Manual · Square D
Class 8030 Types CRM-230, 232 Local/Remote Transfer Interface System
Manual46 pagesPDF 1.4 MB
Instruction bulletin for the Square D SY/MAX 8030 CRM-230 Local and CRM-232 Remote Transfer Interface modules for redundant processors.
Covers · 2 models
The models it covers
Summary
What is in it
The Square D instruction bulletin for the Class 8030 CRM-230 Local Transfer Interface and CRM-232 Remote Transfer Interface modules, which together form the Transfer Interface System that lets redundant Primary and Backup SY/MAX processors control the I/O system. It covers specifications, LED indicators, communication channels, RTI DIP switches, installation and field wiring, power supplies, operation and rack addressing, system start-up and troubleshooting, with appendices on update times, control registers and error codes.
Its parts
- Introduction
- Specifications
- Description of Hardware
- Installation
- Operation
- System Start-Up
From the manual
Key facts from this manual
Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.
Square D instruction bulletin 30598-251-01 (February 1987) for the Class 8030 Types CRM-230 Local Transfer Interface and CRM-232 Remote Transfer Interface of the SY/MAX programmable controller family. Together they form a Transfer Interface System that lets a Primary and a Backup processor share control of remote I/O and switch over on a fault. It covers specifications, LED meanings, DIP switch settings, installation, wiring, start-up, troubleshooting and error codes, with a 1990 addendum on older CRM230 modules.
- What it is
- Remote Transfer Interface (RTI) module of a Transfer Interface System that lets redundant Primary and Backup processors control the I/O p. 5
- Current draw
- CRM-232: 1.0 Amps @ 5 VDC from the SY/MAX power supply (CRM-230: 1.6 Amps @ 5 VDC) p. 5
- Channels
- CRM-232: two channels, A and B, wired to the I/O channels of the CPU A and CPU B Local Transfer Interfaces p. 8
- Mounting
- CRM-232: CPU slot (slot 1) of a digital or register I/O rack that is a drop, one per drop; not the LRK-100 Control Station I/O rack p. 6, 10
- Processors
- Model 500 (Series M or later) and Model 700 (Series C or later); not Model 300 p. 6
- Transmission rate
- I/O Channel 62.5K Baud; Register Transfer Channel 375K Baud p. 6
- Cable and distance
- Belden 8723 or equivalent two pair, twisted, shielded cable; I/O Channel 2500 feet (762 m) max, Register Transfer Channel 25 feet (7.6 m) max p. 10, 11
- I/O capacity
- Per LTI I/O Channel: 8 drops max, 1024 digital I/O max, 255 registers max; per drop: 128 digital I/O and 127 registers max p. 5
- DIP switches
- CRM-232: six switches on the rear; drop number select, terminator for processor A (switch 2) and processor B (switch 1); switch 6 not used p. 9, 10
- Switchover time
- 3 CPU scans or 60 ms (whichever is greater) with the RTC link intact; 3 CPU scans or 250 ms if not synchronized and the RTC link is not intact p. 6
- Operating temperature
- 0°C to 60°C (32° to 140° F); humidity 5% to 95% non-condensing p. 6
- Dimensions
- 3.81 x 32.5 x 16.76 cm (W x H x D) p. 6
- Weight
- 3.0 lbs (1.36 kg), approximate p. 6
- Keying pin kit
- Optional Class 8030 Type CBP-104 p. 9
What this manual walks you through
- Reading the LTI and RTI LED indicators p. 7, 8
- Using the LTI RESTART pushbutton in the Primary or Backup rack p. 8
- Setting the RTI DIP switches for drop number and terminators p. 9, 10
- Keying slots and placing the modules in the rack p. 9, 10
- Wiring the I/O Channel daisy chain and the LTI-to-LTI Register Transfer Channel p. 10, 11
- Arranging power supplies and branch circuits for redundancy p. 11
- Power-up sequence for the Backup and Primary processors p. 21
- Troubleshooting LED indications that differ at power-up p. 21
- Understanding error code categories p. 34
Good to know
- Remove power from the CPU and all I/O racks before inserting or removing any module or communication cable. p. 9
- A star wiring configuration is not allowed anywhere on the I/O channel; wire it as a daisy chain. p. 10
- If the CPU A and CPU B terminals are not wired consistently for each drop, the RTI gives error code 29510 and does not go to RUN. p. 10
- A 1990 addendum warns that with CRM230 LTI modules Series D3 (no revision) and earlier, outputs may not follow the program after an I/O restart; it advises Series D3 Revision 2.0 or later. p. 45
Questions this manual answers
Which processors work with the 8030 CRM-232?
The Transfer Interface System works with Model 500 (Series M or later) and Model 700 (Series C or later) processors. It does not work with Model 300 processors. p. 6
Where does the CRM-232 Remote Transfer Interface go in the rack?
In the CPU slot (slot 1) of each rack that is a drop, with only one RTI per drop. p. 10
What cable and maximum distance does the CRM-232 use?
Belden 8723 or equivalent. The I/O Channel can run 2500 feet (762 m) and the Register Transfer Channel 25 feet (7.6 m). p. 11
How are the CRM-232 terminator switches set?
Only the last RTI on each LTI I/O Channel has its terminator switch ON: switch 2 for processor A, switch 1 for processor B. All other RTIs have them OFF. p. 10
Why does a new LTI show MODULE ERROR and error code 901?
The bulletin calls it normal for a new LTI, whose storage registers hold random data. Keyswitching the CPU from HALT to DISABLE OUTPUTS or RUN a second or third time clears it. p. 21
Contents
Chapters and sections
Each line opens the PDF at its page.
The whole text · 8 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
The file