The text of a manual · part 6 of 8
Class 8030 Types CRM-230, 232 Local/Remote Transfer Interface System, pages 20 to 28
Pages 20 to 28 of 46: 6: System Start-Up; Appendices; Addendum (251-02B)
The original document is the PDF (1.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Square D 8030-CRM-232 and Schneider 8030-CRM-232
Page 20
Page 20 30598-251-01
109-1 8161-13 | I { \ | | | ed RTC FAILURE OVERRIDE 6161-24 CTA | ) | r 1 J UP STARTUP TRANSFER $500 } DWN 109-2 rt J | CLR I 1 1 - 109, _ 01 109-2 | { \ _| | XY / | 109-1 8161-15 | 1+ i \ | | | weed | RE-SYNC
The logic keeps track of the number of Startup Transfer requests executed by monitoring $8161-24. After the third attempt, RTC FAILURE OVERRIDE and RE-SYNC are disabled: consequently the Backup will now shut down in the event synchronization is lost.
NOTE: For multiple LTI systems, the SFARTUP FRANS- FER bits for aff of the LTI’s should be run in parallel to one internal coil, since only the LT] that is initiating the Startup Transfer will set its bit.
Control Register bits can also be used to enable a Primary processog ckup from initiating a Startup Transfer, See]Appendix F.2] Primary/ Backup Bit Exchange.
5.4.5 PRIMARY /BACKUP READ/WRITE BIT EXCHANGE
In the fourth register assigned to the Register Transfer Channel (S76 in the example offSection 5.3.5] eight bit locations are used in order for the Primary and Backup processors to write bits to each other at the end of every scan. These bits are transferred back and forth as long as the Primary and Backup are both synchronized. The bits are transferred over the RTC; thus if the RTC connection is broken, the bits will no longer be updated.
These bits can be used for user-controlled interaction between the Primary and Backup processors. See[Appendix F.2 Primary/ Backup Bit Exchange, for programming examples.
6.0 SYSTEM START-UP
6.1 Preliminary Considerations
This section is intended to be an independent step-by-step guide to help the user get the Transfer Interface System (TIS) up and running with a minimum of complications, To this end, we recommend that the user first become familiar wit acy ng oth ons of this bulletin, in particula Sections 3 S bn [Appendix B
Before applying power to the TIS the following precautions must be taken:
1. Check to see that the system is installed as described in Section 4 (Installation). Jn particulat_insure that: a) the DIP switches are set correctlyj(Section 4.4)
b) the RTC and 1/O channels are wired correctly (Section
2. Check to see that all field wiring is correct.
3. Insure that both processors have their keyswitches in the BALT position.
4. Ensure that all RF! racks in the system are always powered up prior to the CPU racks.
6.2 Rack Addressing And Programming
After observing the above considerations, in particular that both processors are keyswitched to HALT, the user can now apply power to the TIS. At this stage the user does not need to be overly concerned with the status of the LED indicators; however both processor HALT indicators should be flashing ON and the HALT indicator of the RTIs should be ON steady.
The user can now enter addcessing™ and the ladder program for the TIS ( ee Section 5.3, Rack Addessing. for a detailed example of “rack addressing”). It is recommended to perform a CLEAR ALL to memory prior to entering “rack addressing” and the ladder program. It isalso recommended, in order to expedite the initialization process, to just enter a simple ladder program at this point. Later on, once the TIS is up and running and proper hardware operation has been verified, a comprehensive program can be entered.
CAUTION
In order to promote user familiarity and avoid complica~ tions in Startup, the user should not set ON any control register bits at this point, either via the DATA mode or the ladder program.
Page 21
Once “rack addressing” and the ladder program have been entered into beth processors (same “rack addressing” for both), power down both processors in preparation for the succeeding steps khelow. DO NOT at this point put the processors in RUN.
6.3 Power Up Sequence
Now that the processors have “rack addressing” and ladder programs toaded into them, the Power Up Sequence can be initiated, The user is advised to perform the power up sequence as described below, to insure correct initialization of the TIS. Along with insuring correct initialization this sequence will determine the Primary/Backup status of the system. See Appendix C
In the following sequence the user will power up the processors separately and check them out by observing the status of the LED indicators, and then put both processors in operation for redundant control.
