The text of a manual · part 3 of 6

Local/Remote Interface, Class 8030 Types CRM-210, 211, 220, 222, pages 7 to 13

Pages 7 to 13 of 38: 3: Installation; 4: Operation

The original document is the PDF (1.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Square D 8030-CRM-210, Square D 8030-CRM-220, Square D 8030-CRM-222, Schneider 8030-CRM-210, Square D 8030-CRM-211, Schneider 8030-CRM-220 and Schneider 8030-CRM-222

Page 7 read from a scan by OCR; it may hold reading errors

RACK | LOCALINTERFACE | REMOTE INTERFACE TYPES [TYPES CRM-210, 211 [Type CAM-220Type CRM-222 CRK-£00, 210 NO YES YES CRK-210, 300 DRK-210, 300 YES YES YES GRK-110, 210: HRK-100, 150, 200 RRK-100, 200, 300 YES NO YES

Figure 2.4 - Rack Compatibitity 2.2.5 COMPATIBILITY WITH LO The lncal/remote interface system is compatible with:

All register modules.

All 32 point 1/O modules.

All 16 point [/O modules.

All 8 point 1/O modules.

All 4 point input modules.

All 4 point output modules, Series B or later.

Bus Expander, Class 8030 Type CRM-115/116, Series D or later.

Page 7 30598-247-01

2.3 Environmental Ambient Temperature Operating 0°C to 60°C (32° to 140°F) Storage -40°C to 80°C (-40° to 176°F) Humidity 5-95% non-condensing 2.4 Physical

Dimensions (WxHxD)

CRM-210, 211,222 1.5 x 12.8% 6.6 in 3.81 x 32.5 x 16.76 cm CRM-220......... 1.5 x 9.6% 6.61n. 3.8t x 24.4x 16.76 em Weight CRM-210, 211,222 3.0 Ibs. 1.36 ke CKM-220 ........ 1.0 Ib. 0.45 kg Terminal strips CRM-210, 211..... Part Number 25410-02529 CRM-220......... Part Number 30605-255-02 CRM-222......... Part Number 25410-02526

3.0 INSTALLATION

3.1 General Information

CAUTION: To prevent possibie equipment damage, remove power from all local and remote cracks before inserting or removing any component including the interface modules or LI/RI communication cables.

Local Interface Modules identified as Series L or later incor-porate diagnostic enhancements not available in earlier series devices. Expanded error checking of data registers will return a unique error code (901) in the event a data corruption is determined. When initially replacing or installing a new Local Interface (LI), the user should expect the posting of this ertor as a normal “out of the box” condition. After installing the device and powering up the system, upon initially keyswitching the processor to DISABLE OUTPUTS or RUN, the processor will remain in HALT and the LI will indicatea MODULE ERROR. The processor error register (8175) will identify the LI in error while the LI error register will contain the value 901. This is a normal occurrence, reflecting the fact that the LI storage registers are corrupt (contain random data). Key Switching the processor a second (or third) time will result in all LI registers being reset to zero and the error being cleared. Normal operation will then result.

3.2 Inspection

Although each module is subjected to strict quality control procedures, give each module a visual inspection hefore installation. Check for any shipping or handling damage that may have occurred. If damage is found, do not use the madule, replace it.

3.3 Module Keying

Each register or CPU slot on a rack assembly may be keyed. An optional keying pin kit, Class 8030 Type CBP 104, is available for this purpose.

The keying pin may be inserted manually into the slot using the keying pin insertion tool provided with the kit.

