Page 4
Page 4 30598-251-01
LIST OF FIGURES
Description Page Transfer Interface System... 02.0.2. cece eee nen eee eee eee eee tence eeeeeeeeeeens 5 Local Transfer Interface ..... 00. cee eee eee eee ee ree ener tee EEE eee ee eee EEE S EER OEE DEES EOE ES 6 Remote Transfer Interface 20.0... cece cece eee eee eee ene ene REE REE Eee EE ee EEE Eee eee 6 RTI DIP Switches... 2.0. ee een een een eee eee eee eens eee 9 RTI DIP Switch Label... ccc cece nee eee Eee EEA eee nee teeta 9 Module Keying... 2... 26. ee ee tee tee eee eee eee e ee ene tee eee ene 9 1;O Channel Wiring Configuration ...... 00... ccc cece ee eee eee 10 RTC Channel: LTI To LT] Connections 0.0... 0... cc cece eee e eet eee ates eee eb beeeenee 11 §.OChannel: LTI To RTI Connections -.......... 2.20. cece eee entree eee teen ne ee tee een eee tiee iF CPU Address Capabilities 2... 22.0.0 cence cee ene e nee en eee tneeenteeeetne 13 CPU Rack Addressing 0.0... cece ccc cece ree tee tee tee eee tet eee eee dt eae ne we nee eeetentetas 14 Channel 1, Drop #1] Rack Addressing .......... 0... e cece cece erect reece eee e tren neat ee eeeeeeeeees 14 Channel] 1, Drop #2 Rack Addressing «0.0... 0c: c cece r teen e eee ee ee eee ee eet eee treet tenet eeeennes i4 Channel 1, Drop #3 Rack Addressing 0.0.0.0... 0c cece cece eee eee teen ee ebb seat e enti 15 Multiple LTI Rack Addressing ... 2.00... cece cece e cence ee ee eee eee eben cere tenet e eee etee 16 Disable Outputs LED Display... .... ccc eee cee ccc cece eee beeen eee eee eee tee esteeeneee 21 Run LED Display ... 0.2.0... ene en eee et eee een nee Eee eee eens 2I LTI Control Register Assignments . 0.222. ce eee cee cee tee tte ee reece eee tens eee bene eeee tenes .. 23 LTI 1-O Channel Control Register Data Field 2.2.2.0... 0.000200 e et eee ete eeeee 24 LTI I; O Channel Control Register Status Field 2.0.0.0 0 0c eect eee tt esate eebeeeeee 25 RTC Control Register Data Field ...... 0. cece cece ence e eee ee eee ebb eee e ee een een ee gate 28 RTC Control Register Status Field .... 00. ccc cece cee ee cee ee eee etna ree nent eebbeeeane 29 Processor Stat Priority ... 0.2.0.0. eee ene ee tent ene e eee e tees es eastern see ennes 3) | SI: 100) 6) Cam Oe Os 33 Programming Rungs for TIS Requirements ..... 0.2.0... cee ccc reenter eet n eaten eee eeeeee 34 Bit Exchange of READ/ WRITE Register ..... 0... ccc cece ete cece cece ete eee nett eteeeteneeune 42 Primary-to-Backup Control] . 22.0... eee eee eee te eet nese bene ebeeeee 42 Backup-to-Primary Control .. 0... ccc cece cee een eee eee eben een teeter eet ee ee eeeteeeenne 43 Primary Disable of Startup Transfer via Ladder... 00... ccc cece cee eee cece tenet cnet eee seen eee naees 43
Backup Shutdown: Alarm Sequence 0... ccc ccc e eeeee e eee etree eee eee n eens 43
Page 5
30598-251-01 Page 5
1.0 INTRODUCTION
1.1 General information
The Local and Remote Transfer Interface (LTI and RTI) Modules make up the Transfer Interface System (TIS) for the SY: MAX Programmabie Controller family. For critical applications where down-time cannot be tolerated. the TIS will decrease system down-times by enabling redundant processors (Primary and Backup) to control the input: output system, thereby allowing system operation to withstand any single fault in either Primary or Backup Systems without interruption of system 1/O control.
41.2 Summary of Operation
The LTi and RTI modules provide the communication between processors and ] O, and supervise the actual transfer of control from a faulty Primary Processor to a Backup Processor. All communication is via a two pair, twisted, shielded cable.
The Transfer Interface System consists of two matched CPU racks, each containing a Model 500 or 700 processor and up to seven Loca] Transfer Interface Modules. The system designates the controlling CPU rack as Primary and the remaining rack as Backup. Should a fault occur in the Primary system, control would be switched to the Backup and the given designations would change. Each LTI in the Primary rack 1s paired with another in the Backup rack.
The LTI has two communication channels -- a Register Transfer Channel (RTC) and 1/O Channel. The RTCs of each LTI pair are connected together to transfer registers from one LTI to the other. synchronize processor scans, and determine when to switch contro), The | O Channel is wired to and controls the input and output devices via the Remote Transfer Interface.