NOTICE
When initially keyswitching aCPU that has a new “out of the box” LTI installed to DISABLE OUTPUTS or RUN, the processor will remain in HALT and the LTI will indicate a MODULE ERROR, The processor error register (8175) will identify the LTI in error, and the LTI error register will contain error code 901. This isa normat occurrence, reflecting the fact that the LT storage registers are corrupt (contain random data). Keyswitching the CPU from HALT to DISABLE OUTPUTS or RUN a second {or third) time will clear the error.
Proceed with the Power Up Sequence:
1. With both processors powered down, now power up the processor that will be designated Backup, and keyswitch it to DIABLE OUTPUTS. Verify by the status of the LED indicators, shown in Figure 6.1, that the unit is operating correctly. Note that when switching processors from one state to another the LED indicators will momentarily change states before stabilizing.
If an LED display other than indicated ir] Figure 6.1 pccurs, refer to the above NOTICE. If trouble petstStsyTerer to the troubleshooting Section 6.4,
2. Once the unit is operating correctly in DISABLE OUT- PUTS, the unit can be further verified to be operating correctly by keyswitching it to RUN. Be reminded that when the processor is in RUN, it controls external L/O via the ladder program. The ¢ocre BP indication when the unit js in RUN is shown inj Figure 6.2.
| PROCESSOR LTle RTs
IRUN -. flashing] RUN, ON RUN, flashing PRIMARY, ON HALT, flasning
RTC ERROR - ON|CHNL ERROR, flashing
CPU Aor &, ON
Figure 6.1 DISABLE OUTPUTS LED Display
PROCESSOR LTls RTis
RUN, ON RUN - ON RUN, ON
PRIMARY, ON HALT, OFF
RTC ERROR, ON|CHNL ERROR -- flashing CPU A or B - ON
Figure 6.2 RUN LED Display
30598-25101 Page 21
3. Once the unit designated to be Backup is operating properly, power it down in preparation for the succeeding steps.
4, With the processor designated to be Backup powered down, apply power to the processor to be designated Primary, then keyswitch it to DISABLE OUTPUTS. As ify by the status of the LED indicators, shown in[Figure 6.1} that the unit is operating correctly.
If an LED display ot her than indicated in Figure 6.1 occurs, refer to the NO If trouble persists, refer to the Troubleshooting Section 6.4,
5. Once the unit is operating correctly in DISABLE OU1-
PUTS. keyswitch it to RUN and verify by the status of the LED indicators, shown in] Figure 6.2) that the unit is operating correctly.
6. After the processor designated to be the Primary is operating correctly in RUN, leave it powered up and in RUN im preparation for the following steps.
7. With the Primary in RUN (for at least 10 seconds), apply power to the Backup and keyswitch it to RUN. Ifthe Register Transfer Channel communication link is connected and operating correctly, the “RTC ERROR” LED on the Primary will tarn OFF and the Backup will initialize and go into RUN. Ifthe TIS is operating correctly there should be no ERROR indicators illuminated at this time; onthe RTIs, CPU A or B will be ON steady with the complement CPU A or B flashing.
8. Now that the Transfer Interface System is up and running, a more comprehensive ladder program can be entered and appropriate contro] bits set to adapt the TIS to the particular user application.
6.4 Troubleshooting
In the Power-Up Sequence the user verifies correct operation of the TIS by observing the status of the LED indicators. If the LED indications are not as illustrated in the Power-Up
Sequence, the useris_advised to refer to Section 3,1 (LED Indicators} and to] Appendix E {Error Codes) for help. It should be noted that the illustrated LED indications for the power-up sequence assume “rack addressing” matches existing external I/O.
Some typical causes for the LED indications to be different than as illustrated in the Power-Up Sequence are described below:
1. When initially keyswitching a CPU that has a new “out of the box” LTI installed to DISABLE OUIPUTS or RUN, the processor wi! remain in HALT and the LT] will indicate a MODULE ERROR. The processor error register (8175) will identify the LT1 in error, and the LTI error register (S8163 if the first LT!) will contain error code 901. This isa normal occurrence, reflecting the fact that the LTI storage registers are corrupt (contain random data}. Keyswitching the CPU from HALT to DISABLE OUTPUTS or RUN a second (or third) time will clear the error.