The correct positioning of the keying pin for the LI and Ri modules follows:

TYPE DESCRIPTION PIN LOCATION

CRM-210 Local Interface (LI) Module w/512 Registers

CRM-211 Local Interface (LI) Module w/4096 Kegisters

CRM-220 Remote Interface (RI) Module

Between 92 & 94

Between 92 & 94

(for 4 function digital racks) None CRM-222 Remote Interface (RI} Module (for all type rack assemblies) None et KEYING PIN

TI a 84

[|| 86

Ld L150 REGISTER r - “| op KEYING PIN

94 BETWEEN 96 SLOTS a2 AND 94 98

Lith Lith

10a

Keying Pin Location

[Faure 3.4} Module Keying

Keying Pin Insertion

Page 8 read from a scan by OCR; it may hold reading errors

Page 8 30598-247-01

3.4 Module Location 3.4.1 LOCAL INTERFACE

The local interface module (LI) must be placed in the same rack assembly as the CPU. When a register sack is used to house the CPU, the LI module should be placed in the next closest slot. If more than one LI module is required, piace additional modules in adjacent stots. MODEL 500, 700 SLOT 1 2 3 4 5

CPU |LI conven 2 | Lewes 2 LI IN REGIS7ER RACK MODEL 300, 400, 600 SLOT 2 1 SLOT 1 203 ~ 4 5

LI |CPU CPU] LI

L/0

CHANNEL 1 CHANNEL 2

LI INDIGITAL RACK LI IN REGISTER RACK

| Figure 32+ Local Interiace Location

3.4.2 REMOTE INTERFACE

CHANNEL 1 | | CHANNEL 2

The remote interface module (RD) must be placed inte the CPU slot of any rack which is to be a drop.

Only one Ri is required and allowed Tor each drop.

SLOT ce 1 SLOT 1 ec 3 4 &

RI I/0 RI

_|

FROM LOCAL RACK {CHANNEL 1 OR 2) FROM LOCAL RACK (CHANNEL 1 0A 2) RI IN DIGITAL RACK RI IN REGISTER RACK

Figure 3.3} Remote Interface Location 3.5 Field Wiring

3.5.1 POWER CONNECTION

No external power wiring is required. The LI and Rl modules receive their power through the edge connector socket of the rack assembly. Insert the L1 madule in the register slot until firmly seated against the stud ithe middie post above the socket in that slot) and tighten the captive mounting screw al the bottom of the module. These two connections not only provide support for the module but also provide a ground.

3.5.2 COMMUNICATION CABLE

The communication between the LI and RI modules is achieved via a dual shielded twisted pair cable. A hinged plastic flap covers the detachable terminal strip. In order to minimize the potential of electrical interference:

1. Route communication cable in different wire ducts than the power wiring is routed.

2 Connect each end of the communications cable shield to the shield terminal on each module.

Transmission cable should be electrically equivalent to:

Conductor- Maximum Conductor Cable Type Length Capacitance Belden 8723 7,500 feet 35 opffft. Belden 9463* 10,000 feet 19.7 pf/ft.

*Dual cables required.

NOTE: ADDITIONAL DATA LINE PROTECTION In environments where lightning or induced transients over communication lines are likely to cause hardware failures, signal line protection devices are recommended. Even though transient protection is designed imty our SY/MAX communication cir- cuits, additional specialized protection devices are suggested in ureas where there is a high probability of secondary lightning strikes occurring. The specific environments which are of greatest concern are where communication in the out- side environment. Refer iq Appendix G

2.5.3 LOCAL/REMCTE CONNECTIONS

The required method of wiring from one module to the next is daisy chain. Since the LI/RI is designed to operate as a serial link, any configuration other than daisy chain may result in erratic operation. Total allowed cable distance for each channel when using Belden 8723 is 7,500 ft.

LOCAL REMOTE INTERFACE INTERFACES:

{1} 1X1 RED a 2

L2)_Tx2 aL ack (Ax 2 GREEN)

(4) 2 oy WHITE

SHIELD , SHIELD hd

(2) 3), SMZ2F ITO

DAOP #1

{1) 1 2 RED Cd) RP | ia) 1x2, BLACK i AM SBEEN

(4) AX2 Q WHITE

| SHIELD pSHELD in

NAP #2 4 me em Ee ITO

(1) Txt 2 (2) TK2 Q (3) A 2 (4) AX2 2)

SHIELD EoD

DROP #8

LIRI Wirtng Connections

3.6 RI Switch Settings

The RI Moduie has four dip switches on the rear of the module near the edge of the circuit board. A madule must be assigned as one of the eight drops on a specific channel. The switches must be set for the system to operate properly.

