Local/Remote Interface, Class 8030 Types CRM-210, 211, 220, 222: 5: Troubleshooting

Pages 14 to 18 of 38, from Local/Remote Interface, Class 8030 Types CRM-210, 211, 220, 222

The original document is the PDF (1.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Square D 8030-CRM-210, Square D 8030-CRM-220, Square D 8030-CRM-222, Schneider 8030-CRM-210, Square D 8030-CRM-211, Schneider 8030-CRM-220 and Schneider 8030-CRM-222

Page 14 read from a scan by OCR; it may hold reading errors

Page 14 30598-247-01

5.0 TROUBLESHOOTING

5.1 General Information

This section explains the procedures for troubleshooting the local and remote interface (LI/RE} system. Fullowing the outlined procedures will aid in evaluating a malfunctioning system.

5.2 General Procedures

Always do the following:

. Examine and note what the system is doing and has failed to do,

2. Examine the LED y LIAR] interfaces. (Refer ic eigu 5.1 fand] Figure 5.2] LF and RI LED Explanation.

3. Using a Programmer, examine and note the control register information. (Refer to LI Control/Status Registers.)

There are three primary types of malfunctions which can occur within the S¥Y/MAX Family LVRI systems.

L. A CPU processor malfunction. 2. Component faiture. 3. User software program error.

5.2.1 CPU PROCESSOR MALFUNCTION

If a CPU processor malfunction is suspected, refer to the appropriate processor and CRT programmer instruction bul- Jetins for further troubleshooting procedures.

If, however, it appears the problem may be related to the LI/RI system or user control program software, continue in this section.

5.2.2 COMPONENT FAILURE

Besides the CPU, the malfunctioning of the following hardware components may cause the PC system to halt or continue to run in a partial mode.

LI MODULES

RI MODULES REGISTER MODULES VO MODULES

RACK ASSEMBLY POWER SUPPLY

Also, the system may halt if there is a Jack of. or insufficient power at any location or a communication error.

Before replacing any hardwure items, verify the problem by interpreting the LEDs and contol register information.

5.2.3 USER SOFTWARE PROGRAM ERROR

A CRT programmer is helpful in analyzing LI/RI problems whether they are user created or system malfunctions. Use the monitor mode to display the following registers:

81745 - processor error code register. (data & status field)

8176 - processor control register. (data field)

8186 - processor read only status control register. (data field)

8163 - first Lf Error Code Register. (data & status field)

8162 - first LI channel 1 Control/Status Register. (data & status field}

RIGL - first LI channel 2 Contral/Status Register, (data & status field}*

Note: The error cude iegisters vnly display the most critical error detected prior to 4 total system shuidown. An error code may indicate either a specific register problem or it may be indicating the first register address of a block of registers where a problem has been detected.

Progressively inspecting all of the available CPU and LI control registers will aid in pinpointing the trouble area. Inspection of the channel control register data field (bits 1-8) will indicate what racks are halted due to the user program initiated control action while the status field will display the errored drops (bits 21-28).

*For more information, refer to Section 4.3.3 LI Control Register Allocation.

5.3 LI/RI LED Explanation

For a normally operating system. al] of the associated CPU, LI and RI modules should have their RUN LED’s itlumina-ied.When a detected system change occurs, the LED's indicate the status of the system. If an crror has occured, it will also indicate where the error most likely originaled.

However, if any of the RUN LEDs are off, it does not neces-sarily indicate that a system malfunction has occurred. The system could be in some mode of operation other than RUN such as DISABLE OUTPUTS, or even a HALT candition by virtue of the user program.

In most cases, inspection of the LEDs will directly indicate the status of each communications link and ‘‘point’” to the error source.

The meaning.ot t and RI modules LED states is depicted in figureq 5. ] fand 5.2

If it is impractical to view all the diagnostic LEDs or if they do not readily indicate where the faiture has originated, inspection of the error code registers of the CPU and LI will aid in finding a fault.

or code register information ts described in Appendix BJ Errar Codes.

5.4 Fauk Isolation Procedures

Note what the system is doing by examining the following: 1. LEDs

Determine which of the following LEDs are ON, FLASH- ING, or OFF.

A. CPU (system processor) B. LI Cc. RI

2. Frror Registers Determine the contents of the Error Code and Control Registers.

A. CPU (system processor register $8175)

B. LI register (Le S863 for the first LI in a system) refer toy Appendix BJ Error Codes for further information.

Page 15 read from a scan by OCR; it may hold reading errors

Page 15 30598-247-01

LOCAL INTERFACE

REMOTE INTERFACE

All lights OFF indicates loss of SVDC power.

