Page 4
WARNING
The application of this product requires expertise in the design and programming of control systems. Only persons with such expertise should be allowed to program, install, alter, and apply this product. Potential bodily injury, death, or equipment damage could result if the product is improperly applied te any equipment application.
CAUTION
SY/MAX devices contain electronic components that are very susceptible to damage from electrostatic discharge. DO NOT handle this device by the gold edge contacts.
A static charge can accumulate on the aurface of ordinary plastic wrapping or cushioning material. If any SY/MAX device must be returned to Square D, the following packaging instructions must be followed:
PREFERRED: Use the origina! packaging material as supplied by Square D. Place the device inside the metallized plastic bag.
ACCEPTABLE: Wrap the device in some type of antistatic material. Antistatic plastic material can be identified by ita pink color, and can be obtained in sheet or bag form.
UNACCEPTABLE: Do not use ordinary plastic film, foam, or styrene chips ("popcorn™ or peanuts”). These materials can accumulate static charges in excess of 10,000 volts, resulting in possible damage to the SY/MAX electronic companents.
Antistatic {metallized plastic) bags can be obtained from the following manufacturers: @ 3M Company (800-328-1368) Type 2100 bag ® Static, Inc. (800-782-8424) 8000 Series bag @ Charles Water (617-964-8370) CP-303 bag
CAUTION
Improper handling may cause permanent damage to this device.
1) Never remove this device from the rack while power is ON. Turn power supply switch to OFF and wait until all indicating lights are off before removing.
2) Do not subject to static discharge.
3) Donot touch gold edge contacts.
NOTICE
The products and services described in this manual are useful in a wide variety of different applications. Therefore, the user and others responsible for applying the products and services described herein are responsible for determining their acceptability for each application. While efforts have been made to provide accurate information within this manual, the Square D Company assumes no responsibility for the application, completeness or usefulness of the information contained herein.
UNDER NO CIRCUMSTANCE WILL THE SQUARE D COMPANY OR ANY OF ITS SUBSIDIARIES BE RESPONSIBLE OR LIABLE FOR ANY DAMAGES OR LOSSES, INCLUDING INDIRECT OR CONSEQUENTIAL DAMAGES OR LOSSES, ARISING FROM EITHER THE USE OF ANY INFORMATION CONTAINED WITHIN THIS MANUAL OR THE USE OF ANY PRODUCTS OR SERVICES REFERENCED HEREIN.
No patent liability is assumed by the Square D Company with respect to the use of any of the information, products, circuits , programming or services referenced herein.
The information contained in this manual is subject to change without notice.
Page 5
30598-257-02 Page 5
1.0 DESCRIPTION
1.1 Introduction
The Class 8030 Type CRM-5t0 Network Interface Module (NIM) is a communications interface, which allows PCs, CRTs, printers, computers, and other SY/MAX Family devices to communicate with each other, exchanging register data and VO status. When a CRT Programmer is connected to the SY/NET Network, you can program, monitor, force I/O and UP/DOWN load ladder diagram programs to any S¥Y/MAX PC on the Network.
Each Network Interface Module (NIM) can support two devices. Up to 100 NIMs can be connected to a single network, allowing up to 200 devices on one network. With the SY/NET network, you can also link several networks together. Network linking provides network expansion and opens the door for distributed networks and network redundancy.
The SY/NET Network has been designed with simplicity in mind without sacrificing flexibility. Communicating between two PCs can be accomplished by utilizing a single rung of the ladder diagram. To communicate the same data OVER THE SY/NET NETWORK all that is needed is to add two route values; source device number and destination device number. Once these route values are added to a communication rung, the same message will then be sent “‘OVER THE NETWORK”.
The SY/NET Network, in addition to supporting the SY/MAX Family, also supports communications with the 8881 PC, computers. printers, bar code readers, and other ASCII devices. 1.2 Specifications
1.2.1 NETWORK SPECIFICATIONS
A. Cable -baseband twinaxial cable, Belden
9463, or equivalent.