Page 9 read from a scan by OCR; it may hold reading errors

etthe switches for the appropriate drop as shown in Figure 3.5 | RI switch settings.

REAR VIEW crop es S838 CRM 220, 222

Page 9 30598-247-01

Label terminology may vary. The following equivalent terms are used:

OPEN OFF CLOSED QN

DOWN

Either one of these labels will be located on the side of the RI module.

i W/ SWITCHES SET a e Ffuiet! FOR DROP #1 CAUTION: $e) SWITCHES a NSERTING Lh 1 MODULE a if BBA ON “a 1 - Fae, stucl s jets) "| [| CAUTION SET SWITCHES BEFDRE INSERTING MODULE r | vr rirserl switch | 234 SWITCH 12.3 4 6 aa t HiTola7 |. #06 ast OROP OROF }# D0,0 DROPS @°U'D'D., alelal 3 QF CHANNEL SET 2.9 D0.u, § 8 UDU | 1 [4 switcH Down (0; 7.4.0.0. 7 #00; «e Pa? BUR | _ OTHERWISE UP (W) «#OuU ae yu | OL A. > a olrfol ¢ ' a fojojxt 7, ‘7 coe 4 ofofo: a 1-On o OrOrF corey SWATCH LAST DROF: SWITCH ON. . ALL OTHERS; *For each channel, the drop (RI module} farthest fram the LI SWITCH OFF. must have switch | set ON, to a (1). Only one drop per channel requires this switch to be set. Failure to do so may result in a noise susceptible communications link. Figure 3.5 - Rl Switch Settings Figure 3.6 RI Module Labels 4.0 OPERATION

4.1 General Description

Local and remote interface modules allow a programmable controller to communicate with remote VO (digital and register input and output type devices).

The LI/RI intertace system consists of:

1. A local interface module {LI} which plugs into a register slot of the rack containing the CPU.

2. Aremote interface module (Ri) placed in the CPU slot of a digital 1/O rack or the first slot of a register rack.

3. An interconnecting cable between the LI and R!¢si con-sisting of dual twisted shielded pair.

Both the LI and RI modules have diagnostic LED’s indicating the status of the communication link, individual drop operation and module operation.

The local/remote I/O interface system is a serial, multi-channel, multi-drop system. The local interface (LI) receives instructions from the CPU. The LI then serializes this information and transmits it to the appropriate remote interface (RI). An LI module does this over either of its two independent communication channels. Each channel operates full duplex at a rate of 31.25K baud.

The RI interprets this data, verifies and acknowledges it and then acts accordingly. The information being exchanged ts stored in an image table located in each L] and RI.

The continuous exchange of information between the LI and RI image tables is independent of the CPU scan. Transmitted information includes ON/OFF commands for I/O as well as storage register information and housekeeping functions (e.g. loss of communications, error control, freeze or reset of I/O).

The LI module stores control register information while the RI maintains its own specific drop information. This information (user programmable bits} defines the action to be taken in the event of 2 fault at any drop. It can allow the operational drops tu keep running or to shutdown. The shutdown state of the outputs will then be either a reset (OFF) or freeze (last state) condition.

Aciual programming steps are described in the programming equipment instruction Los Fur details on user program mable bits, refer tq Appendix D JLI ControlStatus Registers. 4.2 Local Interface Registers

Two versions of the LI module,are available. The first, Class 8030 Type CRM-210, has 51]B4Iregisters; and the second,

Page 10 read from a scan by OCR; it may hold reading errors

Page 10 30598-247-01

Class 8030 Type CRM-211, has 4096* registers. With either version LI, the first 255** registers are available for external addressing of inputs, outputs, register modules, storage registers or as internals. The remaining registers (257 for CRM- 210, or 3841 for CRM-211) are available for use as internal telay equivalents, timers, counters, and data storage in the Model 500 and 700.

