Page 10 30598-257-02

Note: As shipped from the factory, switches $3, $4, and S5 are set as follows:

123 4 1234567 {234567

Xx Xx X x x x 4 X|X1X X|X X|X X|X XX S83 84 $5 Mode - SY/MAX Family Ports 0 and 1 - 9600 Baud Network Port - 62.5K Baud

Self Test Mode - Off Network size - 1GO Modules

2.2.3 NETWORK PORT

On the bottom of the Network Interface Module (NIM) Is a [network port] {.JThis male connection is where the network cable will be connected. Recommended cable type is Belden 9463.

2.2.4 COMM PORTS

On the front of the NIM arq two COMM ports] These ports are used to interface with y and other devices. These ports operate as RS-422 ports and will not support RS-232C devices directly. With a special cable, RS- 422 can interface directly with current loop devices. Each port operates independently and supports handshaking (Request to Send - Clear to Send) signals. Adaptors are available for RS232C {Class 8010 Type CRM-600).

3.0 CABLING - WIRING

3.1 COMM Port

The COMM ports on the front of the Network Interface Module utilize RS-422 signal levels and also support hardware handshaking (Clear to send - Request to send) signals.

The following is a description of the signals available at the COMM ports.

Pin Number Function Direction l Transmit Data - Out 2 Transmit Data + Out 3 Receive Data - In 4 Receive Data + In 5 Clear to Send + In 6 Request to Send + Out 7 Clear to Send - In 8 Request to Send - Out 9 Shield

3.1.1 SVY/MAX FAMILY

When connecting a Network Interface Module to a SY/MAX Family device, you can use a standard Class 8010 Type cc- 100 Series cable. This cable can be purchased in several lengths. These lengths are:

Ciass Type Length 8010 CC-100 10 Ft. 8010 CC-101 30 Ft. 8010 CC-102 2 Ft.

When an application requires a cable length longer that 30 feet, e a connector kit and assemble your own cable. See Figure 3.1

Cable Kit: Class 8010 Type CCK-102, consists of:

2 - 9 pin connector DB9P 2 - connector covers 18 - pins

Page 11 read from a scan by OCR; it may hold reading errors

1 1 2 2 3 3 4 4 5 5 6 a Co 6 7 7 st Li, 9 9 9 Pin (Male) 9 Pin (Male)

Figure 3.1 - CC-100 - Serres Cable Wiring Diagram

The maximum recommended cable length is 10,000 feet. Recommended cable type is Beiden $723 or equivalent (2 pairs shielded, with ground).

The Neiwork I[nterface Module COMM ports also support handshake signals (Clear to Send - Kequest to Send). These signais are not needed when a SY/MAX Family device is used. and therefore are jumpered in the CC-100 Series cables. The CC-100 Series cables can he used with a variely of devices:

NIM to CRT CRT to PC NIM to PC D-LOG tu PC NIM to D-LOG PCM to PC NIM to PCM NIM to NIM

NIM to Loader/Recorder

3.1.2 LOADER/MONITOR, 8881, AND OTHER PERIPHERAL DEVICES

3.1.2.1 Loader/Monitor To Network Interface Module

The loader/monitor, when used in the message mode, can be connected to a Network Interface Module (NIM) to display alarm or data messages. The NIM would be set for the peripheral mode. Although the loader/moniter does communicate using RS422 signals, the toader/monitor will need to obtain power from a separate power supply (the NIM COMM ports do not provide power}. See instruction bulletin 30598-163- gl.

RS422 to RS232

When it is necessary to connect an RS232 device toa NIM. a Class 8010 Type CRM 600 RS422 to RS232 adaptor can be used. The cable used to connect the CRM NIM

-600 to th should be a Class 8010 Type CC-130]See Figure 3.2

For additional cable/hardware information, see instruction bulletin 30598- 180-01 (printers).