B. Connectors -dual concentric twist lock. Tees, cable ends, adapters, etc. are avail- able from Square D.
-required on each end of the Net- work cable.
-| megahertz.
-Communication baud rate depen- dent (cable length vs BAUD rate).
Transmission type -Manchester encoded HDLC. Message format -packet type similar to ANSI 3.28
Collision avoidance -token passing, based on time win-dows
-based on module number (lowest number has highest priority).
-CRC (cyclic redundancy code) on all network transmissions.
-source/destination message routes are placed in the command for each device wishing to communicate -200 devices per Network maximum
-Net-to-Net linking - standard, no limit
Terminators
Cc
D. Clock frequency E. Cable length F G H
1. Priority
J. Error checking
*
Message routing
L. Number of devices M. Expansion
1.2.2 INTERFACE MODULE SPECIFICATIONS
Plugs into any ‘*‘REGISTER” slot.
Requires 950ma at 5 VDC through back plane rack connection.
Single high speed (SY/NET) connector per module.
Two independent low speed RS-422 reccptacles per module. Baud rates switch-selectable to 9600 Baud.
Four operating modes per low speed port: SY/MAX Family devices, 8881 Programmable Controller, Net to Net, and peripheral devices. Dip switch selectable.
Module *‘address”’ selected by tool operated thumbwheel switches,
. [Pol special commands such as broadcast. See Section 9.0 mon wP oO ™m
2.0 INSTALLATION AND HARDWARE
2.1 Instaliation
The Network Interface Module consists of a single module similar in size to the Model 300 Processor. This moduse can be plugged into the register slot of an [/O rack or any slot in a register rack. A Network Interface Module can be inserted in the following racks:
Class 8030 Type Type CRK-100 GRK-110 CRK-200 GRK-210 CRK-210 HRK-1) CRK-300 HRK-200 DRK-210 RRK-100 DRK-300 RRK-200
The Network Interface Module operates on 5 VDC and obtains this power from an I/O or register rack. No other signals exist between the Network Interface Module and the rack except for power connections.
2.1.1 MODULE KEYING
Each register slot, whether on a digital or register rack, has two keying pins which are installed at the factory. These are located between slot location 4 and 6 and location 96 and 98. These pins insure only register modules can be plugged into register slots.
Each SY/MAX register slot may be keyed to accept only one type of SY/MAX register module. An optional keying pin kit, Class 8030 Type CBP-104, is available for this purpose. The cormect position of the keying pi be Network Interface Module is between pins 14 and roSeerigue 2.1 1} The keying pin is sme'y inserted manually into the s Oto Th ie ak connec-e keying pin insertion tool provided with the kit.
See Figure 2.2.
Page 6
Page 6, 30598-257-02
CAUTION: When inserting or removing the Keying pins, use care to avoid touching the contact fingers within the connector. Improper insertion/removal may damage the connector.
1] 4 REGISTER KEYING PIN 6 * BETWEEN SLOTS 4 AND 6 [1] 8 pf] 19, - OPTIONAL YL) 12 NETWORK INTERFACE MODULE KEYING PIN 14 BETWEEN SLOTS 10 AND 12 i ca 18 Lh “tt, = 28 }+__4 0, - 32 REGISTER = ae SLOT | 38 >, a bP anerd a fine L 4} =| ,_} }__] BE |] 88 =). 90 _|{_} 92 - - j}+- - ce REGISTER KEYING PIN ge © BETWEEN SLOTS 96 AND 98 FoI L
Figure 2.1 - Module Keying
KEYING PIN
Figure 2.2 - Keying Pin Insertion
2.2 Hardware
The Network Interface Module (NiM) consists of a module 2 inches wide by || inches high by 7 inches deep. Located on the front of the NIM are 8 indicator lights, 2 thumbwheel switches P unication ports - for PC's, CRT’s, printers, etc. See Figure 2.3 Module Overview.
See Figure 2.4. aoa
Click here to view graphic.
Figure 2.3, Module Overview a receptacle for the Network Communication Cable. This is where the network cable is attached (Cable
Click here to view graphic.