“Although the registers exist, the ability to address them is dependent upon the type of CPU used. **Any of the 255 registers not assigned to drops may be used as internals for the Model 500, 700.

4.2.1 EXTERNAL REGISTERS

A maximum of 255 consecutive registers can be assigned between the two independent LI channels. Each LI channel can support up to 8 drops. (A drop is a remotely located rack assembly.} Any drop may have a maximum of 127 registers assigned to it. The first 8 registers assigned to a drop are available for digital or register I/O. (e.g. 8 registers x 16 bits provide for 129 I/O points per drop.) Any registers beyond the first 8 are only for register YO.

The registers assigned to drops will be reset to zero (OFF) upon processor halting or power loss. However, it is possible to freeze (maintain last state) regpiste igned to drops. For more information, refer t LI Control/Status

Appendix D,]] Registers.

4.2.2 INTERNAL REGISTERS Internal registers (those not assigned to drops) retain information when the processor halts or there is a loss of main power, The clearing of these registers is dependent upon processor action,

4.2.3 CONTROL REGISTERS

All LI modules have an error code register and u channel contro] register for each serial channel. These registers moni tor and provide additiggg of the remote I/O, For more uniormation, refer tq Appendix BJ Error Codes and Appendix By LI Control/Seacus Isters.

4.3 Rack Addressing

Rack Addressing (also referred to as System Definition) is 2 user programmable identification scaeme thal enables a SY/MAX Processor to obtain information about a specific

It maps the physical location of where the processor (CPU) will “look” for a specific address and its associated information when required.

Once the register addresses have been assigned. they are fixed. Ifa change in address assignments is required, the user rack addressing sottware must be changed.

4.3.1 PROCESSOR (CPU) CONSIDERATIONS

The CPU determines the maximum system addreggi ¢ SY!'MAX Processor capabilities are as shown iff Figure 4.1.

4.3.2 ADDRESSING ASSIGNMENT AND DISTRIBUTION

All address assignments must be mude in a sequentia: and ascending order. The first 255 LI registers may be ussigned to channel | and then to channel 2. Each of these channels can he further divided into & draps. The register addresses for each drop may he further distributed in ascending order to individual slots uf the remote drops.

Internal addresss begin after external addresses have heen assigned. Internal and external registers cannot be inter-mixed.

4.3.3 LI CONTROL REGISTER ALLOCATION

LI control registers are dynamically essigned on the basis of physical position and rack addressing.

1. LI control registers are assigned in a descending order starting with $8163 for the LI with the lowest numbered CPU rack slot number.

2. LI control registers are further defined by the number of channels used.

For exampe, if only channel | is assigned to the first LI], there will be no control register assigned te channel 2. S8 163 is the error code control register. $8162 is the channel control register for channel |, SSI61 is left unassigned.

[f an additional LI is put in a higher numbered CPU siot, it would be assigned the west available control register. te. S8161 becomes the second LI error code register. $8160 is the control register for channel | of the second LI. S8159 is unassigned and availabie for channel 2 or for a third LU's error code register. If only channel 2 is defined. the system automatically assigns a control register lo channel | whether channel ft is used or not.

For more informal t operation of Upembemcmnins registers, refer ta Appendix BJ Error Codes andj Appendix D

1/O point or register LI ControVStatus Kegisters. Register Maximum CPU Addressing Self Contained Supportable Practical Model Capability CPU Registers Li Modules 1/0 Capability 300 112 (1) 112 1 256 500 2008 (2) 460 (3) 14 2000 700 8000 (2) 0 wu 8000 406 4000 4000 15 4000 600 8000 8000 15 8000

(1) Only the hits of the first 32 registers may be forced ON/OFF.

(2) Only the bits of the first 256 registers in each LE may be forced ON/OFF.