The RTL has two communication channels, A and B, to connect to the | O Channel of the Primary and Backup LTIs.
Cuil R P |T T vy! 1/0 A 4 b =e a | cyt R P| T T Uli ) 0 l 8 >. j h a Se |
Figure 1.1; - Transfer Interface System
2.0 SPECIFICATIONS
2.1 General information
The Local and Remote Transfer Interface Modules, as well as the entire SY;MAX Programmable Controller family. are designed and manufactured to comply with U.L. requirements. Refer to UL File Number E85106.
2.2 Electrical 2.2.41 CURRENT DRAW (ON SY/MAX POWER SUPPLY)
8030 CRM-230 Local Transfer Interface 1.6 Amps @ 5 ¥YDC 8030 CRM-232 Remote Transfer Interface 1.0 Amps @ 5 VDC
2.2.2 CAPABILITIES
Registers: CRM-230 contains 4096 registers (255 for externa] drop addressing, 3841 for internal data storage). Unused external registers may also be used for internal data storage. All registers which follow those assigned to Channel 2 are retentive,
| O Channel: 1 1-O Channel per Loca] Transfer Interface. 255 Registers maximum. 1024 Digital 1.O maximum. 8 Drops maximum.
Drops: 128 Digital |.O per drop maximum. 127 Registers per drop maximum.
Available 1: O Points: 1024 Digital | O per LTI. 255 Analog 1 O per LTI. Maximum of 7 LTI’s per system.
Register Transfer Channel: ] Register Transfer Channel per Local Transfer Interface. 32 Registers transferrable per ladder scan. 4096 Registers transferrable upon system startup.
Communication Method: Continuous full duplex serial differential.
Page 6
Page 6 30598-251-01
Transmission Rate: I O Channel), 62.5K Baud.
Register Transfer Channel! 375K Baud.
Transmission Distance (using recommended cable -- Belden 8723):
EO Channel - 2500 f1. (762m.) max.
Register Transfer Channet - 25 ft. (7.6m.) max.
1 O Channel Update Times for Digital 1. O (approximate values):
I drop, 16 1/O - 5 ms.
| drop, 128 1/O, 19 ms.
8 drops, [024 1/0, 91 ms.
Transfer Control Switch Times: 3 CPU scans or 60 ms (whichever is greater) from detection of fault if RTC communication link is intact (regardless of whether or not scans are synchronized. i.e. whether transfer is bumpless or bump).
3 CPU scans or 250 ms (whichever is greater) from detection of fault if processors are not synchronized (bump transfer) and RTC communication link is no¢ intact.
2.2.3 COMPATIBILITY WITH PROCESSORS
The Transfer interface System is compatible with Model 500 (Series M or later) and Model 700 (Series C or later} processors.
The TIS is not compatible with Model 300 processors.
2.2.4 COMPATIBILITY WITH RACKS
The loca) Transfer Interface Module must be mounted ina register slot of the RRK-100 or RRK-200 CPU rack. The Remote Transfer Interface Module is mounted in the CPU slot of any digital or register 1 O rack except for the Control Station I O sack, the LRK-100.
2.2.5 COMPATIBILITY WITH I/O
The Remote Transfer Interface is compatible with: All register modules. All t6 function IO modules (cannot be used in the CPU rack). All 8 function I/O modules. All 4 function input modules. All 4 function output modules, Series B or later. Bus Expander, Class 8030 Type CR M-115/ 116, Series D or later.
2.3 Environmental
Ambient Temperature Operating: 0°C to 60°C (32° to 140° F). Storage: -40°C to 80°C (-40° to 176°C). Humitidy: 5% to 95% non-condensing.
2.4 Physical
Dimensions (W x H x D}
CRM-230, 232........... 15x 12.8 x 66 in, 3.81 x 32.5 x 16.76 cm.
Weight (approximate) CRM-230, 232 .......-.- 3.0 Ibs! 1.36 kg.
3.0 DESCRIPTION OF HARDWARE
The LTI and RTI modules have seven diagnostic LEDs and a removable terminal strip. A marking area is provided for syste identification.
Click here to view graphic.
Figure 3.1, Local Transfer Interface
Click here to view graphic.
Figure 3.2, Remote Transfer Interface
Page 7
3.1 LED Indicators
The Local and Remote Interface Modules have the following LED indicators:
LOCAL TRANSFER REMOTE TRANSfFER INTERFACE INTERFACE
RUN (green) RUN (green}
HALT (red) HALT (red)
CHANNEL ERROR (red) CHANNEL ERROR (red) PRIMARY (green} 1:0 ERROR (red) BACKUP (green) MODULE ERROR (red} RTC ERROR (red) CPU A (green) MODULE ERROR {red) CPU B (green)
Note that when the Transfer Interface System is powered up and operating with a backup in RUN synchronized with the Primary (bumpless transfer mode). the LED indicators wilt be displayed as follows:
LTI - RUN and either PRIMARY or BACKUP steady ON. RTL - RUN and either CPU A or CPU B steady ON, with complement (CPU A or CPU B} flashing ON and OFF.