2. The I/O LED indicator on the processor will iltuminate if “rack addressing” includes drops that don’t actually exist, are not wired, or are not communicating for some reason. Alsa, on the affected 1-TIs the HALT, CHNL ERROR, and MODULE ERBQBuindicatars will be ON. Interrogation of the error coded (Appendix £) will reveal the drop in error.
Page 22
Page 22 30598-251-01
3. The RTI HALT and CHNL ERROR LED indicators will remain ON steady, regarditess of the keyswitch position of the processor, . if the RTI is not communicating with the LTI (e.g., RTI not wired).
4. The RT) HALT, CHNL ERROR, and CPU A (or B) LED indicators will remain ON steady, regardless of the keyswitch position of the processor, if the RT} drop number is incorrect (e.g.. RTI DIP switch setting does not match an existing drop in “rack addressing”).
§. Bear in mind that, since these modules annunciate system errors that may actually originate in another module, error
LEDs on the LTI or RTI themselves do not necessarily indicate a failure in these modules. If beset by erratic and seem-ingly contradictory indications, we suggest following a pattern which includes power-cycling all remote and CPU racks with the CPU keyswitch in HALT. This should be followed by turning each of the CPUs to RUN, accompanied by the user recording error code information as described in Appendix E. Useful information is contained in Register 8175 as welt as the apropriate LTI error registers (S8163, S8160, etc.). Registers 8183 and 8184 may also contain relevant information, depending on the nature of the failure. The procedures of Appendix E can then be followed to help narrow down the source of the problem.
APPENDIX A, LTI/RTI UPDATE TIME
A.1 General Information
This appendix provides equations for calculating the LTL/ RTI update time. Update time refers to the time required to pass information in either direction between the LTI image table and the RTI image table and should not be confused with throughput time. Throughput time, often called system response time, is the time elapsed from the actuation of an input device to the occurrence of an output action, Throughput time must also include [/O module response time and CPU scan time. Further information regarding throughput (overall system response) is covered in the Planning and Installation Guide Instruction Bulletin #30598-175-XX.
A.2 Drop Update Time
One of two equations are used to calculate drop update time. For the purpose of these equations, drops will be put into two categories, digital and register. The digital drop is a pure digital drop (8 or less registers) with no register modules. The register drop contains register modules or a combination of register and digital [/O modules.
A.3 Update Time Equation Variables
D R
Total digital drops on the channel. (0-8)
Total register drops (or digital/ register drops) on the channel, (0-8)
DR = Total register addresses assigned to all digital drops.
(0-64)
RR = Total register addresses assigned to all register drops. (0-255)
X = Register addresses assigned to the drop being evaluated.
(1-8). If more than 8 registers are assigned, use X = 8. A.4 Drop Update Time Equations
Digital Drop Update Time (ms) = 2.31 D+ DR + X + 0.79
Register Drop Update Time (ms) = 2,31 D+ DR + 3.1SR + 1.24(RR + X) + 1.52
Actual performance times may be better than calculated for channels with many registers due to improved message efficiency.
Page 23
30598-251-01 Page 23
APPENDIX B, LT! CONTROL REGISTERS
B.1 General information
Control registers 8001 through 8163 (contained in the processor) are used to monitor, and in some cases, contro] the Transfer Interface System (TIS). These registers reflect the condition of the TIS and contain information about registers and 1/O modules.
The 8030 CRM-230 Local Transfer Interface (LTI) is a two channel module which utilizes three registers to communicate directly with the processor (CPU). The first register is an error code register. The second is a control register for channet I (1/0 Channel). The third is a control register for channel 2 (Register Transfer Channel-RTC). The number of contro] registers used to monitor a particular TIS is based on the number of LTI modules in the system. Each matched pair of LTI modules uses three control registers.
Each register consists of two parts, a DATA field and a STATUS field. The DATA field can be programmed by the user for control functions. The STATUS field, as the name implies, is used just to monitor status of specific system conditions.
B.2 Register Allocation
The first matched pair of LT modules in a Transfer Interface System have register $8163 designated as their error code register. The 1/O Channel (channel I} control register is $8162. The RTC (channel 2) controt register is $8161.
Figure B.t fists the error code, 1) O Channel, and RTC contro!
Tegisters tor Transfer Interface Systems using up to seven matched-pair LTI modules.
