The instruction bulletin for the CRM-510 Network Interface Module (NIM), which links SY/MAX family programmable controllers, CRT programmers, printers, computers and other devices on a SY/NET network. It gives network and module specifications, installation and keying, indicator lights and switch settings, COMM port and network cabling, module operation and routing, the SY/MAX, Net to Net, Peripheral and 8881 modes, communication rung programming, troubleshooting and network performance.
Its parts
- Description
- Installation and Hardware
- Cabling - Wiring
- Module Operation
- Defining the Network
- Modes of Operation
- Application Programming
- Troubleshooting
- Advanced Capabilities
- Network Performance Considerations
- Appendices
- Addendum
From the manual
Key facts from this manual
Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.
Square D instruction bulletin 30598-257-02 (January 1988) for the Class 8030 Type CRM-510 Network Interface Module, which lets SY/MAX controllers, computers, printers and other devices talk to each other over a SY/NET network. It covers mounting, switch settings, port and network cabling, operating modes, communication error codes and troubleshooting.
- Device
- Network Interface Module (NIM) that links SY/MAX family devices over a SY/NET network p. 1, 5
- Ports
- Two independent RS-422 COMM ports, baud switch-selectable up to 9600; one SY/NET network port p. 5
- Power
- 950 mA at 5 VDC through the rack backplane p. 5
- Network size
- Two devices per NIM; up to 100 NIMs and 200 devices per network p. 5
- Mounting
- Register slot of an I/O rack or any slot of a register rack, including CRK-100, CRK-200, CRK-210, CRK-300, DRK-210, DRK-300, GRK-110, GRK-210, HRK-200, RRK-100 and RRK-200 p. 5
- Operating modes
- Each COMM port: SY/MAX Family, Net to Net, 8881 or Peripheral mode, set by DIP switches p. 5, 9
- Network cable
- Belden 9463 or equivalent twinax cable; a 78 ohm terminator at each end p. 11, 12
- Network length
- 62.5 K baud 15,000 ft; 125 K baud 9,250 ft; 250 K baud 4,250 ft; 500 K baud 2,400 ft (drop length 0) p. 12
- Network parts
- Cable end CCK-211, tee CCK-212, terminator set CCK-213, cable extension CCK-214; cables CC-201 (2 ft) and CC-202 (10 ft) p. 11
- COMM cables
- Class 8010 CC-100 (10 ft), CC-101 (30 ft), CC-102 (2 ft); kit CCK-102 for longer cables p. 10
- RS-232 devices
- Class 8010 Type CRM-600 RS-422 to RS-232 adapter with a CC-130 cable p. 10, 11
- Factory settings
- SY/MAX Family mode; ports 0 and 1 at 9600 baud; network port 62.5K baud; self test off p. 10
- Network address
- Set with two thumbwheel switches on the front of the module p. 7
- Network method
- Manchester encoded HDLC, token passing, CRC on all network transmissions p. 5
What this manual walks you through
- Keying a register slot for the network module p. 5, 6
- Setting the network baud rate, port baud rates and modes with the rear switches p. 8, 9, 10
- Reading the eight indicator lights p. 7, 30
- COMM port pinout and cables to SY/MAX and RS-232 devices p. 10, 11
- Building the network cable with ends, tees and terminators p. 11, 12
- Checking COMM port communication by the Rx and Tx lights p. 30, 31
- Looking up communication error codes p. 31, 39
- Running the module self-test p. 31
Good to know
- Never remove the module from the rack while power is on. p. 4
- Do not handle the module by the gold edge contacts; it is easily damaged by static. p. 4
- The COMM ports are RS-422 and do not support RS-232C devices directly. p. 10
- Set only one network baud switch up; otherwise the fastest rate is used. p. 8
- The COMM ports supply no power, so a loader/monitor needs its own power supply. p. 11
Questions this manual answers
How many devices can a SY/NET network of CRM-510 modules have?
Each NIM supports two devices, and up to 100 NIMs fit on one network, so up to 200 devices. p. 5
What do the CRM-510 self-test error flashes mean?
With NET Rx and Tx flashing together: one flash is a ROM checksum error, two a RAM error, three a serial port 0 or 1 error, four a network port error. p. 31
What does communication error 17 mean on a CRM-510?
The remote device is inactive. The network interface module generates this code; check the cable connections between devices. p. 39
What cable connects a CRM-510 to a SY/MAX processor?
A Class 8010 CC-100 series cable: CC-100 (10 ft), CC-101 (30 ft) or CC-102 (2 ft); kit CCK-102 for runs over 30 feet. p. 10
What is the maximum SY/NET network cable length?
15,000 feet at 62.5 K baud, down to 2,400 feet at 500 K baud, with the tee connected directly to the module. p. 12
Contents
Chapters and sections
Each line opens the PDF at its page.
- Class 8030 Type CRM5101
- Network Interface Module1
- Description1
- Warnings and Cautions4
- 1: Description5
- 2: Installation and Hardware5
- 3: Cabling - Wiring10
- 4: Module Operation13
- 5: Defining the Network15
- 6: Modes of Operation17
- 7: Application Programming27
- 8: Troubleshooting30
- 9: Advanced Capabilities33
- 10: Network Performance Considerations35
The whole text · 10 parts