RUN (green)

ON - indicates LI is operational and CPU is accessing image table information. OFF - Indicates LI is in self-diagnostics or has failed.

FLASHING - Indicates LI is running but one or more drops on its channels have been pro- grammed to halt. iBits 1-8 of the LI chan- nel control register.)

HALT (red)

ON - Indicates LI] is in self-diagnostics and/or has halted operation.

OFF - Indicates LI is fully operational and CPU is accessing image table information.

FLASHING - Indicates L] ts running but one or more drops on its channels have been pro- grammed to hall. (Bits |-8 of the L] chan- ne! control register.)

CHANNEL. ERROR (red)

ON - Indicates Li cannot communicate with one or more of its drops which are shutdown. OFF - Indicates all drops operational,

FLASHING - Indicates a module failure on a drop has caused a drop to shutdown on this channel.

MODULE ERROR (red)

ON - Indicates a self diagnostic error or internal tmcout crror has been recognized and halt- ed the CPU.

OFF - Indicates LI] is operational even though a channel HALT or CHANNEL ERROR LED may be ON.

FLASHING - Not valid

Figure 5.1 - LI LED Explanation

All lights OFF indicates loss of SVDC power. RUN (green) ON - Indicates remote drop is operational.

OFF - Indicates RI is shutdown or has not been initialized. Outputs will de-energize pro- vided the shutdown is not a direct resull of a communication error, and the Freeze function is also selected. (Some register modules are capable of maintaining regis- ter information. )

FLASISING - Indicates CPU is in Disable Outputs mode. (50% ON, 50% OFF alternately with HALT LED.)

BLINKING - Indicates LI HAET bit for the drop is set. ; (5% ON, 95% OFF, alternately with HALT LED.} | HALT (red) | ON - Indicates RI is shutdown. If the only LED ON, il indicates rack was shutdown due to program control or has not been initia- lized. OFF - Indicates remote drop is operational.

FLASHING - Indicates CPU is in Disable Outputs mode. {50% ON, 50% OFF alternately with RUN LED.)

Indicates I.E HALT bit for the drop is set. (95% ON, 5% OFF, alternately with RUN LED.)

BLINKING -

CHANNEL. ERROR (red)

ON - Indicates invalid or loss of communica- tions between RI and L!. HALT LED will also be ON.

OFF - Indicates valid communication between RI and LI.

LO ERROR (red)

ON - Indicates: (HALT LED should also be ON.) t. Aread after write error to an output. 2. Enror caused by a malfunctioning regis- ter module. 3. RI malfunction.

OFF - Indicates RI is properly cammunicating with modules in same rack.

FLASHING - Indicates outputs and inputs are frozen

(ON or OFF).

MODULE ERROR (red)

ON - indicates self diagnostic error or internal timeout error has occurred.

OFF - Indicates RI is operational although drop may be shutdown due to system shutdown or program contro}.

FLASHING - Not valid

Figure 5.2 - Rl LEO Explanation

Page 16 read from a scan by OCR; it may hold reading errors

Page 16 30598-247-01

3. Control Registers

Determine the contents of the respective Channel Contro) Registers

A. Channel L, LI register (S8162 for the first LI in the system)

Channel 2, LI regis 61 for the first L] in the system) refer tojAppendix D j LI Control/Status Registers for further information.

Progressive evitluation and interpretation of these bits indicate how to resolve, eliminate or compensate for the system malfunction.

B.

5.5 Undervoltage Lockout Circult (ULC} Operation

Series O and later Local Interface devices are designed with an on-board DC Undervoltage Lockout Circuit that monitors the incoming DC voltage level at the edge connector of the slot in which the LI Module resides. If the incoming DC voltage falls below 4.6 volts, the CRM-210, 211 enters a HALT state and no longer communicates with the processor on the rack, or its associated LO. All LEDs on the front of the module are turned off and the processors in the CPU rack are halted.

When incoming DC voltage rises above 4.6V, the CRM-210/ 211 executes a standard power-up initialization sequence. When recovering from a ULC error, a 902 error code is posted in the LI error register (e.g. 8163).

Even though Series © and later Local Interface devices enter a HALT state when the incoming DC voltage falls below 4.6VDC, other devices in the same rack may remain powered-up, since the ULC resides in only selected SY/MAX Modules.