The contents of the error code registers are discussed in greater detail in) Appendix Ej Error Codes. The contents and format for the channel control registers follows.
Register LTi Location Function
$8163 First (Right of CPU) Error Cade
$8162 First 1/O Channel (1) Contro] Data & Status $8161 First RTC Channel (2) Control Data & Status $8160 Second (Right of first LTI Error Code
$8159 Second module) 1/0 Channel (1) Control Data & Status $8158 Second RTC Channel (2) Control Data & Status $8157 Third (Right of second LT! Error Code
88156 Third module} 1/0 Channel (1) Control Data & Status S8155 Third RTC Channel (2) Control Data & Status $8154 Fourth (Right of third LTI Error Code
$8153 Fourth module) 1/O Channel (1) Control Data & Status $8152 Fourth RTC Channel (2) Control Data & Status S8151 Fifth (Right of fourth LTI Error Code
$8150 Fifth module) 1/0 Channel (1) Control Data & Status $8149 Fifth RTC Channel (2) Control Data & Status $8148 Sixth (Right of fifth LTI Error Code
$8147 Sixth module) 1/0 Channel (1) Control Data & Status $8146 Sixth RTC Channel (2) Control Data & Status $8145 Seventh {Right of sixth LT] Error Code
88144 Seventh module) [/O Channel (1) Control Data & Status §8143 Seventh RTC Channel (2) Control Data & Status
Figure B.1, LT{ Control Register Assignments
Page 24
Page 24 30598-251-0I
B.3 LT? Contro! Register, 1/0 Channel
6.3.1 1/0 CHANNEL DATA FIELD filisfis}i3fizfuf[woflof{s[7}o6]s]f4]{3]2 [1]
SPARE HALT DROP 4! AUTO RESTART HALT DROP #2 SPARE HALT DROP #3 1;0 FAILURE OVERRIDE HALT DROP #4 SPARE HALT DROP #5 SPARE HALT DROP #6 TXFT HALT DROP #7 FREEZE HALT DROP #8 1/0 Channel, Data Field Control Register Bk Name Description | Halt Drop #} When OFF (0) the drop will operate as the ladder program indicates. 2 Halt Drop #2 When ON (1) the drop will be shut down. 3 Halt Drop #3 1. Input status still valid. 4 Halt Drop #4 2. Outputs turn OFF. 5 Halt Drop #5 3. Register 1/O clear (depending upon module type). 6 Halt Drop #6 4, Adrop shutdown under Primary control wil] not cause a transfer from Primary 7 Halt Drop #7 to Backup. 8 Halt Drop #8 9 FREEZE When ON (1) and a loss of transmission, transmission error, or CPU rack error occurs, all outputs are maintained in their last state. This bit is ignored ina Primary LT] if a running Backup is able to take control. 10 TXFYT Transmission Fault Tolerance determines whether three or ten consecutive trans- (Transmission Fault mission errors are allowed to occur before a channel error is acknowledged and an Tolerance) attempt is made to transfer to Backup. OFF (0) = Three errors ON (1) = Ten errors Tt Spare 12 Spare 13 1/0 FAILURE When OFF (0) and drop error occurs, |/O channel wilt shut down and processor OVERRIDE will HALT. When ON (1), and, Backup is ready: TIS will switch control to the backup rather than run with the channei in error {thus ignoring the 1/O Failure Override bit). Backup is not ready: Allows the 1/O channel to continue operating if a drop error occurs. 14 Spare 15 AUTO RESTART When ON (i) allows the [/O Channel to attempt to reestablish valid communications with any drop shut down due to transmission errors (bit 13 must be set to enable bit 15 to be recognized). This control bit performs the same function as the RESTART button on the primary LTI module. This bit is only active in a Primary system with no Backup; otherwise contro] will be switched to the ready Backup. 16 Spare
Figure B.2, LTI1/O Channel Control Register Data Field
Page 25
30598-25101 -Page 25
8.3.2 1/0 CHANNEL STATUS FIELD
[ 32 | 31 | 30 | 29 | 28 | 27 | 26 | 25 | 24 [ 23 | 22 | 21 | 20 J 19 | 18 [17 |
LT] INTERNAL CHANNEL USAGE DIAGNOSTICS COMPLETE LTI INTERNAL, - - - CHANNEL USAGE INITIALIZATION COMPLETE LTI INTERNAL USAGE, - - - - CHANNEL ADDRESSING COMPLETE SPARE SPARE DROP #8 ERROR SHUTDOWN, - DROP #1 ERROR SHUTDOWN DROP #7 ERROR SHUTDOWN, - - - - DROP #2 ERROR SHUTDOWN DROP #6 ERROR SHUTDOWN, - - - - _ - _ - - DROP #3 ERROR SHUTDOWN DROP #5 ERROR SHUTDOWN DROP #4
