Page 33
30598-257-02 Page 33
9.0 ADVANCED CAPABILITIES
The Network Interface Module supports route addresses from 000 to 254. Route addresses 000 to 199 arc used for point to point communications, i¢. from PC to PC ur CRT tu PC etc.
9.1 Special Route Values Route addresses above 199 are SPECIAL FUNCTION
ROUTES. These special route values allow the following functions:
Route Function
200 Read NIM module status
201 Don't care syurce route (first route) 202 Port to port (in-out same module) 203 Module pair (last route)
204 Don‘t care-no action taken
205-232 Unused
233-254 Broadcast capability
CAUTION: Care must be taken when using these advanced route instructions, as more than one module may be affected.
9.1.1 ROUTE 200.NIM STATUS
This route allows the status of the Networelotercface Module to be read in the form of register data.[See Table 9.1] for available data.
Register Deseription
] Type number (310)
2 Software revision
3 Module number - thumbwheel setting
4 Port 0 switch $5
5 Port | switch $4
6 Serial port # - if the message originates from the COMM ports this indicates which port the message came from (0 or |). If the message originated from the network, then the returned data is to be ignared.
7 Partitioned broadcast port 0 address
8 Partitioned Yyoadcast port | address
9 Number of Tx CTOEs
10 Number of ~~ errors
TABLE 9.1 - NIM STATUS
The route valuc 200 indicatcs NIM status will be read. The Toute number fullowing the route 200 instruciion, indicates which Network Interface Module status will be read. For example, to read NIM number 14 status, you would use a route of:
ROUTE A, 200, 14
Where: A -is the route number of the initiating device.
200 -is the NIM status command. 14 -is the number of the NIM to be read
The 200 route must be the second to the last route instruction.
9.1.2 ROUTE 201 - DON’T CARE SOURCE ROUTE
This route instruction allows an initiating device to communicate over the network without knowing its own route address otherwise referred to as ** WHOEVER - I- AM’’.
For example, if 2 PC wishes to communicate to device 22 alt that is needed is:
ROUTE 201, 22
Where: 201 -is the network device number of the initiating PC 22 -is the network device number of the destination device.
The route 20] instruction must be the first route instruction programmed.
NOTE: A special case exists where the Jast route instruction could be route - - -, 200, 20]. This allows the reading of the status registers of the Network Interface Module you are connected to without knowing the module number.
9.1.3 ROUTE 202 - PORT TO PORT {IN-OUT, SAME MODULE)
This route allows communications to occur betwecn two devices connected to the same module, without knowing the module number. For cxampic:
Route 4, 104 - can be replaced with ROUTE 201, 202
The above cxample provides communications from port G to port | or from port | to port 0, within the same module.
The route 202 instruction must be the second route instruction. No additional route values can be used.
9.1.4 ROUTE 203 - MODULE PAIR
This route allows communication between a pair of Network Interface Modules, without knowing either module number. A pair of Network Interface Modules consists of an even numbered module and its module number plus f (or an odd numbered module number, minus |), For example:
ROUTE 6, 203
Routes cammunications between device 6 and device 7 (even number plus |).
ROUTE 7, 203
Routes communications between modules 7 and 6 (odd num-her minus 1).
The route 203 instruction must be the second route instruction, no additional route values can be used.
9.1.5 ROUTE 204 - DON'T CARE (NO ACTION TAKEN}
When route 204 is used, no action is taken by the Network Interface Module. The route is ignored and the next route instruction is used. For example:
ROUTE 3, 204, 25 Is the same as: ROUTE 3, 25. This instruction allows increased flexibility with the data logging module when used with redundant networks.
Page 34
Page 34. 30598-257-02
9.2 Route 233 - 254 Broadcast
Broadcast consists of sending one communication message to several devices on the network. With point to point communications, all messages are acknowledged. The nature of broadcast messages does not allow acknowledgement of the message and therefore broadcast capability should be used with caution.
CAUTION: Model 300 processors do nol support the broadcast function.
9.2.1 SENDING A BROADCAST MESSAGE
Sending a broadcast message can consist of a WRITE or ALARM - for PCs of a PUTN command - fur « D-LOG module. See Figure 9.1.
