registers are used, since the number of registers which can be transferred at the end of any one given scan is 32.

5.4.4 PROCESSOR SCAN SYNCHRONIZATION

To ensure the virtually bumpless transfer from a Primary to a Backup system, the processor scans are synchronized. There-after, both processors receive the same RTI input data simultaneously, and programmed rungs are solved identically, Without this synchronization, processor scans may not be identical due to independent processor scan times ordifferent Primary or Backup programs.

Processor scans are synchronized via the Register Transfer Channels of the LTI modules. Through the RTC, the processor that finishes its scan first is delayed fora period of time to allow the lagging processor to complete its scan. After both scans have been completed, both processors will begin scanning simultaneously, This scan hold or delay time is programmable within limits.

While the rack addressing in both Primaryand Backup must be identical, the ladder diagram programs do not, and the scan hold time is programmable to accommodate different program lengths within the Primary and Backup processors. However, since it is good programming practice to minimize the difference lengths between programs, program differences such as shutdown routines should be pla utines that are only scanned when needed. Seq Appendix F.3)/Different Primary; Backup Systems.

Modifying Scan Hold Time

The Scan Synchronization Register is defined as the third register assigned to the RTC (Channel 2, Drop ]}. The number that resides in this Scan Sync Register will determine exactly how long a faster scanning processor will wait for the lagging processor before it resumes scanning.

The value in the Scan Sync Register can be modified from 3 to 500, This value will determine the number of milliseconds {ms) a faster scanning processor will be held for the lagging processor. If a number is notentered into the Scan Sync Register, the scan hold time will default to 100 ms (register default value of 0). Anentered value outside the acceptable range will default to the closest limit (5 or 500). Entered values will round to the next 5 ms increment.

Loss of Synchronization

If the programmed scan hold or delay time has elapsed and the lagging processor has not yet completed its scan, the Backup processor will fall out of synchronization with the Primary. The Primary will continue scanning and controlling the [/O, but will not be able to perform an End of Scan Transfer unti! the Backup re-synchronizes with a Startup Transfer.

Should the Primary and Backup systems fall out of synchronization, the Backup processor will HALT unless the RTC FAIL- URE QNVERRIDE hit ihit 13) of the RTC Control Register is set (see] Appendix B.4.3. LTI Control Registers).

Bit 15 of the RTC Control Register, called the RE-SSYNC bit, can be used to enable an unsynchronized Backup to request a Startup Transfer to re-synchronize with the Primary. If the Backup successfully re-synchronizes, it will attain a full ready Backup status. If the re-sync attempt is unsuccessful, the

Backup will continue to try 19 chronize as long as its RE- SYNC bit is set ON (i). See Appendix B.4.3] Note that if a fault

30598-251-01 Page 19 should occur in the Primary while the Backup is trying to re-synchronize, a “bump transfer” will occur.

Assuming the TEST bit (bit 14) is cleared. by setting ON the RTC Failure Override bit (bit 13) and the Re-Sync bit (dit 15), the user will allow the Backup to temporarily fall out of sync (for the sake of preserving redundant control} but at the same time attempt to re-establish system synchronization.

NOTE: In deciding whether or not to set the Re-Sync bit, the user must be aware that each re-sync attempt with a

Startup Transfer wi!l delay the Primary system. See Section 5.4.2.

In order for the Primary and Backup systems to attempt to re-synchronize with a Startup Transfer, the following conditions must be true:

1. Backup TEST bit must be reset OFF (0).

2. Backup RTC FAILURE OVERRIDE bit must be set ON (1). 3. Backup RE-SYNC bit must be set ON (1).

4. Proper RTC communication must exist.

The following examples illustrate how to automatically re-synchronize systems. he examples assume address assignments as made inj Section 5.3.5] whereby the Scan Sync register is defined as $75 (the third register assigned to the RTC).

LET S75 = 10

8161-13

{f \ eed

RTC FAILURE OVERRIDE 8161-15

{ \ | ed

4 RE SYNC

The first rung establishes that a faster scanning processor will wait 10 ms for a lagging processor. This rung should be programmed in both the Primary and Backup processors. If this rung were not programmed (and S75 = 0), the faster processor would wait 100 ms (default time) for the lagging processor.

The remaining two rungs set the RTC FAILUREOVERRIDE and RE-SYNC bits. Note that it is assumed the TEST bit (8161-14) is reset OFF (0). If the lagging processor doesn’t reach the end of its scan within 10 ms of when the first processor does, a request for a “Startup Transfer” will be initiated in order to re-synchronize.

Note that the above rungs assume that only one LIT module resides in each processor rack. Additional LTI modutes would require additional rungs to re-synchronize the entire system (i.e., RFC Failure Override and Re-Sync coils would be 8158-13 and 8158-15 respectively for the second LTI, etc.}. For multiple LT] systems, all LTi’s will perform a Startup Transfer whenever any one LTJ requests it.

Considering some of the potentially adverse effects on the scan time of the Primary which can result from continuously enabling Startup Transfers, the next example illustrates rungs which can be used to allow the Backup to attempt to re-synchronize no more than three times before halting.