ERROR SHUTDOWN
1/0 Channel!, Status Fieid
Control Register Bi Name ; Description 17 Channel Diagnostics When ON (1) Complete LTi Channel has completed its diagnostics. 18 Channel Initialization When ON (1) Complete 1. RTIs have completed their diagnostics. 2. Valid LTE/RT] communication. 3. Image table updating sequence complete. 19 Channel Addressing When ON (1), indicates the CPU has loaded valid rack addressing information into Complete the LTI. 20 Spare 2) Drop #1 Error Shutdown 22 Drop #2 Error If drop has been rack addressed: Shutdown 23 Drop #3 Error When OFF (0) drop is operating. Shutdown When ON (1) drop is shut down due to error. 24 Drop #4 Error Shutdown 25 Drop #5 Error If drop has NOT been rack addressed: Shutdown 26 Drop #6 Error When OFF (0) no drop exists. Shutdown When ON (1) drop exists without addressing. 27 Drop #7 Error Shutdown 28 Drop #8 Error Shutdown 29 Spare x» Internal Usage 31 Internal Usage 32 Internal Usage
Figure B.3, LT) |/O Channe? Controt Register Status Field
Page 26
Page 26 30598-251-01
8.3.3 DETAILED DESCRIPTION OF LTI 1/0 CHANNEL CONTROL BITS
The LTI 1/O Channel control register, bits 1-16, are initially reset OFF (0) when the LTI is installed. Once altered by programming equipment, data entry, or by the ladder program. these bits will retain their state until altered again.
HALT DROP Bits (1-8)
Any drop onan I/O Channel may be programmed to halt (turn OFF all of its associated outputs). This is done by setting its LTI HALT DROP bit ON (1). Adrop programmed to halt will have valid updated input status contained within the LTI image table. (Since this halt condition is generated by the user, no error lights are turned on, no transfer takes place, and the CPU will remain in RUN.)
FREEZE Bit (9)
The FREEZE bit is ignored in a Primary LTI if a running Backup is able to take control. Assuming the Backup is halted, the FREEZE bit functions as follows.
When the FREEZE bit (bit 9) ‘is set ON (1), all outputs on the 1/O Channel will retain their last state, ON or OFF, in the event of any of the following conditions:
1. A Communication error at a drop (e.g., broken cable).
2. The CPU HALT bit ($8176-1) is set ON (1), (i-e., CPU error or programmed halit.}
3. Power is lost at the local (CPU) rack,
Although the FREEZE bit may be set ON (1), the operation of the FREEZE function depends upon the detected error. In the following cases, the DROPS WILL NOT BE FROZEN, but reset OFF (0), regardiess of the state of the FREEZE bit:
1. Drop with internal error. (i.e., power loss, faulty RTI, read-after-write or bus error.)
2. CPU turned into HALT via keyswitch or setting the CPU HALT/RUN bit, $8716-3.
NOTE: The CPU must not have’been halted by an error prior to these actions. If the CPU is halted due to an error, turning the keyswitch to HALT will not reset frozen drops.
Turning OFF Frozen Drops
1. Power cycling a drop with frozen outputs will reset (OF F)all the outputs, regardless of the state of the processor.
2. When valid communication exist, setting a Primary CPU HALT bit (S8176-3) ON (1) will result in turning OFF frozen outputs,
Restarting Frozen Drops
1. Place the CPU in either RUN or DISABLE OUTPUTS, by either turning the CPU keyswitch or clearing the CPU HALT bit (58176-3), will allow all drops with valid communications to restart in accordance with the user program.
2. Power cycling the CPU when it is in either RUN or DIS- ABLE OUTPUTS will restart frozen drops.
3. If the CPU is still running (because the [/O FAILURE OVERRIDE bit was ON {1} ), then turning on the AUTO RESTART bit (bit 15) will restart the frozen drop(s) if valid communications now exist between the CPU and drop(s).
