Page 36, 30598-257-U2

APPENDIX A AN INTRODUCTION TO NETWORKS

This introduction is intended to provide a general overview of how industrial networks came to be and to familiarize the reader with some of the terminology. problems. and benefits derived from the technology. The first part is intended to be generic. For more detailed information, a short bibliography is included.

Glossary of Communication Terms:

Access: Allowed availability to information on network Base Band: Single frequency channel used for data transmission (low cost)

BAUD Rate: Speed at which bits of information are transmitted

Connection between similar devices, no pro- tocol manipulation required.

Bridge: Broad Band: More than one frequency is used for data transmission on a single cable

CSMA/CD:, Carrier Sense Multiple Access with Collision

Detection

Data Network: Path for information to travel

Gateway: A device that dves protocol conversion IEEE 802: IEEE’s standard for LAN’s 150: International Standards Organization

ISO DIS7498: ISO's proposed standard for LAN'’s LAN: Local Area Network

Layer: Phase within proposed standards dealing with a specific function.

OSI: Open Systems Interconnection. Network model developed by The International Stan- dards Organization (ISO).

Peripheral: | Those devices which support but are not directly involved in the control operation. Protocol: The language or word configuration used for communication. Usually invalves format for interaction and ¢rror detection.

Redundancy: Duplication of either hardware or software for reliability assurance.

Throughput: The ‘effective’ message rate, not the data rate (quantity of data vs. time) Token: Code that gives authority to devices to

“‘speak'" on the network.

When first introduced, the programmable controller was intended to replace relays with a sotid state device which would improve reliability and greatly increase flexibility. This device needed less panel space than was previously required. Installation costs were reduced, with the larger more complex systems providing the greatest pay back.

The simplicity of this device led to complexity of application when management realized that many tasks formerly thought of as unassociaied could be, and probably should be united. Product flow through factories was recognized as interrelat-ed, even though the individual work stations had separate control needs. From this realization, the need for networks was born.

In its simplest concept an industrial network is a group of two or more programmable controllers communicating with each other. Originally this was accomplished with a ‘‘cross-talk”’ module which took the outputs of one PC into the neighboring PC as inputs, and vice-versa. In cases where this module was not available, LO racks and modules had to be dedicated to this task which resulted in increased wiring costs and more complex programming. Data transfer could be accomplished only by dedicating four 1/O’s for each digit to be transferred, and then writing a BCD decode program in the receiving processor to load a register with the incoming value.

But the pressure from management was for information, such as the number of parts produced, amount of run time, and amount of down time associated with the run, all to be accu-mulated at one location, formatted for intelligent assimita-tion, and distributed as hardcopy. Maintenance people found they could use total run time to help them with preventive maintenance programs, The interest grew. Using I/O, this integration of P.C.s proved tu be cumbersome and difficult to imptement.

A single data cable strung around the perimeter of the plant was desirable. Devices had to be developed to tap into this cable and pick off or insert the data of interest at that point. Several types of cable were utilized: Coaxial cable where broadband transmission was used; twin axia) cable where baseband transmission was used; and even fiber optic cable was used.

Once this selection was made by a PC supplier, compatible gateways could be installed by the user to enable the data to be inserted on the network by the individual devices wherever they were located. Programming could now be done from any location to any device (at least with the Square_D network), and the whole process could be centrally coordinated.

But PC*s were not designed to gather data and process it into meaningful reports. It became apparent that this information needed to be fed into the large mainframe computers being used by the financial people.

Since there was much diversity among components from various vendors, certain societies and groups decided to address the problem of standardization so that all might connect amicably along a data network and so an [SO standard was developed The ISO standard DIS7498 has defined seven layers for network communications. The first two layers deal with data line connections within the network. The next two deal with the movement of the data within the network. The remaining three layers are for operator interaction within the network.

The IEEE 802 seems to be concentrating on the first two layers of the ISO standard DIS7498. The higher layers in geacral deal with the larger mainframe computers and less with PC to PC communication, Standardization, everyone agrees, is desirable; however it is not as yet a reality.