LED functions are as follows:
30598-25101
Page 7
LOCAL TRANSFER INTERFACE
When ON indicates the I/O channe! is fully operational and the CPU is accessing the image table (note CPU need not be in RUN). When OFF indicates the module is esther in self-diagnostics or has failed. When flashing (50% duty cycle) indicates that one or more drops have been programmed to halt (bits | through 8 of the LTI I/O channel control register).
When ON indicates one or more drops are shut down due to a communication problem. When OFF indicates all drops are operational. When flashing indicates that a drop has shut down due
When ON indicates the LTI is in Primary status. When flashing (50% duty cycle) indicates a Backup which is not able to become Primary. When blinking (10% duty cycle) indicates a
The complement of the primary LED with the exception of a 90% duty cycle to indicate a
When ON indicates the RTC is not receiving communication, When OFF the RTC is fully operational. When flashing, indicates the RTC is receiving data but the other RTC is not.
Neme Color RUN GREEN HALT RED The complement of the RUN LED. CHANNEL RED ERROR to a failure on the drop (typically a remote bus error). PRIMARY GREEN Backup in “bump transfer” mode. BACKUP GREEN backup in “bump transfer” mode. RTC ERROR RED MODULE RED
When ON indicates the LT] has recognized a bus error and has halted the CPU. Note this does not necessarily mean the LT] itself is bad. When OFF indicates the LTI itself is operational, despite the possibility that other LT! error LED's may be ON.
Page 8
Page 8 30598-251-01
REMOTE TRANSFER INTERFACE
Function
When ON indicates the drop has been initialized and is operating normally. When flashing (50% duty cycle) indicates the CPU is in DISABLE OUTPUTS. When blinking (10% duty cycle) indicates that the LTI halt bit has been set for that drop.
When ON indicates that the drop either has not initialized or has been shut down dut to program control. When flashing (50% duty cycle) indicates the CPU is in DISABLE OUTPUTS. When blinking (90% duty cycle) indicates that the LT] halt bit has been set for that drop.
When ON indicates a communication problem with the LTI. When flashing indicates a Primary is present but that no communication has been established with the Backup.
When ON indicates a problem has been detected on the remote rack (not necessarily an RTI failure). When flashing indicates outputs on the drop have been FROZEN.
When ON indicates a self-diagnostic error. If error is transient, power-cycling the drop will
When ON indicates CPU A is Primary. When flashing (50% duty cycle) indicates CPU A is in ready Backup status. When OFF indicates CPU A is neither Primary nor a ready Backup.
Name Color RUN GREEN HALT RED CHANNEL RED 1/0 ERROR RED MODULE RED allow recovery. CPU A GREEN CPU B GREEN
Same conditions as CPU A LED except applied to CPU B.
3.2 Communication Channels 9.2.1 LOCAL TRANSFER INTERFACE
The LTI has two communication channels, an I/O Channel and a Register Transfer Channel] (RTC), A removable terminal block is used to wire the two pair, twisted, shielded cable to the module.
3.2.2 REMOTE TRANSFER INTERFACE
The RTI has two communication channels, A and B, toconnect to the redundant CPU racks (1/O channel of respective LTIs). The RT] has redundant serial transmitters and receivers, but the remaining RT] circuitry is not duplicated. A removable terminal block is used to connect the two pair, twisted, shielded cable to the module.
3.3 LT! RESTART Pushbutton
The RESTART pushbutton on the front of the LT! module serves two purposes, depending on whether the LTI is in the PRIMARY or BACKUP rack., In PRIMARY RACK
When the LTI is PRIMARY, the RESTART pushbutton may be used to restore communications on the 1/ Ochannel (between an LTland RTI). The RESTART pushbutton is operational on a PRIMARY LTI when all of the following conditions exist:
1. CPU must be running.
2. Communications error must have originated on the 1/O channel.
3, 1/0 FAILURE OVERRIDE bit must be ON. See Appendix B, LT] Control Registers.
4. It must now be possible to establish valid communications to the affected racks, otherwise no change of state will occur.
NOTE: The RESTART button will only restart drops which were shut down due to communication errors or remote bus errors. It will have no effect if a CPU rack error exists.
WARNING Pressing the RESTART button on the front of the LT] module may cause outputs to turn ON or OFF as dictated by the resumption of communication,, In BACKUP RACK
When the LTL is BACKUP, the RESTART pushbutton may be used to regain synchronization of the Register Transfer Channel between the PRIMARY and BACKUP. The RESTART pushbutton is operational on a BACKUP LTI when all of the following conditions exist:
1. CPU must be running.
2. Communications error must have originated on the RTC channel},
3. RTC Failure Override bit must be ON. See Appendix B, LTI Control Registers.
4. It must now be possible to establish valid communications between the LTI's via the RTC cable.
WARNING Pressing the RESTART pushbutton, with all conditions met, will cause registers to be transferred between LTIs. Ladder scans will be stopped during that time for up to approximately 1/2 second. Thus, the restart should not be attempted during a critical operation.