Class 8030 Type CRM-510 Network Interface Module: 8: Troubleshooting

Pages 30 to 32 of 44, from Class 8030 Type CRM-510 Network Interface Module

The original document is the PDF (1.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Square D 8030 CRM-510 and Schneider 8030 CRM-510

Page 30 read from a scan by OCR; it may hold reading errors

Page 30 =. 30598-257-02

Latch coil 9-2 when ON, indicates a fault was detected from rung five.

This coi] will remain ON until reset by an unlatched coil 9-2, or a data entry.

Rung 7

This rung is used to send an update during the first scan of the processor. During scan one coil 9-4 will be OFF. enabling the normally closed contact in rung two. After the first scan, coil 9-4 will turn ON, disabling the same contact in mung two. The following is a summary of register and I/O usage.

SEND REGISTER DATA ON A CHANGE

ADDRESS USAGE §29, $30, $31 -0- 9-1, 9-2, 9-3, 9-4, 9-5

$30 - Master Timer $31 - Register change memory; holds old I/O or register $29 - STATUS register for “WRITE” cung

9 - O1 when ON, enables periodic update

9 - 02 when ON, indicates a Comm, fault

9 - 03 when ON, enables ‘‘WRITE’’ rung

9 - 04 when ON, enables update for one scan

9 - 05 when ON, sets fault latch and resets communications rung.

29 - 16 when ON, resets rung 2

8.0 TROUBLESHOOTING THE NETWORK INTERFACE MODULE

8.1 Module Troubleshooting Troubleshooting of the Network Interface Module can be broken into two areas. (1) hardware-indicating lights and (2) communications errors.

8.1.1 INDICATING LIGHTS

On the front of the NIM are eight indicating lights, the basic function of these lights are:

Light Description Function NETWORK ON = Busy/Activity RxO Receive Data Thru port 0 Tx0 Transmit Data Thru port 0 Rxl Receive Data Thru port | Txl Transmit Data Thru port |

Network Receiver Error Network Transmit Error 5 Volts applied to module

NET Rx ERROR NET Tx ERROR POWER

During power-up, the NET Tx and Rx lights will flash on and off in a defined sequence. This flashing indicates a self test is being performed. When both NET Rx and Tx lights are off the self test is complete and normal module operation can take place. If an internal fault is found, the power-up sequence will stop and the NET Rx and Tx lights wil] flash on and off_together, pause and then repeat until power is removed] See Table 8.1 for error description.

8.1.2 COMMUNICATIONS

The RxO, TxO and Rx1l. Txt lights indicate communications activity through COMM ports 0 and I respectively. Any ime the Network Interface Module transmits data out a COMM port the Tx LED will light. Also anytime data is received by the NIM's COMM port the Rx LED will light. During PC to PC, or CRT to PC communications these LED’s will flash.

When the Network Interface Module is set for the SY/MAX Family or Net to Net mode, an automatic communications check is made every two seconds. This check is made when no communications are taking place, otherwise referred to as an idle state. During this idle state, the NIM will send a2 small message to the device connected to each COMM port. (This message is an inquire.) If the attached device is a SY/MAX Family device, it will respond with a small message back to the NIM. This message exchange occurs every two seconds, and occurs independent of the customer program (transparent to the user),

If during the idle communications state, the Rx and Tx lights do not flash, inquiries are not getting through and therefore, normal communications cannot occur. Use the following chart to isolate the problem.

Action Possible Cause

I. Rx and Tx lights do |. Check power on NIM.

not flash. 2. Is NIM in SY/MAX Family or

Net to Net mode? Note: The NIM COMM ports support handshaking signals (CTS-RTS). These signals are jumpered allowing the NIM to communicate when the follow- ing cables are attached. CC-100 =CC-103 CC-101 CC-130 CC-102 CC-120 sertes B

See for additional information

Page 31 read from a scan by OCR; it may hold reading errors

3. ly cable plugged into NIM COMM port?

4. Perform sclf-tes NUM and connected ‘levied Seaton 81-3] 2. Tx LED flushes ON | 1. Check power on remote device. second and then turns 2. Check cable to remote device off and repeats. Rx 3. Cheek baud rate of NIM and re- LED off. mate device. 4. Remote device is not a SY/MAX Family device.

3 Tx and Rx LED's |. Check baud rates of NIM and re-flashing independent- mote device. fy similar to #2 2. Perform self-teston NIM and re-above. mote device.

ha

8.1.2.1 Communication Error Codes

When using READ, WRITE, or ALARM rungs, the status register of these rungs will contain a number which describes the results of the communication. When the number is between J and 16,000 the number represents an error code.

The following scction des and their possible causes summary of error codes.

phos: ~ on error codes See Appendix C For a complete

Error Codes Description

Error #3

Error #5

Error #7

Error #9

Errof #13

Error #15

Error #17

Error #19

Error #23

Illegal Address

Ilegal Operation

WRITE to protected Register

WRITE to READ only Register or Input

Link Error

Communication Overflow

Remote device inac- tive

READ count too large

WRITE to fenced reg- ister

Cause

- Out of range Ex- ample: Register 150 on Model! 300 PC,

- Parity Error - 888] mode.

- WRITE to control register 8100- 8192.

- Write to register in WO rack that contains an input card.

- Parity error or wrong baud rate - 8881 mode, loose cable - SY/MAX mode

- Remote device to busy to respond.

- No NIM exists. Remote NIM COMM port not connected.

Model 300 maxi- mum count is 16. Model 500 maxi- mum count is 64.