Let us assemble a generic network example of three programmable controllers from a single manufacturer, ¢ach control-

Page 37 read from a scan by OCR; it may hold reading errors

ling a separate specific function. These three functions deal with a single product and the functions are progressive. Each processor should be able to examine anothers i/O status and register information. This is an example of a bridge. There is ho protoco] problem here, since all are of common manutac-ture. Bridges like this are connected by inexpensively installed low voltage cable. In many cases interface cards are required for each PC. The distances involved may be from 2 few feet to many thousands of feet.

This is also an example of distributed control, because the controllers operate independently of each other yet communicate together as a network. The obvious advantage is that one component - one work station - may fatl, but the whole factory isn’t shut down as it would be if all stations were controlled from one PC.

The next base of complexity results from a desire to accumulate the data in the registers once a day for production records and inventory control. A host computer may be required. Often times, protocol and interconnection problems will make communication impossible. A gateway is probably needed. This device will] act as a translator in two directions, and allow the deviccs to communicate. The gateways are typically connected by a coaxial or twin axial cable, requiring a minumum of installation costs and providing for casy access should future devices be added to the system. With some systems, a tec can be cut into the wire and a drop established to another gateway at a minimal cost.

BAUD ratcs must also be compatible, Each device is programmed to send and/or receive information at a certain data rate. This is usually provided by dip switch scttings in par-ticular steps: L10, 300, 600, 1200, 2400, 4800, 9600, 19.2K BAUD. Modems transmitting over phone lines are typically sci at 300 BAUD. Processor to processor links are usually set at 9600 BAUD. Networks usually transfer data at rates from 19.2K BAUD to 1 MEGABAUD. Obviously, this requires the gateway to provide some communication transmission speed matching, so that the throughput of the network can be kept at its optimum rate.

Up to this point the network has been small enough and simpie cnough that communication will probably take place every time a device wishes to talk. But what happens if everyone decides to talk at once!

The problem of keeping multiple devices from trying to communicate at the same time can be handled by one of two commonly uscd methods: CSMA/CD or token passing. The first method services the requests on a first come first served basis. If there is a large number of devices with a large number of messages, access decreases quickly from about 40% utilization. There is atso a very real possibility of data collisions. (That's where the name comes from, Carrier Sense Multiple Access with Collision Detection.) The method requircs that m the event of a collision al] devices stop transmitting, ignore the data, wait a random amount of time and attempt to send again. This method can result in lower throughput rates.

A differcnt approach to the problem is token passing. where only one device talks at a time. A token or code is passed among the devices on the network. Whichever device picks up the tokcn is the master and remains so until done with its message. A danger in this approach is thal the temporary master may be doing something mundane while a crisis is occurring at another device. Another danger is a lost token.

A good solution to these problems is to have a time super-viscd token passing network (Square D approach). The token can never be indefinitely lost, nor can one device hold it for an indefinite amount of time. Integrity is an important factor

30598-257-02 Page 37 in data transmission. Typically. the transmitting device checks to sec if the receiving device is ready to receive. This established, the transmitting device sends its message. The receiving device acknowledges reccipt of the information and indicates how many bits were reccived. If itis the same as the number sent, all is assumed to be well. But what happens if the receiving device gets something less. or nothing? Does the transmitting device repeat the procedure? If su, how many times? All these questions have to be addressed by the network designer. Redundancy of processors, bridges, gateways, routes, and seftware checks will provide additional integrity. Any system uttlized must be designed to address data integrity.

As we progress toward total factory automation, networks become increasingly important. They allow for data collec-tion, storage and reporting. They can provide for central programming where programs can be uploaded. downloaded. modified or monitored. They can allow troubleshooting to be done remotely at distances of several miles.

As more and more devices hecome available the complexity will inerease. But from the work being done by IEEE and ISO and others in the field on standardization - compatibility. amicability, and usability will come.

General Information

The SY/NET is a high performance, token passing type network designed to communicate with a variety of devices in an industrial environment.

General Capabllities

Layer 1 - Physical

Connection into the system is accomplished utilizing a concentric twinax receptacle located at the bottom of each Network Interface Module le is Belden 9463 termi-nated as described in] Section 3.2.) Total cable length is

Network speed dependent.

Layer 2 - Data Link

This layer handles basic message format which consists of HDLC. Error detection is performed by using a Cyclic Redundancy Check (CRC) and Manchester encoding schemes.