Figure 2.4 - Network Connector
At the rear of the module, near the edge connector, are three sets of switches labeled $3, $4, and S5. These switches are used to select ration, baud rate, and other operational functions. See
Page 7
Click here to view graphic.
Figure 2.5 - Side View, Cover Removed
2.2.1 INDICATOR LIGHTS
The Network Interface Module has eight indicator lights which help in troubleshooting. The lights are:
NETWORK
Rx 0
Tx 0
Rx ]
Tx J
NET Rx ERROR
NET Tx ERROR
POWER
Click here to view graphic.
Figure 2.6 - NIM LEDs
30598-257-02 Page 7
NETWORK, This AMBER light when on, indicates activity on the Network. Typically this light is very dim: this is normal. As more and more devices communicate over the Network. this light will glow brighter.
Rx 0, This AMBER light indicates that the Network Interface Module is receiving data from the device connected to Port 0.
Tx 0, This AMBER light indicates that the NIM is transmitting data to the device connected to Port 0.
Rx |, Same as Rx 0 except for Port 1. Tx |, Same as Tx 0 except for Port L.
NET Rx ERROR, This RED light indicates that a communication error has occurred on received network data. Typically this light indi- cates that all buffers are full.
NET Tx ERROR, This RED light indicates that an error has occurred when the NIM attemptcd to send a message on the Network. Typically this occurs when a message is routed to a NIM that does not exist.
POWER, This GREEN light indicates that the NIM has power applicd. The Power LED is wired directly to the incoming 5 VDC power to the card.
NOTE: Se roubleshooting for additional information on operation of lights.
2.2.2 SWITCHES
The NIM has 2 types of switches; 2 thumbwheel switches and 3 groups of rocker switches. These switches select various options of the NIM.
2.2.2.1 Thumbwheel Switches
On the front of the Network Interface Module arc two thumbwheel switches. hese switches are used to select the module address on the network.
On the right side of the module - next to the thumbwhcels - are two access holes. These holes allow setting of the thumbwheels using a small screwdriver. Once sct. you should write the number of the thumbwhceels onto the write-in areas on the front of the module. This number dcfings the network device number for COMM ports 0 and |. SeefSection 5.2}for more information.
Click here to view graphic.
Figure 2.7 - Thumbwhee! Switches
Page 8
Page 8 = 30598-257-02
2.2.2.2 Printed Circuit Board Mounted Switches
On the rear of the Network Intestace M : > £roups of switches lubeled $3, S4. and $5
Click here to view graphic.
Figure 2.8 - Printed Circuit Board Mounted Switches
Each switch group contains 4 or more wuividual switches numbeved 1-4 or 1-7. These switches are used to set NET- WORK baud rate, COMM port baud rate, mode of operation for Ports 0 and L. and other special functions.
Manufacturers supplying DIP switches have not standardized on the physical position of a DIP switch and its corresponding electrical state. This has caused a lotof confusion as to which way a switch should be set. Complicating the situation further, are the numerous state descriptions use cribe whether a switch is conducting or not {Sec Table 2.1] x UP__| 7 L OPEN | 0} OFF X}| DOWN || JCLOSE | | | ON
Table 2.1 - Switch Label Options
Throughout this manual two switch conventions will be used, (1) physical and (2) description.
A physical switch setting refers to the position of the switch handle with respect to the printed circuit board. The letter “*X"" will denote handle position, for example, the following will refer to switches 1, 4 and 7 up and 2, 3, 5, and 6 down.
12345 6? xX: x x XIX] [X[X
Description switch settings of "SUP" and “DOWN” will be used when a combination of switches are being discussed. For example:
SWITCH BAUD RATE 4 5 6 UP |DOWN |BOWN 9ADO UP |DOWN| UP 2400 UP UP |DOWN 1200 UP UP UP 300 $4 or S5
The above table describes BAUD rate options for the COMM ports. A BAUD rate of 9600 could also be described as:
SWITCH 123456 7 x
X[X 9600 BAUD
Switch Group S3 - NETWORK BAUD RATE
Switch group S3 selects the baud rate for the network. As the network baud rate is increased, it becomes necessary to limit the maximum overall length of the network cable in order to reduce anise susceptibility caused by signal reflections in the cable. For this reason, the petmork b ate can be change from SOOK to 62.5K baud] Sce Table 2.2.