Register is pro- tected by proces- sor and cannot be written into.

3U598-257-02 Page 31

Error #29 Hicgal Route - Not enough route numbers.

Connected to wrong NIM (first number)

Middle route number directed to NIM which is not set up for Net- to-Net mode.

8.1.3 SELF-TEST

Far a more thorough test of the Network Interface Module’s memory, COMM ports and network port, use the following procedure.

1. Remove power to the NIM. 1234567

2. Remove cables from COMM and Net- = work ports.

3. Remove NIM trom rack.

4. Set switch 7 on switch group $4 S4

{DOWN} to enable self-test

Replace NIM.

6. Put test plugs into both COMM purts of NIM.

7. Reapply power to NIM.

wa

NOTE: Test plug is Class 8010 Type CTP-1!1 (two required). No test plug is required for the network port

When power is apphed t the NIM. the Tx] and Rx Sights will flash on and off followed by the Tx0 and RxO lights. This pattern will repeat approximately 50 times. At the same time the Rx und Tx ERROR lights will flash.

After approximately 75 seconds the NETWORK LED will turn on and off indicating data is being transmitted/reccived out the network port. This pattern will repeat four times. The above pattern will then repeat until power is removed. ‘The total test sequence takes approximately 90 seconds.

If an error is detected in the NIM, the NET Rx and Tx LED's s will flash on and off together, pausc and the flashing scquence until power is removed] Refer to table 8.1

Self Test Errors (Indicated by both Net Rx and Tx Leds Flashing)

One flash - ROM checksum error. Two flashes - RAM error.

Three flashes - serial port 0 or | ertor. Fuur flashes - network port error.

Table 8.1 -Network Error Lights

To turn the self test mode OFF set switch 7 UP on switch group 54.

8.2 System Troubleshooting

If it has been determined that the Network Interface Module is in operating order and the devices connected to it are ok, the following procedure can be used to isolate a network system fault.

Page 32 read from a scan by OCR; it may hold reading errors

Page 32 = 30598-257-02

Assumptions

Before troubleshooting can begin, several assumptions have to be made. They are:

- SY/MAX Family devices are involved. (PC, CRT, D- LOG)

- Power is applied to rack and Network Interface Modules.

- No error lights are on the NIMs

Basic Tools

For troubleshooting some basic pieces of hardware will be required, they are:

- One SPR-200 or SPR-300 CRT

- One PC Model 100, 300, 500, 700 - Two CC-100 Series Cables

- Two Network Interface Modules

- Appropriate Network Cables

Basic Layout

Figure 8.1 Bhows a basic minimum network layout that will Be Used dr troubleshooting. It is suggested that the two Network Interface Modules connected be isolated from the overall network. This removes the possibility of a defective network cable, duplicate Network Interface Module numbers, or conflicting network communications.

Figure 8.1 - BASIC Network Layout

Basic Operation

In our basic system layout, we have a PC, a CRT and iwo NIMs. A total of two NIMs have been_connected together using tee connectors and terminatra[ee Section 3.22) The intent is to start with a small network and expand to the full system. The following is a step by step procedure for network system troubleshooting.

STEP 1; Verify correct operation of PC and CRT.

A - Connect CRT to PC using CC-100 series cable. B - Turn on CRT (SY/MAX menu must be displayed). C - Depress STATUS softkey (leftmost key).

The CRT should be showing the status of the PC. If an error is indicated, correct before continuing. Possible errors could reflect a bad CRT, PC or cable.

STEP 2: Check PC to NIM operation. Now that proper non-network operation has been verified:

A - Connect the PC to the NIM using a CC-100 series cable.

B - Turn the processor key to HALT.

C - Apply power to PC and NIM.

D - Monitor NIM RX and TX LEDs for the Comm Port where the processor is connected.

The RX and TX LEDs should flash on, then off, once every two seconds, this is normal. If you d v rLED indications, correct before continuing|(See Section 8.1.2]for

LED operation).

STEP 3: Check CRT to NIM operation.

A - Connect CRT to other NIM Module,

B - Apply power to CRT and NIM (SY/MAX menu must be displayed).

C - Monitor the RX and TX LEDs as in step 2 above and verify proper operation.

STEP 4: Route CRT to PC over the Network.

A - Depress ROUTE softkey on CRT.

B - Enter network device numbers of CRT and PC (do not use special route addresses 200 and above).

C - Depress STATUS softkey on CRT to display processor status.

If the CPU status is displayed, the network system is working. Next, reconnect the network modules to the overall network system and again verify proper CRT to PC operation.

The most common errors that occur on the network are error code numbers 29 and 17.

Error 29 - Illegal Route

Error 29 refers to an illegal route value. This occurs when the network device number of the CRT does not match the thumbwheel number on the NIM where the CRT is connected.

Error 17 - inactive Device

Error 17 refers to a failure to communicate with a remote network device. Several causes of this error are:

I - The network device number does not exist. A. Route number may be incorrect. B. No NIM on the network has this number. C. Remote NIM does not have power. D. NIM network port is not connected (loose).

2 - NIM Comm Port specified by route is not working. A. No cable is attached to the Comm Port. B. Attached device is not working. C. Attached device is not a SY/MAX Family device.

When the above step by step troubleshooting procedure has not resulted in an operating network, you have now reached the point where local field support or headquarters support may be required. Before the call is made, several important picces of information should be obtained. These arc:

! - NIM series number (A. B.C. D). - Was system on-line before failure occurred or is this a New system (start-up) probiem. 3 - What are the switch settings for the Network Interface Modules involved.

ta