Some possible causes for the ULC being engaged are, an overloaded power supply or a poor cable connection between the power supply and the rack. If these or other problems arise, correct the respective problem first, then normal operation can be resumed.

5.6 Module Replacement Procedure

If it is necessary to replace components. use the following procedure:

Keyswitch the CPU to HALT prior to removing power. Remove power from all rack assemblies in a system. Disconnect communication cabling and remove module. Set switches on replacement modulc.

Install module and attach communication cabling. Reapply power to system.

Restart the system and verify operation.

WA tr me teh

NOTE: ERROR 901 identifying register corruption may require toggling processor keyswitch several times to clear the error.

5.7 LI/Ri Communication Restart (Push Button)

Whenever communication is lost between the LI and an RI, an error code is generated and the Channel Error LED will be ON. Communication may be lost because of the following:

|. Loss of power at the Local CPU Rack.

2. A broken cable between the LI and RI.

3. Loss of power at a Remote Rack (DROP).

4. Hardware malfunction.

Reestablishment of LTR] communications will always be attempted each time any of the following occurs:

LUR?t LED RESPONSES TO ERRORS

LI LIGHTS AE LIGHTS cw u OPERATING STATUS WITH A DAOF FAILED WITH ALL OROPS OPERATIONAL FAILED DROP OPERATION DROP CHAMMNEL BITS COMDITION CHANNEL CHANHEL FAILUAE RUN |CHANWEL MODULE RUN CHANNEL |MODULE| AUN [CHANNEL| UO | MODULE [AUN |CKANNEL| 10 |MODULE OVERRIDE |FREEZE AUNWALT | HALT | ERROR / ERROR| MALT ERROR | ERROR HALT| ERROR (ERROR) ERROR [HALT| ERROA |EAROR| EARON | BIT19 | BITS | k C - - . kK Q Q k ) u oO R tJ QO ib Serr CAL Kent r C - - e A a a F a tl 0 f 0) 0 't Drabble, Onepuls TL R if - - Co. I 0 tf] 8 i] t 0 8 i] iF] i} _ Conrul Register Hatt Ba: Set io} t kK 1 1 K u uy H u iW AY H ) ul el Iraasossi blr J F R F I kK i 0 Q H 0 | \} H 0 lh 0 uv tl Bus ut Real Aler | Wry tow QO fF k i] I R | 0 0 H 0 f x H Q 7 QO ib | Ties pissin knot QO F k F I R | 0 0 H 0 I ot) x n t 0 ib i} Bust Real Alkt A Write Live R ( R I if k ' 0 0 H 0 ti x R 0 Ib 0 | 3 Transission [nor ] | R f R F t k : oO 0 HM 0 | Q Kk 0 '} QO | 0 ! Bus or Read Wer ' . Write Eetot K t R 1 ¢. a 0 g ul a F % K a u q t 1 Trans niestien | mor a t R t ( k O 0 it 0 4 0 R Q u ‘I 1 | Rus se Real 4ther Wore Lan 0 = OFF NOTES: |. Run light on LI signifies that LI is operational no inutler | = ON what error condibons{s) exist wilbin the RI or CPU. - = NOT APPLICABLE R = RUN 2. The state of the remote channel error light is dependent H = HALT on which device detected communication error first: F = FLASHING (50% Duty Cycle) On-remote and OFF-local. B = BLINKING (Halt 95% ON, Run 5% ON) X = EITHER ON or OFF (2)