4, Pushing the RESTART button on the LTI (assuming CPU and communications are fully operational and LTI 1/O FAILURE OVERRIDE bit is set ON (1) ) will also restart frozen drops.
TRANSMISSION FAULT TOLERANCE Bit, TXFT (10)
If LTI to RTL communication is disrupted (in environments with extreme noise for example), the TIS will attempt to establish a valid data transmission three times before acknowl-edging a communication error and attempting to switch control to the Backup system. Should a communication error be acknowledged in a Primary without a ready Backup, the TIS will take action according to the status of the 1/O FAILURE OVERRIDE bit (bit 13).
Transmission Error Detection
Two types of data transmission error detection methods are used in the LT1/RT1 communication link. The first detection method counts the number of times a specific block of data is determined to be invalid. The second method counts the number of consecutive blocks of data which are determined to be invalid. The cumulative values for each type of transmission error are kept internally by the LT] and RTI modules. Whena good transmission occurs on a communication channel, the respective transmission error counters are reset to zero.
The user has the option of increasing the transmission fault tolerance level from three to ten transmission errors. This is done by setting the Transmission Fault Tolerance bit ON (1). Be aware that setting the number of transmission errors to ten will require additional time for the system to recognize a transmission error and either attempt a transfer from Primary to Backup or shut down a Primary that does not have a ready Backup.
Note that the transmission fault tolerance bit only affects the operation of the system when invalid data is detected. Another type of error, communication loss, is detected by interna] timers in the system. A pause in communication of greater than 3ms will cause an error to be generated. Therefore, if there is a complete loss of transmission due to cable damage or hardware malfunctions, the TIS will attempt to transfer contro! from a Primary to Backup almost immediately.
When the LT] acknowledges excessive transmission errors (more than the TXFT) the TIS wiil switch contro! frofn Primary to Backup. Should the Backup not be able to take control, the system will shut down unless the 1/O FAILURE OVERRIDE bit (bit 13) is set ON (1).
1/0 FAILURE OVERRIDE (Sit 13)
The purpose of the I/O FAILURE OVERRIDE bit is to allow portions of the TIS to continue operating in the presence of an I/O error. The actual response of the system depends on two major factors, the type of 1/O error involved and whether there is a ready Backup available.
Page 27
There are 4 major types of 1/O errors, 1. Distorted communications (typically caused by noise}.
2. Complete loss of transmission (usually caused by hardware failure or cable problem.)
3. Power Loss at remote drop, 4, Remote drop bus etror.
The system responds in the same manner for the first 3 types of errors. For remote drop bus errors, the response is different.
System Response With A Ready Backup
Hf there is a Backup “online” (i.e., one that is in full run and able to take control) and the Primary detects one of the first 3 types of 1/O errors, the system transfers control to the Backup unit regardless of the setting of the Primary’s 1/O FAILURE OVERRIDE Bit. The former Primary then goes into HALT with an 1/O error. If the error remains, the new Primary will continue to run or go into HALT in accordance with the condition of its 1/O Failure Override bit.
If, however, the 1/O error isa remote drop buserror, the system ~ responds differently. In that case, a transfer is not made. Instead, the Backup goes to HALT withan I/O error regardless of the setting of its 1/O FAILURE OVERRIDE Bit. The original Primary then either continues to run if fs 1/O FAILURE OVERRIDE Bit is set (1) or it will also go to HALT with an I/O error if the bit is cleared (0). The system responds differently to remote bus errors because they represent a more serious failure of the remote I/O, Transferring control to the Backup could cause unpredictable I/O operation, so the Backup is forced to HALT.
System Response When Backup Is Not Ready
A Backup may not be “ready” for a number of reasons. Its power may be off, it may have been manually keyswitched to HALT, its TEST bit may be set, or it may be in HALT because of some error. Whenever the Backup is not ready to take over, the Primary responds to all four types of I/O errors in the same manner. If its I/O FAILURE OVERRIDE Bit is cleared (0) when an 1/0 error is detected, the processor will go to HALT with an I/O error. If the bit is set ON (t), the drop in error will shut down, but the CPU will continue to RUN and allow the rest of the 1/O channels to continue operating.