(3) For internal use only as reluys and storage registers.

Figure 4 1 - CPU Address Capabilities

Page 11 read from a scan by OCR; it may hold reading errors

4.3.4 LURI ADDRESSING WITH MODEL 500

The following example is used to illustrate the concept of address assignment.

This example consists uf a Model 500 system with two remote 1’Q channels. The first channel handles 256 digital 1G points and one register module. Two remote drops are used to handle these requirements. The second channel consists of a register rack with 5 register modules.

SLOT 1 2@ 3 4 5

START RODRESS $1 | ~ |ss61 CPU |LI MODEL |CRM LOCAL (CPU) Sea |e1d RACK ENO ADDRESS 5460] - I|sor2

Figure 4.2 - Local (Model 500 CPU) Rack Address Assignments

LOCAL (CPU) RACK

Slot }- = The Made] 500 has been assigned all of its 460 internal registers. (SI thru S460)

Slot 2 - The Model 500 physically takes up two slots therefure, shot 2 has no address assignments required.

Slot 3 - The LI module (CRM-210) has been assigned all of its 512 registers. (S461 thra $972) Slot 4, 5 - No address assignments required.

Assigning all available registers to the CPU and LI dees not affect the CPU scan. Note that the first register of the 11 has a start address of $46], one more than the assigned end address of the processor. The LI end address is $972 which is 512 more than the end address of the processor,

Note that the start and end addresses of the system slots are shown, However, when programming addressing assignments, only ending addresses can be entered, Starting addresses are automatically assigned beginning with the next available register. For a full explanation of the step by step rack addressing programming procedure, refer to the SFW-3XX Programming Instruction Bulletin.

SLOT 1 2 3 4 5

START ADORESS st - |sest cPU |LI LOCAL CCPU)

MODEL |CRM

Sao \212 RACK ENO ADORESS s4sa| - |sa7e

CHANNEL 1 24 DROP #1 = S461

‘RI |12@ oterta. 170 (CRM| @ RECTSTERS

222 |sasi-1 THRU S468-16

- (S468

|

Figure 4.3 - Channel 1, Drop #i Rack Address Assignments

Page 11 30598-247-)

CHANMEL 1, DROP #1 Slot} - To handle 128 digital 1/O points, 8 - 16 bit registers are required. (S461-1 thru S468-16)

Note that the addresses for digital /O are always assigned to stot |.

Slot 2 - No address assignments required.

CHANNEL 1, DROP #2

The next order of business is to add another drop tu an already existing channel. This drop also has 128 digital 1’O points but unlike drop #1. it has a register module. The module is in the register slot, (slot 2) which requires 16 register addresses.

Slot L - ¥ registers are assigned for the [28 digttal [-O. (8469-1 thru S476- 1). Slut 2 - (G6 registers are required for the register module.

(S477 thru $492).

The total requirement for this drop ts 24 registers. Observe that the start address for drop #2 is one more than the end address for drop #1. The first digital address for drop #2 is S$469-1 and the last digital address ts $476-16. Therefore, slot 1 has an ending register address of $476. Slot 2 ends at $492, allowing for the required 16 registers needed by the register module.

This process of adding a drop at a time in a daisy chain fashion could be continued until al) 258 registers were assigned to a channel ot until all 8 drops had been assigned.

SLOT 1 e 35 4 5S

START ADORESS $1 | ~ [$461 cPuU {LI a MODEL ICRM LOCAL (CPU) : SQB le1@ RACK ENO AOORESS |ssca| - |s972

CHANEL 1

DROP #1

RI jies orerta r/o CRM| a recrsters

; 222|s461-1 THRU - §468 $468-16 REMOTE eo DROP #2 $477] $469 BCD) RI jize orextat 1/0 IRIMICRM] 2 RecrsTess L4lie2e|sasa-1 THRU $492 |$476 5476-16

