marked by numbers. Following are the steps one would go through to isolate each type of problem (based on the previous flow chart). The four problem areas are the:, CPU, Local Register Module, Remote Register Module, Remote I/O Module

FOUR P.C. SYSTEM MALFUNCTIONS

0) ® CPU REG|REG RACK cpu , MoD | MOD

1 2 3 #4 =°5 ! 461] 473} 477

Y 460 4472 | 476 | 480

4 POINT DIGITAL 1/0 1 MODULES ££ | JN wil’)? 1? 1 ~ NOT| p © DROP 1 WISED nd J tt 462 ] 2 3 4 5 463 | 467 ® p} [REG|REGINOT [NOT DROP 2 MOD |MOD|USEDUSED} ~ P| 466 | 472

Figure B.1, A Typical P.C. System

“NOTE: Arbitrary register assignments have been added to this diagram to aid in the following explanation. Malfunction in CPU

A malfunction in the CP shut down therefore the]“P.C. System Shuts Down” flow chart should be used.

Page 27 30598-247-01

Result of STEP 1: Since a malfunction in the CPU itself, caused the system to shut, interrogating control register 8175 would result in an error code in the range of 30000 By referring to the|“CPU/LI Error” sec- tion the specific error can b mined.

2. Malfunction in a Local Register Module (Located in

CPU Rack)

A major malfunction in a register module located in the CPU rack would cause the sysiem to shut down, therefore the “P.C, System Shuts Down” flow chart should be used.

Result of STEP I: Interrogating control register 8175 would result in a 20473 error code.

Result of STEP 2: The error code indicates the register module in slot four of the CPU rack has malfunctioned since it is the module containing register 473 as the first regis- ter address. By looking at the status field of register 473 and then referring to the appropriate register module Instruc- tion Bulletin, the specific error can be determined.

3. Malfunction in a Remote Register Module

A malfunction in a register module located in a remote rack will cause the total system to shut down if the override bit in the fe eRe ae If this is the case, the]/*P.C, System Shuts Down” flow chart should be used.

Result of STEP |: Interrogating control register 8175 would result in a 20461 error code.

Result of STEP 2: The register number indicated in the error code is 461, which is the first register in the LI. Interrogating the LI error code register (in this case 8163) will pro- vide additional information as to which module in the remote 1/0 system caused the shut down.

Result of STEP 3: Interrogating the LI error code register

(8163 in this case) would result in a 20467. Since the register module in DROP two SLOT three contains regis- ter 467, that module is responsible for the system shut down. By looking at the status field of register 467 and then re- ferring to the appropriate register mod- ule [Instruction Bulletin, the specific er- ror can be determined.

4. Malfunction in a Remote 1/O Module

A malfunction in an output module located in a remote rack will cause the total system to shut down if the override bit in the | set. If this is the case, tha “P.C. System Shuts Down” flow chart should be used.

Result of STEP 1: [nterrogating control register 8175 would result in a 20461 error code.

Page 28 read from a scan by OCR; it may hold reading errors

Page 28 30598-247-01

Result of STEP 2: The register number indicated in the error code is 461, which is the first register in the LI. Interrogating the LI error code register (in this case 8163) will pro- vide additional information as to which module in the remote I/O system caused the shut down.

Result of STEP 3: Interrogating the LI error code register (8163 in this case} would result in a 10461. Looking at the status field of 8163 will provide the bit mask, indicat- ing which output module associated with register 461 caused the failure.

5.2.32 WHEN A REMOTE RACK SHUTS DOWN

When the P.C. system incorporates remote I/O and a remote rack or racks halts without causing the rest of the system to halt, the error code register of the Local Interface module controlling that drop will contain the error number of the fault. When the LI error code register is interrogated, the number will be in the following ranges:

Li ERROR DESCRIPTION CODE 3001 §-32728 CPU/LI Error 20000-28192 Slot Register Error 10000-18192 Read After Write Error

In the case of the 10000-18192 Read After Write Errors, the affected bits are indicated in the LI error code register.

Following is a flow chart which illustrates the previously described procedure.

EXAMPLES:

Using the malfunctions three and four y Figure B I Jas examples, following are the steps one would’Z0 Through to isolate each type of problem (based on the previous flow chart). The two problem areas are the:, Remote Register Module, Remote [/O Module

1. Malfunction in a Remote Register Module

A malfunction in a register module located in a remote rack will cause just that rack (drop) to shut down only if the override bit in the | If this is the case, the]“Remote Rack/s Shuts Down” flow chart should be used:

Result of STEP I: Interrogating the LI error code register (8163 in this case) would result in a 20467. Since the register module in DROP two slot three contains register 467, that module is responsible for the system shut down. By looking at the sta- tus field of register 467 and then referr- ring to the appropriate register module Instruction Bulletin, the specific error can be determined.

2. Malfunction in a Remote 1/0 Module

A malfunction in an output module located in a remote rack will cause just the rack (drop) to shut down only if the faiiure override biti j If this is the case, the [*Remote Rack/s Shuts Down** flow chart should be used.

Result of STEP |: Interrogating the LI error code register (8163 in this case) would result in a 10461. Looking at the status field of 8163 will provide the bit mask indicat- ing which output module associated with register 46] caused the fatlure.

6.2.4 PROCESSOR COMMUNICATION PORT ERROR DETECTED

These errors are different from those Processor Errors associated with communications listed earlier in this appendix. The difference is that Processor Communication Porn Errors are detected by the processor rather than the external communicating device. The only Processor Error that has any relationship to Processor Communication Port Errors (01000-09999) is Processor Error code 13. When error 13 is indicated in a status register of a communication rung, interrogation of control register 8175 will result in the display of one of the Processor Communication Port Errors (01 000- 09999).

These errors can also be detected when an external device is asking for information from the local processor. In this case. there is no communication rung status register to indicate the fault. Therefore, it is up to the user to implement the means to annunctate these types of errors.

REMOTE RACK(S) SHUTS DOWN

IF 30000-32728: Refer iq “CPU/LI Error” |

STEP 1: INTERROGATE APPROPRIATE LOCAL INTERFACE ERROR CODE REGISTER

IF 20000-28192, Using the register number from error code (last four digits), determine slot to which register is assigned. The register module in that slot. generated the error. Look at status field of that register then refer to appropriate register module Instruction Bultetin for the meaning of the error number.

{IF 10000-18192; Look OP Read Aner Waite Eror] register for an indication of the affected bits and refer tof*Read After Write Error”