The I/O FAILURE OVERRIDE bit for the first LTI can be set on (1) with the following rung programmed in the ladder program.
8162-13
{ \ | XZ 1/0 FAILURE OVERRIDE
If 1{O FAILURE OVERRIDE is desired, this rung must be programmed as the first rung in the ladder program. Anexcep-tion to this rule is if the timed interrupt or any other feature
30598-251-01 Page 27 which requires programming the special] TLET $8165 rung is used. For this exception, the 1/O FAILURE OVERRIDE bit should be set by the very next rung. !f multiple 1/O FAILURE OVERRIDE bits need to be set via the ladder program, their corresponding rungs should be first in the program or immediately follow the special TLET $8165 rung,
CAUTION
Care must be taken whenever the 1/O FAILURE OVER- RIDE bit is set ON (1), because the system will continue to operate when drop errors occur, However, with the 1/O Failure Override bit set, it is also possible to selectively halt drops through ladder programming by setting ON (1) individual HALT DROP bits.
NOTE: The 1/O FAILURE OVERRIDE bit, which controls the operation of the I/O Channel, should not be confused with LURE OVERRIDE bit described in Section B.4.3
AUTO RESTART Bit(15)
If a drop has been shut down due toa transmission error, setting the AUTO RESTART bit (bit 15) ON (1) will allow the LTI to automatically attempt to reestablish valid communication to that drop (provided the processor is operating in RUN or DIS- ABLE OUTPUTS mode). In order to keep the processor Tunning under error conditions, the 1/O FAJLURE OVER- RIDE bit (bit 13) must be ON (1).
The AUTO RESTART bit enables the system to recover froma transmission error without pushing the RESTART button. This bit acts in the same manner as does the RESTART button on the front of the respective LT] module with one exception, drops with remote bus errors (which have subsequently been cleared) can be restarted with the Restart pushbutton but not with the Auto Restart_bit. For more information on the RESTART button, Section 3.3)
NOTE: The AUTO RESTART bit is only active in single processor control (Primary without Backup); otherwise, control will be switched to the Backup before a restart is attempted by the Primary.
DROP ERROR SHUTDOWN Bits (21-28)
DROP ERROR SHUTDOWN bits are used for diagnostic purposes. They are turned ON (1) when their respective drops shut down. When used in conjunction with having the 1/O Failure Override bit set ON (1), these bits can be extremely useful in implementing ladder control programs to effect user defined contro] functions, such as selective shut downs of the individual drops, as opposed to having all drops shut down.
NOTE: The DROP ERROR SHUTDOWN bit will be displayed as ON (1) for a drop that is present but not defined in the rack addressing. The drop error bit of an undefined drop bening ON (1) will not affect the shutdown operation of the TIS.
Page 28
Page 28 30598-251-01
B.4 LTI Control Register, Register Transfer Channel
8.4.1 RTC DATA FIELD fielisliafifwftufwls{[s[7foe[s]4a[3]2 [1 } EOS Transfer Spare Register Spare RE-SYNC Spare TEST Spare RTC FAILURE OVERRIDE Spare Spare Spare Spare Spare Spare Spare RTC Data Field Control Register Bit Name Description I Spare 2 Spare 3 Spare 4 Spare 5 Spare 6 Spare 7 Spare 8 Spare 9 Spare 10 Spare HW Spare 12 Spare 13 RTC FAILURE When set ON (1) ina Backup LTI, will allow Backup processor to continue to RUN OVERRIDE despite losing synchronization with the Primary. This bit is active only in the Backup LTI. 14 TEST When set ON (I) ina Backup LT], the LT] (upon a HALT to RUN transition) will not request a Startup Transfer from the Primary processor. 15 RE-SYNC When set ON (1) ina Backup LTI that is in RUN, the Backup system will attempt a Startup Transfer to re-synchronize the TIS. To enable the RE-SYNC bit, the RTC FAILURE OVERRIDE bit must also be set ON (1) and the TEST bit must be reset OFF (0). 16 EOS TRANSFER When set ON (J) in a Backup LTI that is in RUN, the Backup LTE will request an End of Scan Transfer of 32 registers. The block of 32 registers to be transferred is determined by the value residing im the End of Scan Transfer Register (second register assigned to the RTC).
Figure B.4, RTC Control Register Data Field