NIM

A co on TO S232

° a EVICE cc + 130

Figure 3.2 - CRM-600 - RS422 to AS232 Adapter

30598-257-02 Page II

3.1.2.2 3881 To Network Interface Module

When an 8881 PR-3 is connected to a NIM, an RS232 to RS422 adaptor would normally be required. if the distance between the 8881 PR-3 and the NIM is 5U feet or less, a peciat RS232/current loop cable can be used. See section 6.4.1 }for specific cable information.

3.2 Network Port

On the bottom of the Network Interface Module is a network port. This port provides communications between Network Interface Modules. When you connect two or more NIMs together, you wall form a communications network.

3.2.1 HARDWARE, CONNECTORS, TEE’S, TERMINATORS

Cannecting Network Interface Modules together involves several parts. The following is a description of these parts.

Connectors

When building a Network cable. you will need four types of connectors. These connectors are:

Connector Class Type Cable End 8030 CCK-211 Tec Connector 8030 CCK-212 Terminator (sct of two) 8030 CCK-213 Cable Extension 8030 CCK-214 Cable End

-_

The cable end consists of a [emale socket and can be used with Belden 9463 or equivalent twinax cable. Two cable ends are required for cach Iength of network cable.

Factory assembled cables have been made in two lengths. These lengths are:

2 foot length Class 8030 Type CC-201 10 foot length Class 8030 Type CC-202

When an application requires a cable length longer than 10 feet. you can purchase a connector kit and assemble your own cable. Connector kil is a CLASS 8030 type CCK-211 (two required).

Recommended cable type is Belden 9463 or equivalent twinax cable.

See Appendix B}for cable assembly instructions.

Page 12 read from a scan by OCR; it may hold reading errors

Page 12 30598-257-02

Tee Connector

The Tee connector consists of two male plugs and one female socket. Ihe female end, plugs in under the Network Interface Module. Uhe two male plugs allow connections to a network cable.

Terminator

The terminator consists of a female socket and an internal 78 ohm resistor. One lerminator is required at each end af the network cable. Only two terminators are required per network system.

Cable Extension

The cable extension consists of two male plugs. This extension can be used to (1) connect two network cables together, (2) replace 2 tee connector when a Network Interface Module is removed, (3) used to provide the splice for a future Network Interface Module (replace the cable extension with a tee connector) and (4) used to extend the distance between the Network interface Module and the tee connector.

3.2.2 MULTIDROP CONFIGURATION The SY/NET communication system consists of a baseband-bus configuration. What this means is that a single cable is extended across a plant or building and then all devices that wish to talk on the network simp D io the network, sharing this common cable.JSee Figure 3.3

SY/NET #2

Figure 3.3 - Sample Network Layout

3.2.2.1 Network Cable Length

By changing the BAUD rate of the network, you can vary the maximum overall length of the network cable and the distance between the Network Interface Module and the Network Tee Connector (drop length). The following table describes the maximum network cable length based on network BALD rate.

Network Maximum Natwork Length BAUD rate (in feet) 62.5 K BAUD 15,000 125 K BAUD 9,250 250 K BAUD 4,250 500 K BAUD 2,400

Drop length equals 0 feet.

: i ED i$} -2 a ies

TERMINATOR “TEE” TYPE CC 202 "TEE™ am

These maximum network cable lengths are based on connecting the network ‘‘T’’ connector directly to the Network Interface Module (drop length equals 0 feet). When it is necessary to extend the distance between the network *‘T"' connector and the Network Interface Module the following chart can be used as a guide in determining the maximum possible network length.

Network Number Drop Maximum Net BAUD rate of Drops Length Length (ft.} 500 K 100 0 2,400 250 K 100 0 4,250 125 K 100 0 9,250 62.5 K 100 0 15,000 62.5 K 25 100 109,250 62.5 K 100 100 950 ctm EXTENSION TERMINATOR “TEE” yee chan “TEE” TEAMIMATOR