Z ROWTE, _, AL - NT - - - - - RauITE, ROUTE, STAT, LOGAI ~ REMOTE - COU | TWRITE2 201 254 «S96 S20 $30 ' |
Figure 9.1 - WRITE Rung Using A Broadcast Route
The above WRITE nung will send register 20 to register 30 in all devices connected to port | of the SY/NET Interface Module.
Broadcast route instructions must be the LAST route instruc-tian.
NOTE: Broadcast messages are only sent ‘‘over the network’’. Broadcast messages will not be received by the same module that initiated the broadcast message.
When performing net-to-net broadcasts, the module containing the net-to-net link will pass the broadcast message to the network, the opposite COMM port in the same module will not receive the broadcast mes- Sage.
CAUTION: Broadcast messages are not acknowl- edged. It is the user's responsibility to determine which devices should be affected.
9.2.2 RECEIVING A BROADCAST MESSAGE
Every device on the network has the option to turn off (prevent receiving) a broadcast message.
This option to disable receiving broadcast messages is set by setting switch 1, UP on $4 or 85.
Once set to disable receiving broadcast messages. the Network Interface Module will ignore all broadcast messages.
NOTE: You may also prevent registers from being altered by using the tegister protect bit (8 176-4} or register fenc-ing.
9.2.3 BROADCAST ROUTE VALUES
Broadcast routes can be broken into two categories: (1) general and (2} module group.
9.2.3.1 General Broadcast
General broadcast allows messages to be sent to ALL Network Interface Modules on a single network. The general broadcast is broken into two areas. One route value refers to port 0 of all NIMs, and another to port | of all NIMs, these values are:
ROUTE 253 ROUTE 254
BROADCAST TO ALL. PORT 0 RROADCAST TO ALL, PORT |
9.2.3.2 Module Group Broadcast
20 broadcast route instructions have been set up to allow isolation of broadcast messages tov a group of ten devices.
The following chart describes broadcast route number and module group effected.
Raute Number, [Port Module Group Receiving 233 0 O- 9 234 1 235 0 10-19 236 I 237 0 20 - 29 238 1 239 0 30 - 39 240 I 24\ Q 40 - 49 242 1 243 ) 50 - 59 244 1 245 0 60 - 69 246 I 247 0 70-79 248 ]
249 1) 80 - 89 250 1
251 0 90 - 99 252 1
253 0 GENERAL 254 1
CAUTION: Broadcast messages are not acknowl- edged! The device initiating a broadcast will not receive areply (Bit 16) Also, there is no guarantee that all devices received the message.
For example, a route value of 235 will broadcast to all network device numbers 10 thru 19, A route value of 236 will broadcast to all device numbers 110 thru 119.
Page 35
30598-257-02 Page 35
10.0 NETWORK PERFORMANCE CONSIDERATIONS
From the factory, the Network Interface Module is set for the most general operating conditions. These conditions are:
SY/MAX Family mode
COMM ports set to 9600 BAUD Network BAUD rate set to 62.5 K BAUD Network size set to 100 modules
10.1 Network Baud Rate
The network BAUD rate has been set to 62.5 K BAUD to provide the most noise tolerant system with the maximum network cable length, By increasing the network BAUD rate to 125 K BAUD, you can increase the network speed (throughput) by seven percent. Each increase in the network BAUD rate will improve throughput by seven percent up to a maximum BAUD rate of 500 KJ See Section 3.2.2,for maximum network cable length based on BAUD rate.
10.2 100/30 Switch-Switch 7 on Switch Group $5
The 100/30 switch, switch 7, located on switch group S5 of the Network Interface Module controls the network size and NIM timers. From the factory this switch is set UP. What this means ts the network size could contain up to 100 modules numbered 00-99.
By setting the 100/30 switch to 30, the maximum number of modules for the network is 31; numbered 00-30. Also the module timers are altered and will not time beyond 30 time periods (modules 31-99 will not gain access to the network).
Reducing the network size to 30 modules will improve network access by a factor of three.
NOTE: All modules on the network must have the same setting for the 100/30 switch. If any modules have switch 7 set DOWN on switch group S85, (30 modules) the network size will be set to a maximum of 30 modules