|

Figure 4.4 - Channel 1, Drop #2 Rack Address Assignments

Page 12 read from a scan by OCR; it may hold reading errors

Page 12 30598-247-01

SLOT 1 2 5 Ss START ADORESS si | - 1s CPU |LI 580 |21¢8 RACK END RDORESS s4ce $972 CHANNEL 1 CHANNEL 2 DROP #1 DROP #1 e 1 1 2 3 4 5 6&6 7 8 8 i ~ 1$461 - |8483]$497|S5a1/s517 | sis RI |120 orerra 170 RT |A/OIOZAIBCOl a rm! Rom eee 61-1 222)121)121/141 - |$a¢go $468-16 - $496| 3500 $$16|Ssis | 5s22 Vv FUTURE DROP #2 CUP TO DROP #8)

120 DIGITm r/0 68 RECISTERS 3463-1

THRU $476-16

Figure 4.5 - Channel 2, Drop #1 Hack Address Assignment

CHANNEL 2, DROP #t

In this example. 4 9 slot register ruck is connected to channel 2

Note that the sturting address for channel 2 is one greater than the ending address of channel |. In other words, when channel ! ends, channel 2 begins.

Requirements for register modules vary. As an example, a 4 channel analog module requires 4 regisiers for complete addressing. A BCD 1/0 module requires 16 registers and a 32 point 1/0 module requires 2 registers cach,

Slot 1 - No address registers are required since there is no digital [/O bus in the register rack. (The 32 point ditigal 1/O modules appear as another register modute to the LI.)

Slot 2 - 4 registers are assigned to a4 channel analog input module. (S493 thru $496)

Slot 3 - 4 regisiers are assigned to a 4 channel] analog output module. ($497 thru $500)

Slot 4 - 16 registers are assigned to a 16 (4 digit} BCD input module. (SSO! thru $516)

Slot 5 - 2 registers are assigned to a 32 point digital input module. (5517 and $518)

Slot 6- 2 registers are assigned to a 32 point digital output module. (S519 and $520} Slot 7,8,9 - No address assignments required. The total number of registers required for this drop is 28.

Note the beginning and ending addresses for each slot are sequential] and in ascending order.

LI ADDRESS DISTRIBUTION MAP

Here is 4 map of how the first L] has been user programmed in this example.

Observe that the LI has a fixed number of registers and rack addressing has assigned a unique address to each onc.

Le ASSIGNED REGISTCR AOORCSS

1 $451

2 S452

5 s45

4 s4ge CHANNEL 1. ORCP 8]. SLOT i f é

é 7 r) s1en

$ s4e8

; 3 >) aemee 1. OROF BZ, SLOT L is S475

17 9477

; ‘ porwe: L. DROP ®, MOT 2 32 S42

33 $485 yi ; “) ommees 2 DROF #1, SLOT Z * 4%

7 saa?

4 y “pomwes & uN aL gol 3 “~ an

4 $s y y “pomees © ONOF si SLO 4 56 S535

3? 17

, y Bit DAF We SLOTS 72 sla

3 5513

, . “pores « OROF §L, SLOT & s S20 L23___ 5521 17) UNUSED, AYRILABLE FOR EXTERNAL 1/0 OR ree ae] NTH DTA STORRGE/RELAY EQUIVALENTS | 8 ___ $738 | ONLY AYAILABLE FOR INTERNAL ORTA Pain paoe |S STORRGE/RELAY CQUIVELENTS

- = > CONTROL REGISTERS FOR DATA AND STATUS

Figure 4.6 - LI Register Map

Page 13 read from a scan by OCR; it may hold reading errors

4.3.5 Li ADDRESSING WITH THE MODEL 300, 400 AND 600

As Figure 4.1, CPU Addressing Capabilities shows, the Model 300, 400 and 600 processors differ from the Model 500 and 700 in the arca of self-contained CPU registers. All of the registers available tu the Model 300, 400 and 600 are self-contained. In other words, it is unnecessary to Rack Address storage registers to modules like the LI as in a Model 500 or 700 system. When creating rack addressing for a Modet 300, 400 or 600 system, only assign the mumber of register required for current and future remote drops. While it is valid to assign additional registers 10 the LI, it may reduce overall system throughput.