Layer 3 - Network

The SY/NET Network utilizes a unique Masterless time token passing technique which eliminates message collisions while providing predictable access to any device connected to the system. The lower numbered Network Modules have a higher priority. As the network becomes busy to the point of con- Gnuaus message flow, all devices will still have regular access.

Layer 4 - Transport

Routing of messages is accomplished utilizing a simple sequence of numerical values representative of the point to which the end devices are connected (PC, CRT, etc.) Messages consist of packets of information of variable length, depending upon the function and amaunt of data ta be sent.

Layers 5, 6 and 7

Read, Write, and Alarm Communication rings within the PC further define layers 5, 6, and 7 which describe the data to be cammunicated, direction of data exchange, and error detection

Page 38 read from a scan by OCR; it may hold reading errors

Page 38 = 30598-257-02

APPENDIX B INSTALLING A NETWORK CABLE END

The network cable cnd (Class 8030 Type CCK-211) consists of ten parts.

WRENCH CONE NOTCHED SUELD cRiMP DIELECTRIC INSERT DIELECTRIC DIELECTRIC wut CONE WASHER SHIELD ed BODY ASSEMBLY 1 2 a 4 5 10

NETWORK CABLE END

The twinax cable (Beldon 9463 or equivalent) consists of seven parts.

OUTER JACKET (BLUE) OUELECTRIC

FILLERS BLUE

WHITE

BELOGN 9463 OF EQUIVALENT

TWINAX CABLE

The following is a procedure for assembling a network cable end to the twinax cable.

STEP | - Place WRENCH CRIMP NUT (1) onto network cable; threaded part of nut should face right.

STEP 2 - Strip approximately one inch of insulation from end of cable, be careful not to damage shield wires.

STEP 3. - Cut back BRAIDED shield to within .2 inches of cable jacket.

STEP 4. - Cut off filler cords to cable jacket.

STEP 5 - Thread blue and white wires thru small end of

CONE (2) and press cone into cable until re- cessed into cable jacket (cable end wilt flare out).

STEP 6 - Place small end of CONE DIELECTRIC (3) over wires and seat inside CONE (2}.

STEP 7 - Place red WASHER (4) over wires and seat against CONE DIELECTRIC (3).

STEP 8

STEP 9 STEP 10 STEP II

STEP 12

- Cut blue and white wires to a length of .35 inches

(measured from red washer (4)). Strip insulation off blue wires .2 inches.

Tin BLUE wire.

- Bend WHITE wire at a right angle away from

STEP 13 -

STEP 14

STEP 15 -

STEP 16 -

STEP 17

STEP 18

STEP 19

NOTE:

STEP 20

STEP 21

STEP 22

STEP 23

NOTE:

BLUE wire.

Place white NOTCHED INSERT (5) over BLUE wire and press until flush with red WASHER (4). (WHITE wire should fit into notched insert.)

Place PIN (6) over BLUE wire. Pin should be flush with NOTCHED INSERT (5).

Carefully solder pin (6) to BLUE wire (apply solder bead to hole in side of pin).

When solder cools, test connection by lightly pulling pin (6) with pliers - common problem found with cabic is cold solder joints.

Place pin dielectric (7) over pin (6). Place shield (8) over PIN assembly and seat against red WASHER (4). Thread WHITE wire thru notch in SHIELD (8).

- Strip WHITE wire back .25 inches.

Wrap WHITE wire around shield (8) and solder, let cool.

Solder and wire must not extend beyond shield ridge - otherwise WHITE wire could come in contact with connector body.

Place SHIELD DIELECTRIC (9) over shield (8) until flush with red WASHER (4).

Place BODY ASSEMBLY (10) over shield as- sembly.

- Thread WRENCH CRIMP NUT (1) into BODY

ASSEMBLY (10).

Perform continutity check on cable - you should have IOK ohms or greater resistance between blue wire and white wire and cither wire and shield. If a lower resistance is found, check for short in cable end, cable, opposite cable end.

Resistance measurements should be made: (1) without Network Modules attached (2) without Terminator attached.