Figure 5.3 - LV RIL ED Response to Errors

Page 17 read from a scan by OCR; it may hold reading errors

Page 17 30598-247-01

LURI FAULT STATUS

CHANNEL FAULT PROGRAM HALTED OROP DROP FAULT (Transmission Loss) See Notes FAILED DROP OPERATIONAL DROP FAILED DROP OPERATIONAL DROP HALTED OPERATION DROP FAILURE stars LOCAL REMOTE LOCAL REMOTE LOCAL REMOTE LOCAL REMOTE LOCAL REMOTE E OVEAWE | FREEZE | AFTER WAGE DROP MAGE OROP IMAGE OROP mag ORoP MAGE paar BT 1S | BITS | FAURT INPUTS OUTPUTS [INPUTS OUTPUTS] INPUTS JOLTPUTS JONPUTS [OUTPUTS [INPUTS [OUTPUTS INPUTS KX TPUTS] SNPLTS FOUTPUTS| INPUTS KATPUTS| INPUTS RXCTPUTS INPUTS [OUTPUTS TURN TURS TURN TURN TLR® 6 0 HALT [CLEAR] CLEAR |, OFF | CLEAR | CLEAR] - OFF [CLEAR] GEAR | CFF LbaR PcubaR |, OFF UPDATE] CLEAR OFF TURN | LAST | LAST Last | vast { Last LAST | LAST | LAST LAST nS 0 I HALT jCLEAR] CLEAR OFF | STATE f STATE STATE | STATE | state | - | stare | state | state {| - | Seale [tpoame| ear | - dh TURN | LPDATE | LPDATE UPOATE TURN 1 PDATE. LPbale TRS f a RUN [CLEAR] CLEAR “ OFF TLADOER [LADDER] = - | LADDER [CLEAR] CLEAR |, OFF | LPDATE | ADDER LADOER JL PUATEY CLEAR |, OFF TURN | UPDATE | LPDATE UPOATE | LAST | LAST LAST LPDATE UPDATE WRN | | RUN CLEAR] CLEAR F, OFF |LADOER |LADDER| - [| LADDER | STATE | Stark |, | STATE | UPDATE [LADDER LADDER JUPDATE| CLEAR |, OFF

NOTES:

|. LI HALT Bit refers to bits | to 8 of the LI channel control data register.

2. Regardless of how outputs on a drop get frozen, if communication is re-established. che drop will reset, clear all outputs and local image table information for that drop. and stay in the halted mode until restarted.

3. Restarting the system may be done in any of the following ways.

A. Toggling the CPU keyswitch.

B. Power cycling the local (CPU) rack.

C. Auto Restart function of the LI/RI system. D. Pushing the LI Restart button.

For more detailed information, refer tof Section 5.6. LI/RI Communications Restart (Push Button). |

4. If the CPU halts its execution due to an error, turning the keyswitch to HALT will not reset frozen outputs on any of the remote drops even if valid LV/RI communication is present.

Figure 5.4 - CPU and LI/RI Response to I/O Faults

Toggling the CPU keyswitch out of HALT.

Power cycling the power to the local CPU racks while the

CPU is in RUN of DISABLE OUTPUTS.

3. Power cycling the remote drops while the Failure Override Bit is ON.

4. Pushing the LI restart push button while the Failure Override Bit is ON and the CPU ts in RUN or DISABLE

OUTPUTS.

Le ed

The RESTART button is operational when all the following exists:

i. CPU must be cunning.

Communications error must have originated on one of the

LI channets.

3. Failure Override Bit must be ON.

4. Valid communications must be able to be established to the affected racks. or else no change of state veill vccur.

na

NOTE: The RESTART button wall only restart drops which are shutdown due to communications errors. It will have no effect if a local (CPU) rack error exists.

WARNING: Pressing the RESTART (RESET) button on the front of the LI module may cause outputs to turn ON or OFF.

5.7.1. FROZEN DROP RESET

An operational drop with frozen outputs may be reset by:

I. 2.

Power cycling the remote drop.

Setting the drop HALT bit ON while the Failure Override Bit is ON and CPU are operational. For more intocmution on how to apply these bits, refer tof appendix D| LI Control/Status Registers.

Turning keyswitch to HALT providing the CPU rack is operational, no errors exist.

.8 CPU and LI/RI Response to Faults

Figure 5.4epicts how 4 system will respond to a detected ult condition within the LI/RI portion of the system.

Page 18 read from a scan by OCR; it may hold reading errors

Page 18 30598-247-01

5.9 Obtaining Additional Assistance

If additional assistance is needed, the following must be available.

I. Aconcise statement of the problem. Also, determine what the system is actually doing. 2. A physical description of the system indicating the quanti-ties and types of the following: A. [nputs and outputs. B. Channels. C. Drops. D. Registers per drop. E. W/O per drop.

Qty. Serial Number w

Is this a start-up of a new system or an addition or repair to a previously operable system? How long has the system been operational? Have any overriding control register bits been set? What is the rack addressing as seen on the CRT screen? Check contents of the following registers:

A. CPU ERROR CODE

B. LI ERROR CODE

C. LI CHANNEL CONTROL/STATUS 8. Describe the equipment involved:

NOAS

Class Type Series Revision

Processor

Local Interface(s)

Remote Interface(s)

Bus Expander(s)

Rack Assembly(s) Register Module(s) Communication Module(s) CRT Programmer Loader/Recorder

Other Equipment

Figure 5.5 - Equipment List