BAUD MAX LENGTH
SWITCH RATE (Cable Feet)
| 2 3 4 LP | DOWN |DOWN |DOWN | 500,000 2,400 MAX DOWN| UP |DOWN|DOWN} 250,000 | 4,250 MAX DOWN |DOWN] UP |DOWN] 125.000 | 9,250 MAX DOWN | DOWN [DOWN | _UP 62,500 | [5,000 MAX
Table 2.2 - Networx BAUD rate
Note: Setonty one switch UP otherwise the fastest baud rate will be active.
By providing a selectable baud rate, the user can adapt the SY/NET system to many geographical layouts.
Note: Reducing the baud rate by 50% does not cut network performance by 50%, thercis only a 7% change in performance J See Scction 10.0 for more performance information,
Switch Groups $4 and 85 - COMM PORT ! AND O Switch groups $4 and S5 are used to select:
- Mode of operation for COMM ports - Baud rate for COMM ports
- Self test
- 100/30 network size
Switch groups $4 and S5 each contain 7 switches. Switches |-6 on switch group $5 contro] COMM Port 0. Switches |-6 on switch group $4 contro] COMM Port 1.
Switch #7 on switch groups $4 and 55 select self test and network size respectively.
The following is a description of all switches (1-7) on switch groups S4 and S5.
Switch 1
This switch selects several options depending on the made you are in.
Page 9
30598-257-02 Page 9
SY/MAX Family and 8881 Mode Switches 4, 5, and 6 - Select Baud Rate
This switch selects whether broadcast messages on the network should be received.
SWITCH BAUD RATE 1234567 4 5 6 Up Disable Receive Broadcast Se UP_ | DOWN | DOWN 9600 1234567 Bown | Receive Broadcast. UP |DOWN| UP 2400 Ee uP UP | DOWN 1200 See Section 9.1 for more broadcast information. UP UP UP 300 Net-to-Net Mode - Switch reserved for future use $4 or S5 Peripheral Mode In the peripheral mode. you have the option to select parity Switch 7 On switch group S4 1234567 for each communication port. When UP allows normal oper-alion. - when DOWN. enables self-test] See Section 8.1.3. Up Eight Bit Word, No Parity Down | Seven Bit Word, Odd Parity
Switch 7 On switch group SS 1234567 When a SY/MAX Family CRT is used in the peripheral When UP sets network size to
. this switch should be in the DOWN position. 100» DO yidisetsnetiie
Switch 2 and 3 - Made
MODE SWITCH By setting baud rate and mode switches, the user can adapt 2 3 the Network Interface Module to a variety of devices, i.e.
SY/MAX DOWN | DOWN CRT's, Programmable Controllers, modems. printers, com- Net To Net UP |DOWN puters. 888) DOWN} UP Peripheral UP UP S4 or $5 Figure 2.9)provides a summary of Switch settings. I MODE 1 c S$AUD RATE, ~ SWITCH #1 OPTIONS 12 3 fx RECEIVE/ syMAX Te 1 BROADCAST J - Fy DISAGLE NET TONET |=} 456 NAGLE EOL] eao0 $4 & S5 ess) [x] |x x} 8 BIT NO PARITY PERIPHERAL Hd] Tz 7 BIT ODD PARITY > 1200 SELF S4 & SS TEST xix) 300 xf OFE NETWORK NETWORK = |¥]*< |<} LY ON ee BAUD 19] 2 x RATE S/RElg 30 ONLY 1 UP 4 é REAR VIEW aii NETWORK CTI] MODULE xxix] | é 1234 fe 53 NETWORK POAT
Figure 2.9 - Summary of Switch Settings