Page 39 read from a scan by OCR; it may hold reading errors

APPENDIX C

30598-257-02 Page 39

COMMUNICATION ERROR CODES

The following is a list of error codes that will be annunciated during communications. Al] communication error codes are odd numbers ie: ], 3, 5, ete. For a complete list of error codes see Instruction Bulletin 30598-105-O1 (Processor).

ERROR ERROR CODE CODE NO. ERROR DESCRIPTION NO. ERROR DESCRIPTION G1 Illegal protocol opcode, the device does not rec- 29 An attempt has been made to send a message with ognize the instruction. an illegal route. 03 An illegal address has been attempted. 31 The end of the tape was encountered before the operation could be completed. 05 An illegal instruction has been attempted which is not allowed. (Example: Write 10 NIM set to pe- 33 Tape Data Error detected, the block of data in-ripheral made.) volved in the Read or Write operation was faulty. 07 An attempt has been made to alter data in a pro- 35 The cartridge is not seated properly or missing. or tected register. Check Control] Register 8176. the ‘‘Record’’ tab on the cartridge has been set to the Write Inhibit position. 09 An attempt has been made to alter data ina READ only register or Input. 37 An attempt to Skip or Read 2 file was made when already past the last file on the tape. 1] Communications error (receiver overflow). 39 Alarm already set within the D-LOG Module. 13 Communications error (link error). This error is generated by the processor. Check Control Regis- 4l Communication error with D-LOG Module was ter 8175 or the COMMs status register. Check encountered. cable connections between devices. 43 An illegal operation has been attempted - D-LOG 15 Communication overflow. Module protected. 17 The remote device is inactive. This error code is 45 Operation is not allowed - D-LOG Module's tape generated by the network interface module. operation in progress. Check cable connections between devices. 47 Operation is not allowed - keyswitch violation. 19 An illegal READ parameter has been assigned. 49 l/O, Register or Channel is safeguarded; used in 21 Trying to change a forced bit or WRITE to an Type SCP-344 and 544 RAM/PROM Processor. external output while the processor is in HALT. 51 Undefined register - a module is not seated prop- 23 An attempt has been made to alter data in a fenced erly or missing. register. 33 Illegal tape format - erase track required.

Page 40 read from a scan by OCR; it may hold reading errors

Sabo al

0598-257-0 ty

Page 40

APPENDIX D SUMMARY OF SWITCH SETTINGS

NETWORK SWITCH SETTINGS

[ - - - - Move 1 BAUD RATE, 4 SWITCH #1 OPTIONS 2 x RECEIVE/ SY/MA x] x 1 BROADCAST [x] Disaste_ | NET TO NET * 456 [ftwaece x x uIx $4 & $5 x x 8881 = ELT] 200 1 oan x] 8 BIT NO PARITY PERIPHERAL [%1%4% Gis 7 BIT ODD PARITY, | 1200 SELF S4& SS TEST *1*1*! 300 x| OFF NETWORK NETWORK x] | <}x ON SIZE BAUD 3/8 /8/2 x] 100 RATE S11 30 ONLY 1 UP SET SAME Z _, S S4 a REAR VIEW q j NETWORK x x MODULE Leet Lieb Py é 1234 12345 Lj 83 $4 NETWORK COMM PORTS PORT IT

NETWORK INTERFACE MODULE SIDE LABEL

SVNET ® NETWORK INTERFACE

CLASS 8030 TYPE CRM-5IO

COMM. PORT@ SWITCH SETTINGS $4 AND S5 NETWORK, SWITCH 53 SwiTcHT- SELF TEST) SWITCR SWITCH Switch SPECIAL ite €) MODE BAUD RATE [T2314 Jeaup RATE cor «OPERATION RB 1 jt SY/ MAX oje]i 9600 oli|i $00 K SET SELF TEST ANI Oo]. Ti¢elitoa 2400 t/ Ot 250 100/30 SWITCH TO CRE 886i ojali t260 1ji1to 128 K {OPEN} O| O[ PERIPHERAL [ o| of o 300 i{itifo 62.5 K NETW PARITY [22S Bt Le p ay 1_ _ || g__ |} 1 Rese : * | $3 | $4 $& an

CONSULT INSTRUCTION AULLETIN 30596-257- 01 FOR ACDITIONAL INFORMATION