As an example, the Rack Addressing presented in the previous section for a Model 500 system can be used, as is, for a Model 400 or 600 system. But in order to optimize the system, only those registers required for remote drops (S461 $520) should be assigned to the LI. All other registers ($521-S4000 for the Model 410) or $521-S8000 for the Mode] 600) would still be available for storage. Because the Model 300 has only 112 registers available, the Rack Addressing presented in the previous section would not apply. Refer tolAppendix F] for additional information on Rack Addressing with a Modc! 300. 4.3.6 MULTIPLE Lis

If more drops or registers are required than those that can be supported by the present I.1, merely add an additional Ll module. *

An LI module only provides storage register locations lu a processor which possesses the capability to address them. The LI module does not increase the CPU addressing range capability.

SLOT 1 2 3 4 §&

STRRT ADORESS $1 | - |saeilsg7s cPuU {LI} LI MODEL |CRM/CRM Loca. (CPU) Sao |2e1a@e1o RACK END RODRESS saea| - |sszelsi

Figure 4.7 - Local (CPU) Rack Addresses with Multiple Lis

LI control register assignments are dependent upen Lt position and number of channels used.

*The number of Lis per system is CPU dependent, the Model 300 will support only one LI Module.

4.4 Summary

These steps should be looked at prior to setting up any LI/RI system.

1, Sketch out the physical system configuration, (rack as-semblics, power supplies, I/Os, etc.).

3. Determine the address allocations based upon requirements of the system.

3. Consider the system response time. Refer te LUR1 Update Time.

Page 13 30598-247-01

4.4.1 HAROWARE CONSIDERATIONS

1. Determine the physical 1’O requirements inciuding tu-ture expansion. (Quantity, voltages, racks ) Determine I/O locations and number of drops reguired as well as I/O per drop. 3. Determine the type of register modules required, including future expansion. 4. Determine the location of register moduies, quantity, and types of racks required. 4. All modules used with the local/remote interfaces must be of compatible series. 6. Communications devices should be powcred down when connecting and disconnecting communication cabling. If a communication wire were to be shorted, premature chip failure may result. . The Li module is always installed in the local CPU rack assembly. 8. The RI module is always installed in slot (, the CPU slot of the remote drop.

ho

+a

4.4.2 SOFTWARE CONSIDERATIONS

CAUTION: Only qualified personnel should ever program or implement action which may override the default system operations. A thorough understanding of the control bits is required. If any control bits are misapplied, adverse consequences may result.

1. Any detected system error will result in the system halting. However, it is possible to override the halting of the total system when an error is in the remote location, dependent upon the severity of the error detected.

2. All digital ’O address on a drop must be assigned to slot L.

3. No registers need be assigned to slot | of a register rack used as a drop.

4. Register Planning

Register and I/O distribution Jor present and future needs should be considered prior to attempting any register address allocation (rack addressing).

For effective distribution uf register addresses:

A. Distribute external addresses evenly among channels. This allows for a uniform LI/R] update ume.

B. Examine the LVRI update time. If it is too Jong, add an additional LI module tu ubtuin more channels. This will reduce the nuf isters per channel. For more detail, refer to] Appendix A.J/LI/RI Update Time.

Determine the CPU's ability to access the repisters in the LI. For more information, refer tol Figure 4.1Jand the appropriate processor instruction bulletin’ Remote drop addressing must be done sequentially. Therefore, plan to add future remote drops to channel 2.

For more information, refer to|Appendix Cj Channel

Expansion.

5. CPU will go into the RUN mode only if all the drops are operational. Note that a drop may be made to appear operational by setting a channel control register Fal ide Bit ON (1). For more information, refer tofAppendix nl LI Contral/Status Registers.